Plan Review Details - Permit 06030591
Plan Review Stops For Permit 06030591
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 17:42 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 17:42 Sent To M
Notes
2006-03-24 00:00:00TO MECH BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-17 Cont ID  
Sent By adarroug Date 2006-03-17 Time 16:25 Rev Time 0.00
Received By adarroug Date 2006-03-17 Time 16:25 Sent To M
Notes
2006-03-17 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-15 Cont ID  
Sent By tgordon Date 2006-03-15 Time 15:31 Rev Time 0.00
Received By tgordon Date 2006-03-15 Time 11:47 Sent To  
Notes
2006-03-15 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-03-27 Cont ID  
Sent By tgordon Date 2006-03-27 Time 09:46 Rev Time 0.30
Received By tgordon Date 2006-03-27 Time 09:46 Sent To  
Notes
2006-03-27 00:00:00*** PROVISO ***
 1)THE DWELLING WILL BE REQUIRED TO HAVE
 SMOKE ALARMS INSTALLED IF NOT ALREADY
 PRESENT, PER 2004 FBC/R 313.1.1, AND SEE
 2004 FEBC 303.1 LEVEL ONE ALTERATION
 INCLUDE REPLACEMENT OF EQUIPMENT.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-03-20 Cont ID  
Sent By tgordon Date 2006-03-20 Time 14:47 Rev Time 0.30
Received By tgordon Date 2006-03-20 Time 14:47 Sent To  
Notes
2006-03-20 00:00:00*** DENIED ***
 1) PLANS MAY NOT BE DONE IN PENCIL.
  
 2) PLEASE SUBMIT TWO COPYS OF PLANS.
 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 3) PLEASE SHOW ON MECHANICAL PLANS AN
 EQUIPMENT LISTING WITH MANUFACTURE NAME,
 MODEL NUMBER, TONS, SEER, HEATER KW,
 TOTAL COOLING BTU'S; SENSIBLE COOLING
 BTU'S; AND COPPER LINE SIZES.
  
 4) AS REQUESTED IN LAST REVIEW, PLEASE
 SIGN BOLTH COPYS OF ENERGY CAL'S.
  
 5) PLEASE SHOW SIZE OF SUPPLY AIR DUCT
 (FLEX) FROM AHU TO TO THE MIXING BOX.
  
 6) PLEASE SUPPLY RETURN AIR TO THE
 BEDROOMS, SEE NOTE #7.
  
 7)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 8) PLEASE PROVIDE LIABILITY INSURANCE
 INFORMATION FOR EWING & EWING AIR COND.
 NOT EWING HEATING & AIR INC..
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-15 Cont ID  
Sent By tgordon Date 2006-03-15 Time 15:19 Rev Time 0.30
Received By tgordon Date 2006-03-15 Time 15:19 Sent To  
Notes
2006-03-15 00:00:00*** DENIED ***
 1) PLEASE SUBMIT A MECHANICAL PLAN FOR
 REVIEW.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 3) PLEASE PROVIDE PROOF OF LIABILITY
 INSURANCE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved