Plan Review Details - Permit 06030883
Plan Review Stops For Permit 06030883
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-03-30 Cont ID  
Sent By rmcdouga Date 2006-03-30 Time 10:52 Rev Time 0.00
Received By rmcdouga Date 2006-03-30 Time 10:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-24 Cont ID  
Sent By rmcdouga Date 2006-03-24 Time 07:59 Rev Time 0.00
Received By rmcdouga Date 2006-03-24 Time 07:15 Sent To  
Notes
2006-03-24 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE DESIGN PRESSURE FOR THE MODIFIED
 BITUMEN SYSTEM INDICATED ON PAGE 12 OF
 THE NOA IS TOO LOW, ENHANCED FASTENING
 IS REQUIRED. SUBMIT SIGNED AND SEALED
 RAS 117 CALCULATIONS FROM AN ENGINEER,
 ARCHITECT OR REGISTERED ROOF CONSULTANT
 AS REQUIRED BY LIMITATION NUMBER 7 ON
 PAGE 13 OF THE NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  