Plan Review Details - Permit 06030925
Plan Review Stops For Permit 06030925
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-08-23 Cont ID  
Sent By jwitmer Date 2006-08-23 Time 10:18 Rev Time 2.22
Received By jwitmer Date 2006-08-23 Time 10:18 Sent To  
Notes
2006-08-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06010452/ 06030925
  
 ADD:422 SUNSET/ 433 AVON RD
 CONT: BURKHARDT CONSTRUCTION
 TEL: (561)659-1400
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 601
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 2A)THE UNITY OF TITLE SUBMITTED IS NOT
 FOR THE LOTS BACK TO BACK, PHASE I AND
 PHASE II BUT FOR THE LOTS THAT ARE ON
 BOTH SIDES OF SUNSET. THIS IS A MATTER
 THAT ZONING, UTILITIES NOR THE LAW
 DEPARTMENT HAS APPROVED. THIS ISSUE HAS
 TO BE RESOLVED BEFORE A PERMIT WILL BE
 ISSUED.
 2B)ALSO SHEET A-1 PHASE-I REMOVE THE
 FENCE FROM ACROSS THE RITE OF WAY BEFORE
 A PERMIT WILL BE ISSUED.
 2C)PROVIDE A UNITY OF TITLE THAT HAS
 BEEN APPROVED FOR LOTS 116 AND 142
 COMBINING THESE LOTS INTO A SINGLE LOT.
  
 3) CONFLICT OR DISCREPANCY IN PLANS AND
 THE ARHITECTS RESPONSE. SHEET A-1
 PHASE-II ITEM# 17 INDICATES THAT THIS IS
 A NEW OVERHEAD FIRE RATED DOOR, WHEREAS
 COMMENT# 8 RESPONSE (06030925) INDICATES
 THIS IS AN EXISTING 3HR FIRE RATED
 DOORWAY. WHICH IS IT, SINCE THIS CROSSES
 PROPERTY LINES NO PERMIT WAS PULLED
 PROVIDE LITERATURE ON THE FIRE RATING
 SINCE WE STILL NEED A 2 HR SEPERATION
 FROM THE PAINT SHOP. TABLE 302.1.1.
  
 4) SHEET A-1 PHASE-II INDICATES A NEW
 HANDICAPPED RAMP AS A RESULT OF A
 MEETING BETWEEN THE OWNER, DESIGN TEAM,
 CONTRACTOR AND BUILDING DEPARTMENT.
 11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE. LOWER LANDING IS NOT
 INDICATED ON PLAN. WILL REQUIRE THE
 ELIMINATION OF ANOTHER PARKING SPOT.
  
 5) THE ARCHITECT HAS SUBMITTED A LETTER
 ON DISPROPORTIONATE COST BUT THIS LETTER
 STILL DOES NOT RELIEVE THE OWNER FROM
 VERTICAL ACCESSIBLIITY.
 11-4.1.6(1)(F) NOTHING IN THIS SECTION
 SHALL BE CONSTRUED TO RELIEVE THE OWNER
 OF ANY BUILDING, STRUCTURE OR FACILITY
 FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND
 BELOW OCCUPIABLE GRADE LEVEL, REGARDLESS
 OF WHETHER THE CODE REQUIRES AN ELEVATOR
 TO BE INSTALLED IN SUCH BUILDING,
 STRUCTURE.
 THE DESIGN TEAM HAS CREATED A RAMP
 TO ENTER THE WAREHOUSE PORTION BUT NO
 VERTICAL ACCESSIBLITY TO THE OFFICES.
  
 6A) A-1, PHASE I INDICATES ROOF TOP AIR
 HANDLERS, THE CURB IS TO BE TIED TO THE
 ROOF DECK BY 3"X3" ANGLES NO MENTION AS
 TO HOW THE ANGLES ARE FASTENED TO THE
 ALUMINIUM FRAME.2004 FBC BUILD 1503.1
  
 6B) THESE SAME 3"X3" ANGLES ARE TO BE
 BOLTED TO THE ROOF WHAT TYPE OF WEATHER
 PROOFING IS TO OCCUR AROUND THE BOLTS?
 2004 FBC BUILD 1503.1
  
 6C) M-1.2 PHASE I PLANS INDICATE THE
 HURRICANE SUPPORT DETAIL WITH A 5/8"
 EYEBOLT THROUGHT THE ROOF DECK BUT NO
 MENTION AS TO HOW TO MAKE THE CONNECTION
  
 WEATHER TIGHT? 2004 FBC BUILD 1503.1
  
 7) ONLY ONE COPY OF LISTED ITEMS BELOW
 REQUIRES (2) SUBMITTALS:
 7A) MSDS SHEETS
 7B) CARBON MONOXIDE MONITORING SYSTEM.
  
 8) WORK TO BE COMPLETED UNDER SEPERATE
 PERMIT:
 A) EXTERIOR MOTORIZED OVERHEAD DOORS
 B) PAINT BOOTH, MIXING ROOM & SUPRESSION
 SYSTEM.
 C) GENERATOR, PAD & LANDSCAPE WALL
 D) FUEL TANKS
 E) FENCING ACROSS SUNSET WITH CITY
 APPROVAL.
 F) KLAUS CAR STORAGE RACKS
  
 BUILDING PROVISOS:
 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSELY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-23 Cont ID  
Sent By jwitmer Date 2006-08-22 Time 12:34 Rev Time 6.66
Received By jwitmer Date 2006-08-22 Time 12:34 Sent To  
Notes
2006-08-22 00:00:00PERMIT:06030925
 ADD: 433 AVON RD
 CONT: BURCHANDT CONSTRUCTION
 TEL: (561)718-2602
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) COMMENT FROM THE PREVIOUS REVIEW,
 DEALS WITH A UNITY OF TITLE. PROVIDE A
 COPY OF THE UNITY OF TITLE APPROVED BY
 ZONING AND RECORDED AT THE COURT HOUSE,
 CLERK OF THE COURT.
 THE UNITY OF TITLE PROVIDED WOULD TIE
 THE LOTS THAT ARE ACROSS THE ROAD FROM
 EACH OTHER (LOTS 114 AND 116)ON
 SUNSET.THIS UNITY OF TITLE HAS NOT BEEN
 APPROVED THROUGH EITHER ZONING,
 UTILITIES NOR THE LAW DEPARTMENT.THIS
 UNITY OF TITLE MUST BE DESOLVED.
 THE UNITY OF TITLETHAT IS
 REQUIRED, AND TO BE APPROVED BY ZONING
 IS LOT 116 AND 142. AFTER IT IS RECORDED
 AT THE COURTHOUSE A COPY IS TO BE
 PROVIDED TO THE CONSTRUCTION SERVICES
 DEPARTMEENT.
  
 3) COMMENT# 8 FROM THE FIRST REVIEW
 DEALS WITH THE SAME PROPERTY LINE WALL,
 THE DOORWAY BETWEEN THE TWO INDEPENDENT
 LOTS. PLANS INDICATE ITEM 17 IS A NEW
 OVERHEAD FIRE DOOR WHEREAS THE RESPONCE
 INDICATES THIS IS AN EXISTING OVERHEAD
 DOOR. IS THIS DOOR EXISTING OR NEW? IF
 NEW PROVIDE INFORMATION ON THE DOOR
 RATING, 2HR WALL REQUIRES A 1 1/2 HR
 FIRE RATED DOOR.
  
 4) THIS COMMENT IS NEW AS TO THE NEW A

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-10 Cont ID  
Sent By jwitmer Date 2006-07-10 Time 14:55 Rev Time 2.22
Received By jwitmer Date 2006-07-10 Time 14:18 Sent To  
Notes
2006-07-10 00:00:00BUILDING PLAN REVIEW
 PERMIT:06030925
 ADD: 433 AVON RD
 CONT: BURCHANDT CONSTRUCTION
 TEL: (561)718-2602
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICA TION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) COMMENET # 5A FROM THE PREIOUS
 REVIEW, DEALS WITH THE OPENINGS ON THE
 WEST SIDE OF THE BUILDING. IN THE
 MEETING WE HAD IT APPEARS THERE IS A
 MISS-UNDERSTANDING OF THE LEVEL II WORK
 ON THAT WALL. IF THE EXISTING WINDOWS
 THAT ARE A CODE VIOLATION TABLE 602, ARE
 NOT TOUCHED THEY MAY STAY, NO NEW
 OPENINGS CAN BE MADE WHEN REPLACING
 WINDOWS THE OLD ONES ARE REMOVED HENCE
 THEY CAN BE BLOCKED INREDUCING THE
 FIRE LOADAT THE PROPERTY LINE WALL.
  
 5B) COMPLIES, WITH A SEPERATE PERMIT TO
 BE APPLIED FOR BY SPECIALTY CONTRACTOR
 FOR THE PAINT BOOTH AND MIXING ROOM.
 903.4(5) COMPLIES WITH THROUGH ALTERNATE
 METHODS AND MATERIALS (FIRE SUPRESSION
 SYSTEM-DRY CHEMICAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By jwitmer Date 2006-05-08 Time 13:22 Rev Time 2.22
Received By jwitmer Date 2006-05-08 Time 13:22 Sent To  
Notes
2006-05-08 00:00:00BUILDING PLAN REVIEW
 PERMIT:06030925
 ADD: 433 AVON RD
 CONT: BURCHANDT CONSTRUCTION
 TEL: (561)718-2602
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUM- BER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICA TION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 3) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 4) WPB ADMIN105.9*
 FL S S 469. THIS AGENCY IS THE LOCAL
 ASBESTOS AUTHORITY, AND SHOULD RECEIVE
 ALL NOTIFICATIONS FOR BUILDING
 DEMOLITION OR RENOVATION PROJECTS.
 CONTACT THEM FOR GENERAL INFORMATION ON
 ASBESTOS ISSUES INCLUDING REGULATIONS,
 CONTRACTORS OR CONSULTANTS.FL SS 469.003
 PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENVIROMENTAL SCIENCE &
 ENGINEERING AIR POLLUTION CONTROL
 SECTION)
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561)366-3070
  
 5) SHEET A-1:
 5A) WEST ELEVATION, PROVIDE INFORMATION
 HOW CLOSE THIS BUILDING IS TO THE
 PROPERTY LINE? TABLE TABLE 602.
  
 5B) PLANS INDICATE A PROPOSED PAINT
 SPRAY BOOTH, PROVIDE DETAIL SHEETS.
  
 5C) PLANS INDICATE NEW WALLS ABOVE THE
 RESTROOMS, A EQUIPMENT PLATFORM. DETAIL#
 8 DOESN'T INDICATE IF THE METAL STUDS
 ARE DRYWALL OR STRUCTURAL RATED?
 ARE THE STAIRS GOING TO THE PLATFORM NEW
 ALSO? NO DETAILS?
 505.5 INDUSTRIAL EQUIPMENT PLATFORMS.
 INDUSTRIAL EQUIPMENT PLATFORMS IN
 BUILDINGS SHALL NOT BE CONSIDERED AS A
 PORTION OF THE FLOOR BELOW. SUCH
 EQUIPMENT PLATFORMS SHALL NOT CONTRIBUTE
 TO EITHER THE BUILDING AREA OR THE
 NUMBER OF STORIES AS REGULATED BY
 SECTION 503.1 . THE AREA OF THE
 INDUSTRIAL EQUIPMENT PLATFORM SHALL NOT
 BE INCLUDED IN DETERMINING THE FIRE
 AREA. INDUSTRIAL EQUIPMENT PLATFORMS
 SHALL NOT BE A PART OF ANY MEZZANINE,
 AND SUCH PLATFORMS AND THE WALKWAYS,
 STAIRS AND LADDERS PROVIDING ACCESS TO
 AN EQUIPMENT PLATFORM SHALL NOT SERVE AS
 A PART OF THE MEANS OF EGRESS FROM THE
 BUILDING.
  
 505.5.1 AREA LIMITATIONS.
 THE AGGREGATE AREA OF ALL INDUSTRIAL
 EQUIPMENT PLATFORMS WITHIN A ROOM SHALL
 NOT EXCEED TWO-THIRDS OF THE AREA OF THE
 ROOM IN WHICH THEY OCCUR. WHERE AN
 EQUIPMENT PLATFORM IS LOCATED IN THE
 SAME ROOM AS A MEZZANINE, THE AREA OF
 THE MEZZANINE SHALL BE DETERMINED BY
 SECTION 505.2 , AND THE COMBINED
 AGGREGATE AREA OF THE EQUIPMENT
 PLATFORMS AND MEZZANINES SHALL NOT
 EXCEED TWO-THIRDS OF THE ROOM IN WHICH
 THEY OCCUR.
  
 6) THE SOUTHEAST CORNER OF THE BUILDING
 A PLATFORM AND STAIRWAY ARE CONSTRUCTED,
 PROVIDE MORE DETAILS?
  
 7A)1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 7B) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7C) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7D) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 1) WINDOWS
 2) MOTORIZED OVERHEAD DOORS
 3) STOREFRONT WINDOWS
 4) STOREFRONT DOORS
 5) MULLIONS
  
 8) PROVIDE INFORMATION ON COMPLIANCE
 WITH TABLE 302.1.1PAINT SHOP 2HR
 SEPERATION OR 1HR AND PROVIDE AUTOMATIC
 FIRE -EXTINGUISHING SYSTEM.
  
 9) PROVIDE THE AMOUNT OF PAINT AND
 SOLVENTS TO BE STORED ON SITE AND
 FLAMMIBLITY, THIS WILL DICTATE OCCUPANCY
 SEE CONTROL AREAS TABLE 307.7(1)
  
 10) PROVIDE MSDS SHEETS FOR THE ABOVE
 MATERIALS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2006-08-10 Cont ID  
Sent By dpalmer Date 2006-08-10 Time 20:51 Rev Time 0.00
Received By dpalmer Date 2006-08-10 Time 19:59 Sent To  
Notes
2006-08-10 00:00:00*** PLEASE SEE ALL REVIEWS ARE UNDER
 06010452 AS THIS IS BEING DONE UNDER ONE
 PERMIT AND NOT UNDER TWO.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-02 Cont ID  
Sent By dpalmer Date 2006-07-02 Time 13:56 Rev Time 0.00
Received By dpalmer Date 2006-07-02 Time 12:54 Sent To  
Notes
2006-07-02 00:00:00IN ELEC FOR REVIEW
 ******** UNSAT 2ND REVIEW ********
  
  
 1) NOTE: PLEASE SEE ELECTRICAL PLANS
 WHICH DID NOT INDICATE VEHICLE LIFTS AND
 SPRAY BOOTH ON PREVIOUS PLANS, NOW
 INDICATE THIS AS SOME SORT OF SERVICE
 REPAIR/BODY SHOP.
 PLEASE SEE NEC 511 AND 516. ALL AREAS AN
 CLASS LOCATION SHALL BE INDICATED AND
 LAYED OUT PER NEC 500, 500.5, 501, CLASS
 1 DIV 1, CLASS 1 DIV 2?
 NFPA-88B, 1997
 PLEASE SEE THIS SHOWN WITH A "WAREHOUSE"
 OCCUPANCY WHICH DOES NOT SEEM TO
 CORRELATE WITH NEW REVISED PLANS AND
 PROPOSED WORK.
  
 2) NOTE: PLEASE SEE PLANS NOW INDICATE
 AN OPEING TO ADJACENT SPACE WHICH IS
 ANOTHER TENANT, ADDRESS AND OCCUPANCY
 FOR "VEHICLE STORAGE".
 THIS ADDITONAL METERED SERVICE MAY NOT
 BE GRANTED AT THIS TIME.
 "SEPARATION" IS NOT ACHEIVED BY THE
 OVERHEAD DOOR, AS THIS CAN BE OPENED AT
 ANY TIME AND LEFT IN THE OPEN POSITION.
 PLEASE SEE TWO DIFFERENT PROJECTS ARE
 COMING IN FOR PERMIT, WHICH SEEM TO BE
 INFACT THE SAME BUSINES, SPACE ETC.
 ** PLEASE KNOW, THESE ARE BEING STATED
 AS TWO SEPARATE "BUILDINGS"?? PLEASE SEE
 DEFINITIONS OF "BUILDING" AND SEPARATION
 REQUIRED BYE A "FIREWALL". PLEASE SEE
 "FIREWALL" AND CONSTRUCT ACCORDINGLY.
 PLEASE KNOW, AT THAT TIME THE SECOND
 SERVICE AND METER WILL BE GRANTED.
 230.2
  
  
 3) NOTE: PLEASE SEE THAT PLANS REFLECT
 ALL CURRENT CODES IN EFFECT.
 NFPA-70 2002, NFPA-101 2003, NFPA-72
 2002 AND FBC 2004. PLEASE SEE PLANS
 REFERENCE THE 2001 FBC.
  
 4) NOTE:PLEASE SEE FBC CHAPTER 13
 WHICH APPLIES TO THIS SPACE.
 PLEASE PROVIDE LIGHTING DENSITES FOR
 AREAS.
 PLEASE PROVIDE OVER RIDES AS REQUIRED
 AND INDICATE THE MAX AMOUNT OF TIME FOR
 DEVICES CHOSEN. (TIMERS 4HRS MAX) , OCC
 SENSORS 30MINS MAX).
 PLEASE SEE ENERGY CALCULATIONS SHALL BE
 SIGNED, DATED AND SEALED BY ALL DESIGN
 PROFESSIONALS RESPONSIBLE.
 PLEASE SEE THESE ONLY CONTAIN A
 SIGNATURE AT THIS TIME.
 PLEASE SEE 13-415.1.ABC.1.1,.1.2,.1.3
 PLEASE SEE 13-415.1.AB.1,
 13-415.2.ABC.1, AND TABLES 415.2.C1,
 415.2.B.1
  
 5) NOTE: PLEASE KNOW, "IF" ADDITIONAL
 SERVICE IS GRANTED , PLEASE BOND BOTH
 SERVICES AT THE GROUNDING ELECTRODE
 SYSTEM.250.94,250.90 ETC
  
 6) NOTE: ** IMPORTANT" AS REQUESTED BY
 THE BUIDLING REVIEWER ON PREVIOUS NOTES:
 ONCE ALL REVIEWS ARE COMPLETE, BEFORE
 RESUBMITTING PLANS, PLEASE COMPLETELY
 REMOVE ALL OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. ONE COPY
 OF THE OLD/VOIDED REMOVED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP TO ALLEAVIATE ANY DELAYS
 INTHE PROCESS.
  
 ** PLEASE KNOW, ONE SET OF EACH OF THE
 PREVIOUS SUBMITTED ELECTRICAL PLANS
 ALONG WITH THE NEW REVISED ELECTRICAL
 PLANS ARE BEING RETAINED BY THIS OFFICE
 AS EACH SET CONTAINS COMPLETELY
 DIFFERENT INFORMATION FOR USE/OCCUPANCY
 ETC.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELETRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, OR COMMENTS
 PLEASE CALL.
 A CALLED WAS PLACED TO THE ELECTRICAL
 ENGINEER'S OFFICE AND A MESSAGE WAS LEFT
 AS OF THIS REVIEW TO GO OVER PLANS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-14 Cont ID  
Sent By dpalmer Date 2006-04-14 Time 09:39 Rev Time 0.00
Received By dpalmer Date 2006-04-14 Time 09:05 Sent To  
Notes
2006-04-14 00:00:00***** UNSAT *****
  
 1) NOTE: PLEASE PROVIDE NOTE FOR TYPE OF
 TIME CLOCK BEING INSTALLED FOR LIGHTING
 CONTROL SYSTEM. IS THIS AN ASTRONOMICAL
 TYPE OF CLOCK?
 FBC CHAPTER 13. 13-415.1.ABC.1.1
 PLEASE PROVIDE SCHEDULE FOR RELAY PANEL
 /DETAIL FOR THIS.
  
 2) NOTE: PLEASE SUBMIT MANUFACTURES
 SPECS/CUT SHEETS FOR ATS WHICH IS BEING
 INSTALLED FOR FUTURE GEN.
 215.5
  
 3) NOTE: PLEASE CLARIFY THE MEANS OF
 DISCONNECT WHICH WILL BE REQUIRED FOR
 GEN FEEDERS. IS THE MDP PANEL GROUPED
 WITH THE MAIN AND ATS? IF THE MDP IS
 GROUPED AND CONTAINS A MCB FOR
 DISCONNECTING POWER THEN A SEPARATE
 DISCONNECT WOULD NOT BE REQUIRED.
 PLEASE INDICATE THE LOCATION ON PLANS OF
 THE MDP AND ATS.
 215.5,225.31-225.39
  
 4) NOTE: PLEASE VERIFY NEW SERVICE AS
 SHOWN. PLANS INDICATE AN EXISTING
 SERVICE AND MAIN. IT IS NOT KNOWN AT
 THIS TIME IF AN ADDITIONAL SERVICE IS
 PERMITTED PER 230.2
  
 5) NOTE: PLEASE SEE 700.12E FOR
 CICUITING OF EM/EXT LTS.
 *EXCPT*
  
 6) NOTE: PLEASE CLARIFY IF THE
 CONTINUOUS / LIGHTING LOADS ARE SHOWN AT
 125%.215.3,230.42
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALLL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2006-07-14 Cont ID  
Sent By mwennerg Date 2006-07-14 Time 15:23 Rev Time 0.00
Received By mwennerg Date 2006-07-14 Time 15:23 Sent To  
Notes
2006-07-14 00:00:00***DENIED***
  
 PLEASE SEE ELECTRICAL COMMENT (1)
 REGARDING OCCUPANCY TYPE. PLEASE NOTE
 THAT IT WAS INITIALLY BELIEVED THAT THIS
 MET CRITERIA FOR STORAGE, HOWEVER PAINT
 SPRAY BOOTH, MIXING ROOM ETC. INDICATES
 INDUSTRIAL USE IN ACCORDANCE WITH NFPA
 101, 2003 EDITION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-07-12 Cont ID  
Sent By mcarsill Date 2006-07-12 Time 12:51 Rev Time 0.00
Received By mcarsill Date 2006-07-12 Time 12:28 Sent To  
Notes
2006-07-12 00:00:001. ALL VEHICLES ON DISPLAY SHALL HAVE
 THE BATTERIES DISCONNECTED AND CONTAIN
 VERY LITTLE FUEL. THIS ITEM WAS VERIFIED
 WITH OGS&P ON 7/12/06 BY PHONE.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE PROPOSED SPRAY BOOTH AND MIXING
 ROOM. BOTH WILL BE REQUIRED TO BE
 PROTECTED WITH AN AUTOMATIC FIRE
 SUPPRESSION SYSTEM UNDER SEPARATE
 PERMIT. THE SPRAY BOOTH SHALL COMPLY
 WITH NFPA 33.
  
 3. COULD NOT LOCATE ANY CUT SHEETS ON
 CARBON MONOXIDE DETECTORS THAT ARE
 PLANNED FOR USE IN THE LITERATURE.
 PLEASE PROVIDE PRODUCT LITERATURE AND
 HOW WILL THESE DEVICES BE TESTED.
 CALIBRATION GAS AND TEST EQUIPMENT WILL
 MOST LIKELY BE NEEDED IF THE SET POINTS
 ON THESE DETECTORS DO NOT COME FACTORY
 SET. PLEASE PROVIDE MORE DETAILS AS
 REQUIRED.
  
 4. ALL WORK SUBJECT TO FIELD INSPECTION
 AND APPROVAL. PLEASE HAVE THE PROJECT
 ARCHITECT CONTACT THIS OFFICE AT
 804-4709. THANK YOU.
  
 APPROVED PROVISO
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-05-18 Cont ID  
Sent By mwennerg Date 2006-05-18 Time 14:36 Rev Time 0.00
Received By mwennerg Date 2006-05-18 Time 14:36 Sent To  
Notes
2006-05-18 00:00:00***DENIED***
  
 1) ADDRESS IS REQUIRED ON BUILDING THAT
 SHALL BE MINIMUM OF 6" IN HEIGHT AND
 CONTRASTING TO THE BACKGROUND. PLEASE
 ADD NOTE TO ELEVATIONS IF NEW OR
 EXISTING.
  
 2) PLEASE PROVIDE MORE DETAILS REGARDING
 PAINT MIXING ROOM.
  
 3) SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR PAINT SPRAY BOOTH. ALL WORK
 SHALL COMPLY WITH NFPA 33.
  
 4) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED TO BE MOUNTED AT LOCATIONS TO
 MEET HAZARD AND MINIMUM 75' TRAVEL
 DISTANCE REQUIREMENTS.
  
 5) PLEASE SHOW LOCATION(S) OF DUCT SMOKE
 DETECTORS. IF BUILDING HAS A FIRE ALARM
 SYSTEM, DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 6) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 13:52 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 13:52 Sent To  
Notes
2006-08-09 00:00:00TO "COMM" BD#53
2006-07-31 00:00:00WAITING FOR "COMM" BD--NEW MECH AND
 PLUMB SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 09:25 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 09:25 Sent To  
Notes
2006-07-02 00:00:00TO COMM BOARD SPACE#61, B
2006-06-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-02 Cont ID  
Sent By jleech Date 2006-06-02 Time 10:19 Rev Time 0.00
Received By jleech Date 2006-03-21 Time 19:48 Sent To  
Notes
2006-05-25 00:00:005/25/06-TAKEN FROM "COMM" BD AND ROUTED
 TO "P"
2006-04-12 00:00:00TO "COMM" BD#19
2006-03-21 00:00:00WAITING FOR COMM BOARD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-17 Cont ID  
Sent By pkrauss Date 2006-07-17 Time 07:24 Rev Time 0.00
Received By pkrauss Date 2006-07-17 Time 07:24 Sent To  
Notes
2006-07-17 00:00:00DENIED:433 AVON ROAD/BUILDING 1
  
 PLEASE NOTE, MEETING WAS HELD WITH
 BURKHARDT CONSTRUCTION SEVERAL MONTHS
 AGO WITH REGARDS TO THE VEHICLE STORAGE
 AT 422 SUNSET RD.
  
 1.PLEASE CLARIFY WHICH BUILDING WILL
 BE USED FOR STORAGE AND WHICH BUILDING
 WILL HAVE THE SPRAY PAINT BOOTH.
 ACCORDING TO MY NOTES, THE REVIEW UNDER
 PERMIT 06010452 IS FOR THE PRIVATE CAR
 STORAGE - BUILDING 1 (REFERENCE PERMIT
 06030925).THE PLANS SUBMITTED INDICATE
 BUILDING 1 AS HAVING A SPRAY PAINT
 BOOTH.
  
 2.WHERE IN RELATION TO THIS BUILDING 1
 IS THE OTHER BUILDING LOCATED?
  
 3.PLEASE PROVIDE INFORMATION ON THE
 "NEW CAR LIFTS" INDICATED ON PLAN SHEET
 A-1.PLEASE PROVIDE MANUFACTURER'S
 SUBMITTAL DATA.PLEASE INDICATE WHAT
 THE LIFTS ARE NEEDED FOR IF NO
 MECHANICAL WORK IS TO BE DONE ON THE
 VEHICLE.
  
 4.MANUFACTURER SUBMITTAL DATA WAS
 SUBMITTED FOR THE SPRAY BOOTH & PAINT
 MIXING ROOM.PLEASE INDICATE WHICH
 MODEL OF THE SPRAY BOOTH WILL BE
 INSTALLED.PLEASE NOTE, ADDTIONAL
 PERMIT REQUIRED FOR SPRAY BOOTH & MIXING
 ROOM.
  
 4.SPRAY PAINT BOOTH TO HAVE A MINIMUM
 CLEARANCE OF 3 FT ROUND SPRAY BOOTH AND
 A FIRE RESISTANCE RATING OF 1 HOUR IN
 ACCORDANCE WITH NFPA 33 SECTION 5.3 &
 5.3.2.
  
 5.PLEASE INDICATE TERMINATION OF
 EXHAUST FROM THE SPRAY BOOTH.INDICATE
 DISTANCES FROM PROPERTY LINES AND
 ADJOINED/CONTINGUOUS BUILDINGS. SHOW
 COMPLIANCE WITH 2004 FMC 502.7.3.6.
  
 6.PLEASE SEE COMMENT #2BY JIM WITMER
 DATED 7-10-06.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-25 Cont ID  
Sent By tgordon Date 2006-04-25 Time 09:25 Rev Time 1.00
Received By tgordon Date 2006-04-25 Time 09:25 Sent To  
Notes
2006-04-25 00:00:00*** DENIED ***
 1) PLEASE PROVIDE MINIMUM VENTILATION
 0.05 CFM PER SQUARE FOOT, PER. 2004
 FBC/M 404.2 .
  
 2) PLEASE CORRECT LOW LEVEL ALARM TO 25
 PARTS PER MILLION, PER 2004 FBC/M 404.1
 ENCLOSED PARKING GARAGES.
  
 3) PLEASE SHOW ON MECHANICAL PLANS A/C
 ROOF EQUIP. MOUNTING DETAILS THAT THIS
 COMPLIES WITH 2004 FBC/M 301.13 AND WITH
 STANDS 140 MPH WINDS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-08-24 Cont ID  
Sent By jleech Date 2006-08-24 Time 09:40 Rev Time 0.00
Received By jleech Date 2006-08-24 Time 09:40 Sent To  
Notes
2006-08-24 00:00:00DENIED;
 1.ADA DETAIL FOR PHASE 11 ON PAGE A-2
 ONLY SHOWS A DETAIL OF THE LAVATORY.
 DETAIL OF THE WHOLE BATHROOM IS REQUIRED
 SHOW THE TOILET, SHOWER, AND LAVATORY IN
 DETAIL. REQUIREMENTS FOR COMPLIANCE CAN
 BE FOUND, FBC-2004 CHAPTER 11; TOILET,
 11-4.16.1 THRU 11-4.16.6; LAVATORY
 SECTIONS 11-4.19.1 THRU 11-4.19.6;
 SHOWER SECTIONS 11-4.21.1 THRU
 11-4.21.8.
 2.HOT WATER REQUIRED TO SERVICE SINK.
 (SHOW ON PLAN) SHOW LOCATION OF WATER
 HEATER, OR WATER HEATERS, SIZE AND FUEL
 SOURCE.
 3.SANITARY RISER DIAGRAM;
 A)TRENCH DRAIN AND FLOOR DRAIN SHALL
 NOT BE DOUBLE TRAPPED. SEC 1002.1
 B)WHAT IS THE 4" VERTICAL DRAIN AND
 BACK WATER VALVE FOR? NEED MORE
 INFORMATION)
 C)WHY IS A FLOOR DRAIN NEEDED IN THE
 FUTURE PAINT BOOTH? (SECOND REQUEST)
 4.SAND INTERCEPTER; (SECOND REQUEST)
 PLANS MUST BE VIEWED AND APPROVED BY THE
 UTILITY DEPTMENT FOR SIZE AND LOCATION.
 THE CONTACT PERSON IS;
 LYNN MASSON
 PHONE # 822-2271
 FAX# 822-2279
 E-MAIL [email protected]
 5.PLUMBING FIXTURE REQUIREMENT TABLE FOR
 PHASE 11 IS NOT CORRECT. WORK WILL BE
 DONE IN THIS PART OF THE BUILDING.
 PLEASE CHANGE CLASIFICATION TO BUSINESS,
 OR CHANGE BOTH PHASES TO BUSINESS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-07-15 Cont ID  
Sent By jleech Date 2006-07-15 Time 08:17 Rev Time 2.50
Received By jleech Date 2006-07-15 Time 07:37 Sent To  
Notes
2006-07-15 00:00:00DENIED;
 1.PROVIDE INFORMATION ON SPRAY BOTH. WHY
 WOULD A FLOOR DRAIN BE REQUIRED?
 2.PLEASE SHOW A DETAIL OF NEW HANDICAP
 BATHROOM. BATHROOM MUST MEET FBC-2004
 CHAPTER 11;
 SHOWER SECTIONS 11-4.21.1 THRU
 11-4.21.8.
 LAVATORY SECTIONS 11-19.1
 THRU11-4.19.6
 SHOW TURNING RADIUS IN BATHROOM ON
 DRAWING.
 3.HANDICAP CODE SECTION 11-4.1.3(11)
 BOTH BATHROOMS MUST BE ACCESSIBLE.
 4.MINIMUM PLUMBING FIXTURES, FBC-2004
 PLUMBING TABLE 403.1(8) REQUIRES A MOP
 SINK AND A DRINKING FOUNTAIN. DRINKING
 FOUNTAIN MUST MEET HANDICAP CODE
 SECTIONS 11-4.15.1 THRU 11-4.15.5, AND
 SECTION 11-4.1.3(11).
 5.PLANS MUST BE REVIEW BY THE UTILITY
 DEPARTMENT FOR SIZE AND LOCATION OF SAND
 AND OIL INTERCEPTOR.
 THE CONTACT PERSON IS;
 LYNN MASSON
 PHONE (561) 822-2271
 FAX(561) 822-2279
 [email protected]
 6.DETAIL OF SAND AND OIL INTERCEPTOR IS
 REQUIRED. HOW IS PIPING TO BE INSTALLED
 (INSIDE THE TANK) TYPE OF MATERIAL TANK
 IS MADE FROM. SHOW COMPLIANCE WITH
 SECTIONS 1003.4 THRU 1003.4.2. ALSO
 1003.9 VENT IS REQUIRED.
 7.EMERGENCY EYE WASH AND SHOWER STATION
 SHOULD BE IN A CENTRAL LOCATION NEAR THE
 PAINT STORAGE AND PREP AREA, ALSO A DOOR
 TO THE SPAY BOOTH SHOULD BE ON THE SIDE
 OF THE EMERGENCY EQUIPMENT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-02 Cont ID  
Sent By jleech Date 2006-06-02 Time 10:13 Rev Time 0.00
Received By jleech Date 2006-06-02 Time 10:13 Sent To  
Notes
2006-06-02 00:00:00NO PLUMBING WORK SHOWN ON PLANS.