Plan Review Details - Permit 06030124
Plan Review Stops For Permit 06030124
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-30 Cont ID  
Sent By adarroug Date 2006-03-30 Time 15:28 Rev Time 0.00
Received By adarroug Date 2006-03-30 Time 15:28 Sent To M
Notes
2006-03-30 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-07 Cont ID  
Sent By tgordon Date 2006-03-07 Time 11:10 Rev Time 0.00
Received By tgordon Date 2006-03-04 Time 15:54 Sent To  
Notes
2006-03-04 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-03-31 Cont ID  
Sent By tgordon Date 2006-03-31 Time 15:25 Rev Time 0.30
Received By tgordon Date 2006-03-31 Time 15:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-07 Cont ID  
Sent By tgordon Date 2006-03-07 Time 10:59 Rev Time 0.30
Received By tgordon Date 2006-03-07 Time 10:59 Sent To  
Notes
2006-03-07 00:00:00*** DENIED ***
 1) ENERGY CALAULATIONS SUBMITTED WITH
 BUILDING PERMIT IS CALLING FOR 28,000
 TOTAL BTU'S, PLANS SUBMITTED ARE CALLING
 FOR 31,200 TOTAL BTU'S. THE PLANS CAN
 NOT CALL FOR MORE THAN THE ENERGY CAL'S.
 PLEASE CORRECT.
  
 2) PLANS ARE CALLING FOR MORE SENSIBLE
 BTU'S THAN THE MANUAL J CAL. WILL ALLOW
 PLEASE CORRECT.
  
 3) PLEASE SHOW THE COPPER LINE SIZES,
 AND THE CONDENSATE DRAIN LINE LOCATION
 ON THE MECHANICAL PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  