Plan Review Details - Permit 06030848
Plan Review Stops For Permit 06030848
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-06-29 Cont ID  
Sent By mperson Date 2006-06-29 Time 10:57 Rev Time 0.33
Received By mperson Date 2006-06-29 Time 10:57 Sent To PC
Notes
2006-06-29 00:00:00 
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,750 CUBIC FEET REQUIRED.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-06-12 Cont ID  
Sent By mperson Date 2006-06-12 Time 15:03 Rev Time 0.33
Received By mperson Date 2006-06-12 Time 15:03 Sent To PC
Notes
2006-06-12 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED BY PLAN REVIEW:
  
 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING FOR
 THE GENERATOR LOCATION.(NOTE: ZONING
 FAILED GEN/RES APPLICATION 6/4/06 SEE
 ATTACHED COPY OF ZONING PLAN REVIEW
 COMMENTS)
 2. PLEASE SEE ATTACHED ONE-STOP-SHOP
 ON-LINE WEB SERVICE SHEET ATTACHED FOR
 REFERENCE ON GEN/RES PERMIT APPLICATIONS
 PASS OR FAILED STATIS.
 3. PLEASE SIZE AND INDICATE MATERIAL
 TYPES TO THE BBQ'S, POOL HEATER,
 GENERATOR, WATER HEATER RISERS, AND THE
 EXISTING SYSTEM FOR RESUBMITTAL IT WILL
 SAVE A PHONE CALL TO FIND OUT THE
 INFORMATION.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-03-28 Cont ID  
Sent By adarroug Date 2006-06-07 Time 17:57 Rev Time 0.33
Received By mperson Date 2006-03-28 Time 09:15 Sent To PC
Notes
2006-03-28 00:00:00****DENIED****
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR A GAS PERMIT:
  
 1. GAS PERMIT CAN NOT BE ISSUED UNTIL A
 RES/GEN PERMIT HAS BEEN APPROVED BY
 ZONINGS APPROVAL OF GENERATOR LOCATION.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 16:31 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 16:31 Sent To P
Notes
2006-06-21 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-07 Cont ID  
Sent By adarroug Date 2006-06-07 Time 17:58 Rev Time 0.00
Received By adarroug Date 2006-06-07 Time 17:58 Sent To G
Notes
2006-06-07 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-07 Cont ID  
Sent By adarroug Date 2006-03-28 Time 17:57 Rev Time 0.00
Received By adarroug Date 2006-03-21 Time 18:08 Sent To G
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved