Plan Review Details - Permit 06030762
Plan Review Stops For Permit 06030762
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-04-11 Cont ID  
Sent By amorse Date 2006-04-11 Time 08:40 Rev Time 0.50
Received By amorse Date 2006-04-11 Time 08:40 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-03-27 Cont ID  
Sent By btrobaug Date 2006-03-27 Time 10:21 Rev Time 0.33
Received By btrobaug Date 2006-03-27 Time 10:19 Sent To P
Notes
2006-03-27 00:00:00 
  
 PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDU
 IT SIZE AND TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-03-28 Cont ID  
Sent By mperson Date 2006-03-28 Time 14:35 Rev Time 0.00
Received By mperson Date 2006-03-28 Time 14:35 Sent To B
Notes
2006-03-28 00:00:00NOTE: NO POOL HEATER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-25 Cont ID  
Sent By adarroug Date 2006-04-25 Time 11:47 Rev Time 0.00
Received By adarroug Date 2006-04-25 Time 11:47 Sent To P
Notes
2006-04-25 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-24 Cont ID  
Sent By spalmer Date 2006-03-24 Time 17:37 Rev Time 0.00
Received By spalmer Date 2006-03-24 Time 17:37 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-04-11 Time   Rev Time 0.00
Received By adarroug Date 2006-03-17 Time 15:21 Sent To  
Notes
2006-03-17 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-04-26 Cont ID  
Sent By mperson Date 2006-04-26 Time 11:44 Rev Time 0.45
Received By mperson Date 2006-04-26 Time 11:44 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-28 Cont ID  
Sent By btrobaug Date 2006-04-12 Time 12:32 Rev Time 0.33
Received By mperson Date 2006-03-28 Time 14:37 Sent To B
Notes
2006-03-28 00:00:00******DENIED******
 REFERENCE: FBC-2004 424.2 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION RQUIRED FOR PLAN REVIEW:
  
 1) COMPLY WITH FBC-2004 SEC 424.2
 PRIVATE SWIMMING POOLS.(ADD TO NOTES)
 2) FBC-2004 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES)
 3) PIPING SCHEMATIC SHOWS AN 1-1/2"
 VENT, THE VENT PIPE MAXIMUM
 LENGTH CHART IS FOR 1" VENTS, AND THE
 MAIN DRAIN DETAIL INDCATES A 1" VENT.
 THESE THREE DETAILS NEED TO CORRELATE TO
 EITHER 1" OR 1-1/2".
 10) FBC-2004 424.2.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK.(ADD TO DETAIL)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2006-04-12 Cont ID  
Sent By btrobaug Date 2006-04-12 Time 15:41 Rev Time 0.33
Received By btrobaug Date 2006-04-12 Time 15:40 Sent To  
Notes
2006-04-12 00:00:00OK PER MICHELLE./WRT.