Plan Review Details - Permit 06030523
Plan Review Stops For Permit 06030523
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-18 Cont ID  
Sent By alange Date 2006-07-18 Time 09:01 Rev Time 2.00
Received By alange Date 2006-07-18 Time 09:01 Sent To  
Notes
2006-07-18 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.SIGN ENERGY CALCS BY PERPARER AND
 OWNER/AGENT PER 2004 FBC 13-600.3.ABC.2
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-10 Cont ID  
Sent By alange Date 2006-04-10 Time 14:39 Rev Time 4.50
Received By alange Date 2006-04-10 Time 14:22 Sent To  
Notes
2006-04-10 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3. ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2005 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
  
 9. ROOF SHEATHING SHALL COMPLY WITH FBC
 2304.9.1 FOR THICKNESS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-16 Cont ID  
Sent By dpalmer Date 2006-07-16 Time 12:58 Rev Time 0.00
Received By dpalmer Date 2006-07-16 Time 10:59 Sent To M
Notes
2006-07-16 00:00:00IN ELEC FOR REVIEW, FROM ZONING ON 7/11
 **** UNSAT ****
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE SOME NEW NOTES.
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AS NOTED,
 WITH NEW NOTES ADDED TO THE BOTTOM OF
 THE FIRST REVIEW NOTES.
  
  
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK/NO. ADDRESSED COMMENT,
 HOWEVER DUE TO CHANGES MADE BY COMMENT,
 PLEASE SEE THE MISPRINT WAS REVISE,
 HOWEVER PLEASE KNOW, THE CONDUIT
 EXTENDING FROM GRND TO METER SHALL BE
 SCHEDULE 80 AS THIS IS AREA IS
 CONSIDERED SUBMIT TO PHYSICAL DAMAGE.
 352.10F
  
 ** PREVIOUS REVIEW NOTE**PLEASE SEE
 UNDERGROUND CONDUITS
 WHICH MENTIONS THE USE OF SCHEDULE "90"
 PVC?? PLEASE VERIFY AS THIS IS NOT A
 COMMON ITEM, NOR IS IT LISTED IN THE
 NEC.
 215.5
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: NO, PLEASE SEE THIS STILL DOES
 NOT SEEM TO BE COMPLETE AT THIS TIME FOR
 INTENDED LOADS, DISCONNECTING MEANS ECT.
 PLEASE ALSO SEE THAT MANUFACTURES
 SPECS/CUT SHEETS WERE NOT SUBMITTED.
 PLEASE KNOW, IT IS NOTED THAT THE
 RESPONSE MENTIONS THIS WOULD BE DONE AT
 A LATER DATE , HOWEVER THIS IS REQUIRED
 AT THIS TIME IF SYSTEM IS GOING TO BE
 UNDER MAIN HOUSE PERMIT. PLEASE SEE
 PLANS ARE NOT DETAILED ENOUGH FOR
 TRANSFER OF POWER AND WHERE THAT IS
 TAKING PLACE, DISCONNECTING MEANS ETC.
 ** PLEASE KNOW, THE PV SYSTEM MAY
 EXCLUDED AND SUBMITTED UNDER A SEPARATE
 PERMIT AT A LATER DATE. NO ELECTRICAL
 FOR ANY DEVICES SHOWN ON PLANS WOULD BE
 PERMITTED AT THIS TIME.
 ** PLEASE KNOW, EQUIPMENT MAY ALWAYS BE
 REVISED.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE COMPLETE PLANS FOR
 PHOTOVOLTAIC SYSTEM. PLEASE SUBMIT ALL
 MANUFACTURES SPECS/ CUT SHEETS FOR
 EQUIPMENT TO BE INSTALLED.
 PLEASE BE SURE ALL SHEETS INDICATE A
 LISTING FROM A NRTL.
 PLEASE BE SURE TO SEE 690 OF THE NEC.
 ** PLEASE BE SURE TO ALSO SEE BLDG
 COMMENTS WITH RESPECT TO WIND LOAD
 CALCULATIONS REQUIRED FOR NEW EQUIPMENT
 BEING INSTALLED ON ROOF.
  
 9) NOTE: NO, PLEASE SEE THIS IS THE SAME
 AS ABOVE. PLEASE SUBMIT AT THIS TIME OR
 KNOW, THE LIGHTING CONTROL SYSTEM CAN BE
 DONE UNDER A SEPARATE PERMIT. NO WIRING
 MAY BE INSTALLED UNTIL THAT PERMIT IS
 ISSUED.
 ** ONCE AGAIN, EQUIPMENT CAN ALWAYS BE
 REVISED.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SUBMIT COMPLETE SPECS/CUT
 SHEETS FOR NEW LIGHTING CONTROL SYSTEM.
 PLEASE BE SURE ALL SHEETS INDICATE A
 LISTING FROM A NRTL.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK, HOWEVER SEE NOTES
 REGARDING LOAD CALCUALTIONS.
  
 13) NOTE:NO, PLEASE SEE LAUNDRY
 CIRCUIT IS SHOWN AT .40VA.
 WASHER REVISED.
  
 ** PREVIOUS PLEASE SEE 220.16, 210.11C2
 FOR MINIMUM VA FOR LAUNDRY AND WASHER.
  
 14) NOTE:OK.
  
 15) NOTE: OK.
  
 16) NOTE: OK.
  
 17) NOTE: NO, PLEASE SEE THESE WERE
 ADDED, HOWEVER PLEASE SEE REDLINED
 PLANS, AS GFI RECEPT IS REQUIRED TO BE
 WITHIN 2' OF THE END/START OF THE
 COUNTERSPACE. ** THIS CAN BE REDLINED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE 210.52C1 FOR KITCHEN
 COUNTER SPACE RECEPTACLES MISSING.
  
 18) NOTE: OK.
  
 19) NOTE: OK.
  
 20) NOTE:NO, PLEASE SEE CALCUALITONS
 WERE SUBMITTED ON PLANS AND IN SPEC
 BOOKS, HOWEVER THEY ARE REFERENCING
 CODES NOT IN THE CURRENT 2002 NEC.
 PLEASE ALSO SEE 220, 220.11 ETC FOR WHAT
 LOADS ARE PERMITTED TO BE DERATED UNDER
 THE TABLE. PLEASE KNOW, NOT ALL LOADS AS
 SHOWN IN LOAD CALCS MAY BE DERATED UNDER
 THE SAME 220.11
 PLEASE KNOW, LOADS MAY BE DONE UNDER
 220.31
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING MINIMUM
 LOAD CALCULATIONS PER NEC.220
  
 21) NOTE: OK.
  
 22) NOTE: NO, RESPONSE MENTIONS THIS IS
 THE LEGAL SIGNATURE, HOWEVER COULD NOT
 LOCATE THE LETTER FROM THE ENGINEER OF
 RECORD. THE LTR WILL BE PLACED IN FILE
 AS PREVIOUSLY NOTED.
  
 ** PREVIUOS REVIEW NOTE **
 PLEASE SEE FS 471.025 WHICH
 REQUIRES THE LEGAL SIGNATURE FOR THE
 ENGINEER OF RECORD. PLANS APPEAR TO
 CONTAIN INITIALS, IF INDEED THIS IS THE
 LEGAL SIGNATURE, PLEASE PROVIDE A
 SIGNED, DATED, SEALED LETTER TO ATTEST
 TO THE LEGAL SIGNATURE. THIS LETTER IS
 REQUIRED TO BE CORRECTLY NOTARIZED UNDER
 FS 117.05
 PLEASE KNOW, THIS WILL GO INTO OUR
 SIGNATURE FILE FOR ANY FUTURE REFERENCED
 NEEDED FOR SIGNATURE.
  
 ** NEW NOTES ***
  
 23) NOTE: PLEASE CLARIFY THE SYMBOL ON
 PLANS AS "SF" AT DOOR LOCATIONS ETC , AS
 THIS DEVICE IS NOT ON SYMBOL LEGEND.
  
 24) NOTE: PLEASE SEE SOME SORT OF
 LIGHTING FIXTURE IS BEING SHOWN IN
 CLOSET WHICH DOES NOT SEEM MIN
 CLEARENCES PER 410.8. PLEASE ALSO SEE
 OTHER TYPE OF FLOURESCENT DOWN LTS,
 WHICH SEEM TO BE DIRECLTY OVER SHELVING
 AREA IN ONE CLOSET.
 PLEASE SUBMIT SPEC/MANUFACTURE CUT
 SHEETS FOR LIGHTING BEING PROPOSED AS
 "STRIP LIGHTING" OF SOME KIND.
 PLEASE SEE 410.8
  
 25) NOTE: PLEASE SEE THE WATER HEATER IS
 BEING SHOWN AS 4.5KW, HOWEVER THE OCP IS
 SHOWN AS 50A'S?
 PLEASE SEE MIN OCP FOR THIS IS 125%,
 HOWEVER MAX OCP IS 150%.(30A) PLEASE
 ALSO SEE CONDUCTOR SIZE SHOWN AT #6
 NEEDS ADJUSTING AS #6 IS NOT RATED UNDER
 THE LUGS OF A 30A BRKR.
 422.11E3
  
 ** PLEASW KNOW, THE DETAILED RESPONSE
 WAS APPRECIATED AS THIS HELPS IN THE
 REVIEW PROCESS.
  
  
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
 ** PLEASE KNOW, IF THIS PERMIT IS GOING
 TO INLCUDE LIGHTING CONTROL SYSTEM AND
 PHOTOVOLTAIC SYSTEM, VALUE FOR COMPLETE
 SCOPE OF WORK WILL BE REQUIRED TO BE
 INCREASED, AS THE VALUES BASED IN THE
 TABLES FOR THE FBC DOES NOT INLCUDE
 THESE SPECIALIZED ELECTRICAL SYSTEMS.
 PLEASE PROVIDE COMPLETE CONTRACT FOR ALL
 TRADES FOR SCOPE OF WORK OR ADJUST VALUE
 IF THESE WILL BE PERMITTED UNDER HOUSE
 PERMIT.
 PLEASE ALOS KNOW, THE ELECTRICAL
 CONTRACTOR UNDER HOUSE PERMIT WILL ALSO
 BE RESPONSIBLE FOR ALL WORK EVEN IF DONE
 BY A SUB CONTRACTOR.
 FBC 108.3
 ** PLEASE HAVE CONTRACTOR CALL TO GO
 OVER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-20 Cont ID  
Sent By dpalmer Date 2006-03-20 Time 17:46 Rev Time 0.00
Received By dpalmer Date 2006-03-18 Time 20:36 Sent To P
Notes
2006-03-20 00:00:00 
 ******* UNSAT ********
  
 1) NOTE: PLEASE ADD NOTE WHICH STATES
 THAT THE LIGHTNING PROTECTION SYSTEM
 SHALL BE UNDER A SEPARATE PERMIT.
  
 2) NOTE: PLEASE CLARIFY PANEL 1B AND 1C,
 AS THESE ARE SHOWN WITH ?FEED-THRU?
 LUGS? ARE THERE OTHER PANELS?
 215.5
  
 3) NOTE: PLEASE SEE 250.6, 250.24B,
 RISER DIAGRAM SHOWS "EQUIPMENT GROUNDING
 CONDUCTORS" FROM FPL TO THE FIRST MEANS
 OF DISCONNECT. PLEASE KNOW, THE
 "EQUIPMENT GRND" SHOULD ONLY BE
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 4) NOTE: PLEASE CLARIFY USE OF WHAT
 APPEARS TO BE A "CT" FOR METERING. THIS
 IS UNCLEAR AS THE PLANS INDICATE A
 METER, BUT THE PLANS DO NOT SHOW A METER
 ON HOUSE?
 IF A CT IS NOT USED, PLEASE INCLUDE
 METER CAN ON RISER AND ADJUST CONDUCTORS
 ETC.
 PLEASE OBTAIN A LETTER FROM AN FPL
 SERVICE PLANNER, WHICH STATES THAT A
 "CT" IS GOING TO BE USED.
  
 5) NOTE: PLEASE SEE UNDERGROUND CONDUITS
 WHICH MENTIONS THE USE OF SCHEDULE "90"
 PVC?? PLEASE VERIFY AS THIS IS NOT A
 COMMON ITEM, NOR IS IT LISTED IN THE
 NEC.
 215.5
  
 6) NOTE: PLEASE VERIFY THE MIN DEPTH OF
 UNDER GROUND SERVICE ENTRANCE CONDUITS.
 PLEASE SEE THE MIN DEPTH PER FPL GUIDE
 LINES IS 24INCHES TO THE TOP OF THE
 CONDUITS.
 PLEASE ALSO SEE NOTE/DETAIL MENTIONS
 18INCHES UNDER ROADS? PLEASE SEE 300.5
 FOR MIN
 DEPTHS.
  
 7) NOTE: PLEASE SEE MINIMUM GROUNDING
 ELECTRODE SYSTEM TO BE SHOWN PER
 250.50,250.52
 PLEASE INCLUDE, CWP, FOOTER STEEL, AT A
 MIN.
  
 8) NOTE: PLEASE COMPLETE PLANS FOR
 PHOTOVOLTAIC SYSTEM. PLEASE SUBMIT ALL
 MANUFACTURES SPECS/ CUT SHEETS FOR
 EQUIPMENT TO BE INSTALLED.
 PLEASE BE SURE ALL SHEETS INDICATE A
 LISTING FROM A NRTL.
 PLEASE BE SURE TO SEE 690 OF THE NEC.
 ** PLEASE BE SURE TO ALSO SEE BLDG
 COMMENTS WITH RESPECT TO WIND LOAD
 CALCULATIONS REQUIRED FOR NEW EQUIPMENT
 BEING INSTALLED ON ROOF.
  
 9) NOTE: PLEASE SUBMIT COMPLETE
 SPECS/CUT SHEETS FOR NEW LIGHTING
 CONTROL SYSTEM. PLEASE BE SURE ALL
 SHEETS INDICATE A LISTING FROM A NRTL.
  
 10) NOTE: PLEASE SEE 2002 NEC 210.12B
 FOR MIN ARC FAULT PROTECTION REQUIRED
 FOR ALL OUTLETS IN SLEEPING ROOMS.
 PLEASE SEE THIS INCLUDES, LIGHTS,
 RECEPTS, SD'S, FANS ETC. PLEASE VERIFY
 THE PROTECTION AND HOW THESE WILL BE
 TIED INTO LIGHTING CONTROL SYSTEMS.
  
 11) NOTE: PLEASE SEE NFPA-72 11.5.1.1
 WHICH REQUIRES A SD ON EACH LEVEL OF A
 MULTI-LEVEL BUILDING IN THE IMMEDIATE
 VICINITY OF STAIRS LEADING TO THE FLOOR
 ABOVE.
  
 12) NOTE: PLEASE MININUM VA REQUIRED
 FOR SMALL APPL CIRCUITS PER 220.12,
 210.52B1,210.11C1
  
 13) NOTE: PLEASE SEE 220.12, 210.11C2
 FOR MINIMUM VA FOR LAUNDRY AND WASHER.
  
 14) NOTE: PLEASE SEE 220.18 FOR MINIMUM
 VA FOR DRYER LOADS.
  
 15) NOTE: PLEASE SEE 210.8A7 FOR ALL
 RECEPTS LOCATED WITHIN 6 FT OF A SINK TO
 BE GFI/ GFI PROTECTED.
 UPPER LAUNDRY ROOM.
  
 16) NOTE: PLEASE SEE KEY NOTE P2 WHICH
 STATES ALL OUTSIDE GFI RECEPTS TO BE
 HALF SWITCHED. PLEASE KNOW, THIS IS NOT
 POSSIBLE AS GFI RECEPTS ARE NOT MADE TO
 BE HALF SWITCH. THERE ARE ONLY LINE OR
 LOAD CONNECTIONS.
 PLEASE SEE 210.52E FOR MINIMUM REQUIRED.
  
 17) NOTE: PLEASE 210.52C1 FOR KITCHEN
 COUNTER SPACE RECEPTACLES MISSING.
  
 18) NOTE: PLEASE SEE MISSING CIRCUITING
 FOR SD'S.
 215.5
  
 19) NOTE: PLEASE SEE PANEL "A" IS
 MISSING LOADS FOR PANEL "C".
 215.5
  
 20) NOTE: PLEASE SEE MISSING MINIMUM
 LOAD CALCULATIONS PER NEC.220
  
 21) NOTE: PLEASE MAKE REFERENCE TO THE
 FOLLOWING CURRENT CODES IN EFFECT. 2002
 NFPA-70, 2002 NFPA-72
  
 22) NOTE: PLEASE SEE FS 471.025 WHICH
 REQUIRES THE LEGAL SIGNATURE FOR THE
 ENGINEER OF RECORD. PLANS APPEAR TO
 CONTAIN INITIALS, IF INDEED THIS IS THE
 LEGAL SIGNATURE, PLEASE PROVIDE A
 SIGNED, DATED, SEALED LETTER TO ATTEST
 TO THE LEGAL SIGNATURE. THIS LETTER IS
 REQUIRED TO BE CORRECTLY NOTARIZED UNDER
 FS 117.05
 PLEASE KNOW, THIS WILL GO INTO OUR
 SIGNATURE FILE FOR ANY FUTURE REFERENCED
 NEEDED FOR SIGNATURE.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
2006-03-18 00:00:00IN ELEC FOR REVIEW.
 REVIEW STOPPED. WILL CONTINUE ON 3/20
 NOTES TO FOLLOW.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-11 Cont ID  
Sent By adarroug Date 2006-07-11 Time 14:14 Rev Time 0.00
Received By adarroug Date 2006-07-11 Time 14:14 Sent To E
Notes
2006-07-11 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-27 Cont ID  
Sent By adarroug Date 2006-06-27 Time 16:22 Rev Time 0.00
Received By adarroug Date 2006-06-27 Time 16:22 Sent To Z
Notes
2006-06-27 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-10 Cont ID  
Sent By alange Date 2006-04-10 Time 14:40 Rev Time 0.00
Received By alange Date 2006-03-14 Time 11:28 Sent To  
Notes
2006-03-14 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-07-17 Cont ID  
Sent By tgordon Date 2006-07-17 Time 11:57 Rev Time 0.30
Received By tgordon Date 2006-07-17 Time 11:57 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-17 Cont ID  
Sent By tgordon Date 2006-03-17 Time 08:05 Rev Time 0.45
Received By tgordon Date 2006-03-17 Time 08:05 Sent To Z
Notes
2006-03-17 00:00:00*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS,
 PER 2004 FBC 13-600.0.ABC .
  
 2) PLEASE PROVIDE DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR GAS FIRE PLACES.
  
 3) PLEASE PROVIDE COMBUSTION AIR
 CALCULATIONS AND OR COMBUSTION AIR FOR
 GAS FIRE PLACES.
  
 4) PLEASE SHOW CLOTHES DRYER VENT
 LOCATION ON MECHANICAL PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-17 Cont ID  
Sent By jleech Date 2006-07-17 Time 12:57 Rev Time 0.00
Received By jleech Date 2006-07-17 Time 12:57 Sent To B
Notes
2006-07-17 00:00:00PROVISO;
  
 FLOOR DRAINS SHALL HAVE A DEEP SEAL TRAP
 OR TRAP PRIMERS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-21 Cont ID  
Sent By jleech Date 2006-03-21 Time 08:33 Rev Time 0.00
Received By jleech Date 2006-03-21 Time 08:33 Sent To B
Notes
2006-03-21 00:00:00DENIED;
 1.SHOW SIZE OF ROOF AREA TO DRAIN TO
 STORAGE TANK, AND SIZE ALL HORIZONTAL
 PIPING. SEE FBC-2004 PLUMBING TABLE
 1106.3.ALSO SHOW SIZE OF ROOF GUTTERS
 AND DOWN SPOUTS.
 2.A/C CONDENSATE IS NOT PERMITED TO GO
 TO SANITARY SEWER. UTILITY ORD. INSTALL
 A DRY WELL FOR CONDENSATE.
 3.SANITARY RISER DIAGRAM IS REQUIRED SEE
 WPB AMENDMENTS TO THE FBC CHAPTER 1,
 SEC106.3.5.4(9)
 4. HORIZONTAL DRY VENTS ARE NOT PERMITED
 IN THE SANITARY DRAINAGE SYSTEM. SEE
 GARAGE FLOOR DRAINS, BIDET, ETC. SEC.
 905.3.
 5.FLOOR DRAINS IN GARAGE AREA MAY
 REQUIRE A SAND AND OIL SEPARATOR. MORE
 DETAIL REQUIRED WHY ARE TWO FLOOR DRAINS
 NEEDED IN GARAGE?
 6.SEE TABLE 704.1 FOR THE MINIMUM SLOPE
 OF HORIZONTAL DRAINAGE PIPE.
 7.PLEASE SHOW A DETAIL OF WATER HEATER
 ASSEMBY. NOT ENOUGH DETAILS. COULD NOT
 FIND MEP SPECIFCATIONS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-07-11 Cont ID  
Sent By mmclean Date 2006-07-11 Time 11:40 Rev Time 0.00
Received By mmclean Date 2006-07-11 Time 11:40 Sent To I
Notes
2006-07-11 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/DECK/SCREEN ENCLOSURE.
  
 NOTE: ANY GATES/WALL/FENCE MUST HAVE A
 SEPERATE PERMIT PULLED WITH CITY OF WEST
 PALM BEACH UTILITY DEPT APPROVAL AND
 OTHER UTILITY DEPT IF APPLICABLE.
  
 NOTE: THE CABANA BATH IS NOT INCLUDED IN
 THIS PROPJECT (N.I.C.)

Review Stop Z ZONING
Rev No 1 Status F Date 2006-03-17 Cont ID  
Sent By mmclean Date 2006-03-17 Time 15:38 Rev Time 0.00
Received By mmclean Date 2006-03-17 Time 15:38 Sent To  
Notes
2006-03-17 00:00:00DENIED,
 1. MUST PROVIDE THE LENGTH OF THE
 DRIVEWAY (SEMI-CIRCULAR)?
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75 % OF
 LANDSCAPE WHITHIN THE FIRST 25FT FRONT
 SETBACK.
  
 2. THE HEIGHT OF THE STRUCTURE EXCEEDS
 THE HEIGHT REQUIREMENT OF 30FT AND AN
 ADDITIONAL 10% FOR CHIMNEY = 33FT
 MAXIMUM HEIGHT.
 3. MUST PROVIDE A COPY OF THE CURRENT
 SURVEY OF PROPERTY.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved