Plan Review Details - Permit 06030769
Plan Review Stops For Permit 06030769
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-28 Cont ID  
Sent By btrobaug Date 2006-03-28 Time 06:23 Rev Time 0.33
Received By btrobaug Date 2006-03-28 Time 06:05 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-20 Cont ID  
Sent By btrobaug Date 2006-03-20 Time 15:04 Rev Time 0.33
Received By btrobaug Date 2006-03-20 Time 14:10 Sent To PC
Notes
2006-03-20 00:00:00 
 PLEASE SUBMIT THE SIZE OF THE SERVICE
 CONDUCTORS PER 310.16, THE GROUNDING
 ELECTRODE CONDUCTOR PER 250.66 AND
 INDICATE THE MAIN DISCONNECT LOCATION
 AND AIC RATING.
  
 PLEASE CORRECT THE DESCRIPTION ON THE
 APPLICATION TO INDICATE IF THE METER AND
 PANEL ARE BEING REPLACED, OR JUST THE
 METER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-24 Cont ID  
Sent By spalmer Date 2006-03-24 Time 17:45 Rev Time 0.00
Received By spalmer Date 2006-03-24 Time 17:45 Sent To E
Notes
2006-03-24 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-20 Cont ID  
Sent By btrobaug Date 2006-03-20 Time 14:10 Rev Time 0.00
Received By btrobaug Date 2006-03-17 Time 14:50 Sent To E
Notes
2006-03-17 00:00:00TO "E" BOX