Plan Review Details - Permit 06030031
Plan Review Stops For Permit 06030031
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-24 Cont ID  
Sent By btrobaug Date 2006-03-24 Time 14:34 Rev Time 0.33
Received By btrobaug Date 2006-03-24 Time 14:23 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-09 Cont ID  
Sent By btrobaug Date 2006-03-09 Time 11:26 Rev Time 0.50
Received By btrobaug Date 2006-03-09 Time 11:12 Sent To PC
Notes
2006-03-09 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ENGINEER MUST SIGN AND SEAL THE
 PLANS PER 471 FS.
  
 2} THE PANEL SHOWN ON THEW PLAN MUST
 COMPLY WITH 110.26 CLEARANCE
 REQUIREMENTS.
  
 3} INDICATE THE PROPOSED LOCATIONS OF
 ALL DEVICES TO BE ADDED SO THAT
 COMPLIANCE WITH THE 2002 NEC CAN BE
 REVIEWED FOR CORRECT CIRCUITING AND
 SPACING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 13:16 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 13:16 Sent To E
Notes
2006-03-24 00:00:00TO BT'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-09 Cont ID  
Sent By btrobaug Date 2006-03-09 Time 11:12 Rev Time 0.00
Received By btrobaug Date 2006-03-03 Time 08:48 Sent To E
Notes
2006-03-03 00:00:00TO "E" BOX