Plan Review Details - Permit 06030193
Plan Review Stops For Permit 06030193
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-10 Cont ID  
Sent By rmcdouga Date 2006-05-10 Time 12:44 Rev Time 0.00
Received By rmcdouga Date 2006-05-10 Time 10:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-27 Cont ID  
Sent By rmcdouga Date 2006-03-27 Time 13:53 Rev Time 0.00
Received By rmcdouga Date 2006-03-27 Time 13:53 Sent To  
Notes
2006-03-27 00:00:00DENIED
  
 1) PLANS SPECIFY THE EXISTING BUILDING
 TYPE AS TYPE IIA, UNPROTECTED. ACCORDING
 TO 2004 FBC TABLE 601 A TYPE IIA
 BUILDING IS ESSENTIALLY ONE HOUR
 PROTECTED. PLEASE CLARIFY. IS THE SPACE
 FIRE SPRINKLERED?
  
 2) THE SCOPE OF WORK IS TO OPEN THE WALL
 BETWEEN TWO TENANT SPACES CREATING ONE
 LARGE SPACE. PROVIDE A DRAWING OF THE
 EXISTING SPACE WITH THE DIMENSIONS AND
 OCCUPANT LOADS FOR THE COMBINED SPACES.
 INDICATE THE EXISTS AND PATHS OF TRAVEL
 FOR THE COMBINED SPACE.
  
 3) SPECIFY ON PLANS THAT THE ALTERATIONS
 TO THE PRIMARY FUNCTION AREA COMPLY WITH
 FLORIDA ACCESIBILITY CODE AS REQUIRED BY
 2004 FBC 11-4.1.6.
  
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-05-02 Cont ID  
Sent By nmccray Date 2006-05-02 Time 10:54 Rev Time 0.00
Received By nmccray Date 2006-05-02 Time 10:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-03-09 Cont ID  
Sent By nmccray Date 2006-03-09 Time 14:34 Rev Time 0.00
Received By nmccray Date 2006-03-09 Time 10:57 Sent To  
Notes
2006-03-09 00:00:00DENIED:
  
 1) SHALL COMPLY WITH NFPA 101 LIFE
 SAFETY CODE, 2003 EDITION, AND NFPA 1
 UNIFORM FIRE CODE, 2003.
  
 2) SINCE THIS BUILDING WILL BE OCCUPLIED
 WHILE THE DEMOLITION, RENOVATION, AND
 CONSTRUCTION ARE GOING ON, IT'S SHALL
 COMPLY NFPA 241.
  
 3) PLEASE PROVIDE A SEATING LAYOUT OF
 THE DINING ROOM, ON THE FLOOR PLAN FOR
 APPROVAL BY THIS OFFICE.
  
 4) IS THE TENANT SEPARATION ONE HOUR
 RATED ON BOTH SIDE OF THIS PROJECT.
  
 5) THE REAR EXIT DOOR APPEARS TO BE
 OBSTRUCTED BY THE OFFICE AND RESTROOM
 DOORS.
  
 6) INTERIOR WALLS AND CEILING FINISH
 MATERIALS COMPLYING WITH SECTION 10.2
 SHALL BE CLASS A THROUGHOUT.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-20 Cont ID  
Sent By adarroug Date 2006-04-20 Time 15:40 Rev Time 0.00
Received By adarroug Date 2006-04-20 Time 15:40 Sent To  
Notes
2006-04-27 00:00:00TO BOB #9
2006-04-20 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-27 Cont ID  
Sent By rmcdouga Date 2006-03-27 Time 15:42 Rev Time 0.00
Received By rmcdouga Date 2006-03-08 Time 14:55 Sent To  
Notes
2006-03-08 00:00:00TO "BOB"#10