Plan Review Details - Permit 06030995
Plan Review Stops For Permit 06030995
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-06-08 Cont ID  
Sent By rmcdouga Date 2006-06-08 Time 16:08 Rev Time 0.00
Received By rmcdouga Date 2006-06-08 Time 16:08 Sent To  
Notes
2006-06-08 00:00:00PERMIT FOR ROOF WAS HELD UNTIL REVISION
 TO CHANGE ROOF DECK ON BUILDING WAS
 APPROVED. SEE MASTER PERMIT 04040562 FOR
 RAS 117 CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-10 Cont ID  
Sent By rmcdouga Date 2006-05-10 Time 09:39 Rev Time 0.00
Received By rmcdouga Date 2006-05-10 Time 07:15 Sent To  
Notes
2006-05-10 00:00:00DENIED
  
 1) THE PRODUCT APPROVAL SUBMITTED FOR
 THE FLAT ROOF IS A SYSTEM FOR FOR STEEL
 DECKS. THE BUILDING PLANS FOR THIS
 STRUCTURE SPECIFY A CONCRETE SLAB OVER A
 VENTED METAL DECK. RIGID INSULATION IS
 SPECIFIED ON TOP OF THE CONCRETE DECK.
 SUBMIT A PRODUCT APPROVAL FOR COVERING
 AN INSULATED CONCRETE DECK. THE PRODUCT
 APPROVAL SUBMITTED WITH THE BUILDING IS
 JOHNS MANVILLE MODIFIED BITUMEN OVER
 CONCRETE DECKS.(FL#644 AND NOA#
 03-0212.07) IF YOU SUBMIT A DIFFERENT
 PRODUCT APPROVAL A REVISION FEE WILL BE
 ADDED TO THE PERMIT FEE.
  
 2) SPECIFY THE METHOD OF ATTACHMENT THAT
 WILL BE USED TO INSTALL THE CLAY ROOF
 TILES. CIRCLE THE FASTENING SYSTEM IN
 THE PRODUCT APPROVAL. THE PRODUCT
 APPROVAL SUBMITTED FOR THE TILE ROOF
 WITH THE BUILDING PERMIT IS MONIER
 LIFETILE MISSION BARREL CONCRETE ROOF
 TILE NOA# 02-1211.07. IF YOU WISH TO
 CHANGE TILES A REVISION FEE WILL BE
 ADDED TO THE PERMIT FEE.
 NOTE: MEAN ROOF HEIGHT IS 54'9". 6/12
 SLOPE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-24 Cont ID  
Sent By rmcdouga Date 2006-03-24 Time 10:18 Rev Time 0.00
Received By rmcdouga Date 2006-03-24 Time 08:08 Sent To  
Notes
2006-03-24 00:00:00DENIED
  
 1) THE PRODUCT APPROVAL SUBMITTED FOR
 THE FLAT ROOF IS FOR STEEL DECKS. THE
 BUILDING PLANS ON FILE INDICATE A
 CONCRETE DECK.
  
 2) SUBMIT RAS 117 CALCULATIONS FOR THE
 FLAT ROOF SYSTEM ENHANCED FASTENING.
  
 3) SPECIFY THE METHOD OF ATTACHMENT THAT
 WILL BE USED TO SECURE THE CLAY TILE.
 CIRCLE THE APPROPRIATE FASTENER TYPE ON
 THE NOA. NOTE: THE ATTACHMENT RESISTANCE
 MUST MEET OR EXCEED THE UPLIFT MOMENT
 REQUIRED FOR THE STRUCTURE.
  
 4) PRODUCTS FOR FLAT ROOF AND CLAY ROOF
 TILES ARE NOT THE SAME AS THE ONES WITH
 THE APPROVED PLANS. A REVISION WILL BE
 REQUIRED.
  
 5) THE MASTER PERMIT LISTS IMPACT
 ROOFING AS THE ROOFING SUBCONTRACTOR. IN
 ORDER TO GET A PERMIT FOR THE NEW
 CONTRACTOR, TWO OPTIONS ARE AVAILABLE. A
 NOTARIZED LETTER FROM THE EXISTING
 ROOFING CONTRACTOR TRANSFERING THE
 EXISTING PERMIT TO THE NEW CONTRACTOR
 WITH A FEE FOR CHANGE OF CONTRACTOR IS
 ONE OPTION. THE OTHER IS TO SUBMIT A
 NOTARIZED LETTER FROM THE BUILDING
 CONTRACTOR STATING THAT THE PREVIOUS
 ROOFING SUBCONTRACTOR HAS BEEN
 TERMINATED AND THE EXISTING ROOFING
 PERMIT WILL BE VOIDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  