Plan Review Details - Permit 06030386
Plan Review Stops For Permit 06030386
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-07-21 Cont ID  
Sent By jgomez Date 2006-07-21 Time 16:36 Rev Time 0.50
Received By jgomez Date 2006-07-21 Time 16:36 Sent To  
Notes
2006-07-21 00:00:00BUILDING REVIEW PROVISO:
 1- AS AGREED WITH CONTRACTOR, PROVIDE
 COMPLETE AND CORRECT INFORMATION FOR
 STORM SHUTTERS UNDER A SEPARATE PERMIT.
  
 2- PROVIDE COMPLETE PRODUCT APPROVAL FOR
 SWING DOORS. PACKAGE SUBMITTED IS
 MISSING THE DRAWINGS.
  
 3- SOIL TEST REPORT COMPANY (TRIANGLE
 TESTING LAB, INC.) TO PROVIDE THE FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER AS
 REQUIRED BY SEC. 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-23 Cont ID  
Sent By jgomez Date 2006-06-23 Time 15:50 Rev Time 2.00
Received By jgomez Date 2006-06-23 Time 14:06 Sent To  
Notes
2006-06-23 00:00:00BUILDING REVIEW PROVISO:
 1-AS AGREED WITH CONTRACTOR PROVIDE
 COMPLETE AND CORRECT INFORMATION FOR
 STORM SHUTTERS UNDER A SEPARATE PERMIT.
 2-PROVIDE COMPLETE SPECIFICATIONS FOR
 ATTIC VENTILATION. SPECIFY SIZE, NUMBER
 AND LOCATION OF VENTS.
 3-PROVIDE COMPLETE PRODUCT APPROVAL
 FOR ENTRY DOOR AND SIDE GARAGE DOOR.
 INFORMATION SUBMITTED IS MISSING THE
 DRAWINGS.
 4- SOIL TEST REPORT COMPANY TO PROVIDE
 THE FIRM CERTIFICATE OF AUTHORIZATION
 NUMBER IN THE SOIL TEST REPORT COVER
 PAGE AS REQ'D BY 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-07 Cont ID  
Sent By jgomez Date 2006-04-07 Time 12:20 Rev Time 3.00
Received By jgomez Date 2006-04-07 Time 12:20 Sent To  
Notes
2006-04-07 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOC.
  
 2- A) SURVEY WAS PREPARED FOR MORTGAGE
 ONLY, IT CAN'T BE USED FOR PERMITTING.
 SEE GENERAL NOTE #12. NEED SURVEY FOR
 PERMITTING PURPOSES.
 B) SURVEY TO HAVE ORIGINAL SIGNATURE
 AS REQUIRED BY CHAPTER 472 FL. STATUTE.
  
 3- PROVIDE DRAINAGE PLAN AS REQUIRED BY
 SEC. R401.3 OF 2004 RESIDENTIAL CODE.
  
 4- SHEET A-1: A) CLARIFY EXTERIOR
 ELEVATIONS. ROOF PITCH IS DRAWN TO 6:12,
 WHILE WRITTEN PITCH CALLS FOR 4:12.
 REVISE AS REQ'D.
 B) SQUARE FOOTAGES DON'T MATCH ACTUAL
 SQUARE FOOTAGES SHOWN ON FLOOR PLAN.
 REVISE SQUARE FOOTAGE AREAS AND TOTAL
 SQUARE FOOTAGE TO MATCH 1ST FL PLAN.
 PROJECT VALUATION WILL BE CALCULATED
 AFTER CORRECT SQUARE FOOTAGE IS PROVIDED
 AND ADDITIONAL FEES MAY BE DUE.
 C) REVISE TOP OF LINTEL ELEVATION.
 8'-0" HIGH DOORS DON'T FIT IF TOP OF
 LINTEL IS AT 8'-0".
 D) CLARIFY WHAT'S THE BLACK SOLID
 LINE SHOWN ON ARCHED WINDOW BETWEEN
 SINGLE HUNG WINDOW & ARCHED WINDOW.
  
 5- SHEET A-2: A) FOUNDATION PLAN AND
 FIRST FLOOR PLAN ARE MISSING STEP AT
 ENTRY PORCH, GARAGE SIDE DOOR AND REAR
 SLIDING GLASS DOORS.
 B) CLARIFY IF WATER HEATER AND A/C
 ARE LOCATED ON AN ELEVATED AREA FROM
 GARAGE FINISH FLOOR.IF SO, FOOTING
 DOESN'T MATCH. REVISE AS REQUIRED.
 C) SPECIFY ATTIC LOCATION AND SIZE.
 SEC. R807 2004 RESIDENTIAL CODE.
 D) SPECIFY CONCRETE SLAB CONTROL
 JOINTS OR WWM SUPPORTS AND SPACING AS
 REQ'D BY SEC. R506.2.4 2004 RESIDENTIAL
 CODE EXCEPTION #2.
 E) PROVIDE BATHROOM WITH DOOR THAT
 ALLOWS 29" MIN. CLEAR OPENING. SEC. R322
 2004 RESIDENTIAL CODE.
 F) SPECIFY TYPE OF GARAGE DOOR AS
 REQUIRED BY SEC. R309.12004 RES. CODE.
 G) ARCH FRAME DETAIL: SPECIFY HOW LONG
 ARE THE 1/2" WEDGE ANCHORS AND CLARIFY
 FASTENER FOR DIAGONAL BAR. SEE COMMENTS
 ON PLAN. SEC. 106.1.2CITY AMENDMENTS
 TO FBC 2004.
  
 6- SHEET A-3: REVISE TRUSS ANCHOR
 SCHEDULE. NUMBER OF FASTENERS AND LOADS
 SPECIFIED FOR HLPTA-75 DON'T MATCH USP
 CATALOGUE. SEE CURRENT CATALOGUE AND
 PRODUCT APPROVAL. REVISE AS REQUIRED.
  
 7- SHEET D-1:TYPICAL 1 STORY SECTION:
 A) REVISE EAVE DETAIL. DRAWN
 INCORRECTLY. NEED TO SHOW TRUSS LEG.
 B) SPECIFY ROOF VENTILATION AS REQ'D
 BY SEC. R806 2004 RESIDENTIAL CODE.
 C) WHAT'S SBXR-30?
 D) WINDOW SILL SHOWN DOESN'T MATCH
 SPECIFICATIONS.
 E) SPECIFICATIONS FOR ROOF SHEATHING
 DON'T MATCH THOSE SHOWN IN THE ROOF/WALL
 SHEATHING TABLE ON SAME PAGE. REVISE AS
 REQUIRED.
 F) WHERE IS THE UPLIFT TABLE FOR
 REBAR SPACING?
  
 8- REVISE ALL GENERAL NOTES ON SHEET
 D-1. SEE CHAPTER 43 OF 2004 RESIDENTIAL
 CODE FOR ADOPTED STANDARDS AND EDITIONS
 TO BE USED.
  
 9- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) ARCHED FIXED WINDOW. NEED 2004
 FLORIDA CODE VERSION AND DRAWINGS WERE
 NOT SUBMITTED IN THIS PACKAGE.
 B) GARAGE SIDE DOOR.
 C) ENTRY DOOR. NEED 2004 FLORIDA CODE
 VERSION AND DRAWINGS ARE MISSING TOO.
 ***NOTE: ENGINEER OF RECORD TO REVIEW
 AND APPROVE ABOVE MENTIONED PRODUCT
 APPROVALS PRIOR TO SUBMITTAL.
  
 10-STORM SHUTTERS: A) NEED 2004 FLORIDA
 CODE VERSION.
 B) DADE COUNTY NOA #03-0421.12 WAS
 SUPERSEDED. SEE DADE COUNTY WEBSITE.
 C) PROVIDE KEY PLAN AND COMPLETE
 INSTALLATION SCHEDULE. SEE ATTACHED
 SAMPLE WHICH PROVIDES ALL REQUIRED
 INFORMATION FOR PLAN REVIEW.
 D) ENGINEER OF RECORD TO REVIEW
 PRODUCT APPROVAL AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 11- A) SOIL TEST REPORT WAS ADDRESSED TO
 PALM BEACH COUNTY. PROPERTY IS LOCATED
 IN THE CITY OF WEST PALM BEACH. REVISE
 AS REQUIRED.
 B) SEE 2004 RESIDENTIAL CODE FOR
 CORRECT CODE SECTION TO BE REFERENCED.
 AND REVISE AS REQUIRED.
 C) THERE WERE NOT ATTACHMENTS
 SUBMITTED IN THIS PACKAGE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-07-14 Cont ID  
Sent By btrobaug Date 2006-07-14 Time 18:53 Rev Time 0.50
Received By btrobaug Date 2006-07-14 Time 18:40 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-26 Cont ID  
Sent By btrobaug Date 2006-05-26 Time 10:38 Rev Time 0.50
Received By btrobaug Date 2006-05-26 Time 09:49 Sent To M
Notes
2006-05-26 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN
 BE REVIEWED.
  
 3} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 4} INDICATE COMPLIANCE WITH ARTICLE
 250.50 FOR THE GROUNDING ELECTRODE
 SYSTEM. ALL AVAILABLE MUST BE USED ON
 THE RISER. SIZE GEC PER 250.66.
  
 5} THE GARAGE DOOR OPENER DOES NOT
 APPEAR ON THE PANEL SCHEDULE OR THE
 CALCULATIONS.
  
 6} THE GARAGE RECEPTACLES MUST COMPLY
 WITH 210.8(A)(2), GFI.
  
 7} 210.70(A)(1) HABITABLE ROOMS. AT
 LEAST ONE WALL SWITCH-CONTROLLED
 LIGHTING OUTLET SHALL BE INSTALLED IN
 EVERY HABITABLE ROOM AND BATHROOM. SEE
 LIVING ROOM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-16 Cont ID  
Sent By dpalmer Date 2006-03-16 Time 12:17 Rev Time 0.00
Received By dpalmer Date 2006-03-16 Time 07:47 Sent To Z
Notes
2006-03-16 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE CORRELATE CIRCUITING,
 CONDUCTOR SIZES, LOADS, FROM PANEL
 SCHEDULE TO LOAD CALCULATIONS.
 215.5
  
 2)NOTE: PLEASE INCLUDE ALLMININUM
 CONDUCTOR SIZES ON PANEL SCHEDULES.
 PLEASE SEE THESE ARE SHOWN AS BLANK AT
 THIS TIME.
 PLEASE SEE NOTES PERTAINING TO THE SIZES
 SHOWN ON LOAD CALCS, MANY ARE 15A
 CIRCUITS W/ #12 AWG AND SOME ARE NOTA
 LARGE ENOUGH FOR THE MIN REQ'D.
 215.5.310.16.240.4
  
 3)NOTE: PLEASE SEE MIN REQURIED DEDICATE
 BATH (S) CIRCUITS PER 210.52D,210.11C3.
 SHALL BE A MIN OF #12/ 20A.
  
 4)NOTE: PLEASE SEE NUMEROUS SINGLE POLE
 CIRCUITS WHICH ARE SHOWN AS 2-POLE
 CIRCUITS ON PANEL SCHEDULE? PLEASE
 CORRECT AND CORRELATE.
 215.5
  
 5)NOTE: PLEASE SEE CU SHOWS A DISCONNECT
 AND A 220V RECEPT FOR CU??
 PLEASE CLARIFY WHAT THIS 22V RECEPT IS
 FOR?
 440.11.
  
 6)NOTE: PLEASE SEE WATER HEATER IS BEING
 SHOWN WITH A RECEPT FOR UNIT. PLEASE SEE
 422.31 WHICH REQUIRES A DISCONNECT.
 PLEASE SHOW.
  
 7)NOTE: PLEASE CORRELATE RISER, PLANS,
 AND PANEL SCHEDULE.
 PLEASE SEE RISER SHOWS A FEED FROM THE
 MCB PANEL TO ????
 PLEASE SEE PLANS DO NOT SHOW THE METER.
 PLEASE SEE RISER NEEDS TO REFLECT
 CONDUIT FROM METER TO MCB UNDERGROUND,
 OR IF NOT UNDERGROUND, THEN A MAIN
 DISCONNECT WITH OCP WILL BE REQUIRED
 OUTSIDE.
 230.70,230.6
 PLEASE ALSO INDICATE THE AIC RATINGS FOR
 ANY NEW DISCONNECTS. 110.9,215.5
  
 8)NOTE: PLEASE SEE "GFI" NOT E ON PLANS
 WHICH MENTIONS ALL RECEPTS W/IN 15' FROM
 POOL TO BE GFI. THIS IS NOT CORRECT,
 PLEASE SEE 680.22 FOR MIN DISTANCE
 REQUIRED.
  
 9)NOTE: PLEASE SHOW AND LABEL ALL ROOM
 AND AREA DESIGNATIONS ON ELECTRICAL
 PLANS.
 215.5
  
 10)NOTE: PLEASE SEE BATH RM WHICH DOES
 NOT SHOW THE SWITCH CONTROL TO THE LT/
 FAN.
 210.70
  
 11)NOTE: PLEASE SEE A RECEPT IN WHAT MAY
 BE THE DINING ROOM, WHICH SHOWS THE
 RECEPT BEING SWITCHED. PLEASE SEE
 210.52B1,210.70, THIS IS NOT PERMITTED
 IN THE DINING AREA. THESE RECEPTS MUST
 BE PART OF THE ONE OR MORE SMALL
 APPLIANCE CIRCUITS.
 PLEASE ADJUST.
  
 12)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 13)NOTE: PLEASE SEE 210.8A2 FOR GARAGE
 RECEPTS.
  
 14)NOTE: PLEASE SEE KITCHEN PLANS
 INDICATE TWO GFI RECEPTS UNDER KITCHEN
 COUNTER? , IF THESE ARE FOR THE
 DISHWASHER OR DIPOSAL, THESE WOULD BED
 DEDICATED RECEPTS/ NON-GFI.
 PLEASE SEE 210.52C1 AS KITCHEN COUNTER
 SPACE MAY SEEM TO INDICATE COUNTER AT
 POSSIBLY BEING OVER 4' WHICH WOULD
 REQUIRE AN ADDTIONAL GFI RECEPT ON
 COUNTER.
  
 15)NOTE: PLEASE SEE MANY RMS CONTAIN
 WHAT APPEARS TO BE A "J-BOX" , HOWEVER
 PLEASE SEE THIS SYMBOL IS NOT SHOWN ON
 SYMBOL SCHEDULE FOR USE/PURPOSE.
  
 16)NOTE: PLEASE SEE THAT PLANS ARE
 REQUIRED TO CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS.
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.471,481,489 ETC
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-26 Cont ID  
Sent By adarroug Date 2006-07-26 Time 11:58 Rev Time 0.00
Received By adarroug Date 2006-07-26 Time 11:58 Sent To M
Notes
2006-07-26 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-10 Cont ID  
Sent By adarroug Date 2006-07-10 Time 16:09 Rev Time 0.00
Received By adarroug Date 2006-07-10 Time 16:09 Sent To E
Notes
2006-07-10 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-24 Cont ID  
Sent By adarroug Date 2006-05-24 Time 15:03 Rev Time 0.00
Received By adarroug Date 2006-05-24 Time 15:03 Sent To E
Notes
2006-05-24 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-12 Cont ID  
Sent By adarroug Date 2006-05-12 Time 13:28 Rev Time 0.00
Received By adarroug Date 2006-05-12 Time 13:28 Sent To Z
Notes
2006-05-12 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-07 Cont ID  
Sent By jgomez Date 2006-04-07 Time 12:32 Rev Time 0.00
Received By jgomez Date 2006-03-10 Time 13:30 Sent To  
Notes
2006-03-10 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-07-27 Cont ID  
Sent By tgordon Date 2006-07-27 Time 16:00 Rev Time 0.30
Received By tgordon Date 2006-07-27 Time 16:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-07-17 Cont ID  
Sent By tgordon Date 2006-07-17 Time 09:56 Rev Time 0.20
Received By tgordon Date 2006-07-17 Time 09:56 Sent To B
Notes
2006-07-17 00:00:00*** DENIED ***
 1) DUCT LAY-OUT IS TO FADED ON
 MECHANICAL PLANS. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY. PER 2004
 FBC 106.1.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-05-30 Cont ID  
Sent By tgordon Date 2006-05-30 Time 14:06 Rev Time 0.30
Received By tgordon Date 2006-05-30 Time 14:06 Sent To P
Notes
2006-05-30 00:00:00*** DENIED ***
 1) PLEASE SHOW SIZE OF SUPPLY AIR DUCT
 AND GRILL TO FOYER.
  
 2) RETURN AIR TRANSFER GRILL TO MASTER
 BEDROOM IS TO SMALL, SEE NOTE #3 (C)
 EXCEPT.
  
 3)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-03-17 Cont ID  
Sent By tgordon Date 2006-03-17 Time 08:51 Rev Time 0.15
Received By tgordon Date 2006-03-17 Time 08:51 Sent To Z
Notes
2006-03-17 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-06-06 Cont ID  
Sent By jleech Date 2006-06-06 Time 08:16 Rev Time 0.00
Received By jleech Date 2006-06-06 Time 08:16 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-20 Cont ID  
Sent By jleech Date 2006-03-20 Time 08:19 Rev Time 0.00
Received By jleech Date 2006-03-20 Time 08:19 Sent To Z
Notes
2006-03-20 00:00:00DENIED;
 1.PLANS ARE REQUIRED TO CONTAIN THE
 PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS.
 2.SANITARY RISER DIAGRAM IS NOT TO CODE
 AND DOES NOT REFLECT THE FLOOR PLAN.
 RISER DIAGRAM ON ONE SET OF PLANS MARKED
 IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-23 Cont ID  
Sent By mmclean Date 2006-05-23 Time 10:23 Rev Time 0.00
Received By mmclean Date 2006-05-23 Time 10:23 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-07 Cont ID  
Sent By mmclean Date 2006-03-22 Time 07:50 Rev Time 0.00
Received By mmclean Date 2006-03-22 Time 07:50 Sent To  
Notes
2006-03-22 00:00:00DENIED,
 1. THIS SURVEY IS INTENDED RO4 MORTGAGE
 OR REFINANCE PURPOSES ONLY. EXCLUSIVELY
 FOR THIS USE BY THOSE TO WHOM IT IS
 CERTIFIED.THIS SURVEY IS NOT TO BE
 USED FOR CONSTRUCTION, PERMITTING,
 DESIGN OR ANY OTHER USE WITHOUT THE
 WRITTEN CONSENT.
  
 (SEE HIGHLIGHTED SURVEY)
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720