Plan Review Details - Permit 06021241
Plan Review Stops For Permit 06021241
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-13 Cont ID  
Sent By adarroug Date 2007-06-13 Time 14:22 Rev Time 0.00
Received By adarroug Date 2007-06-13 Time 14:22 Sent To M
Notes
2007-06-13 14:22:53TO "TGORDON" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-15 Cont ID  
Sent By adarroug Date 2006-07-15 Time 10:59 Rev Time 0.00
Received By adarroug Date 2006-07-15 Time 10:59 Sent To M
Notes
2006-07-15 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-27 Cont ID  
Sent By adarroug Date 2006-03-27 Time 12:31 Rev Time 0.00
Received By adarroug Date 2006-03-27 Time 12:31 Sent To M
Notes
2006-03-27 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-03 Cont ID  
Sent By tgordon Date 2006-03-03 Time 09:59 Rev Time 0.00
Received By tgordon Date 2006-03-02 Time 10:41 Sent To  
Notes
2006-03-02 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-06-14 Cont ID  
Sent By tgordon Date 2007-06-14 Time 09:07 Rev Time 0.30
Received By tgordon Date 2007-06-14 Time 09:07 Sent To  
Notes
2007-06-14 09:07:42RE-STAMP OF MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-07-17 Cont ID  
Sent By tgordon Date 2006-07-17 Time 15:39 Rev Time 0.20
Received By tgordon Date 2006-07-17 Time 15:39 Sent To  
Notes
2006-07-17 00:00:00REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-03-27 Cont ID  
Sent By tgordon Date 2006-03-27 Time 14:48 Rev Time 0.45
Received By tgordon Date 2006-03-27 Time 14:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-03 Cont ID  
Sent By tgordon Date 2006-03-03 Time 09:41 Rev Time 0.30
Received By tgordon Date 2006-03-03 Time 09:41 Sent To  
Notes
2006-03-03 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 2) ENERGY CAL'S. ARE CALLING FOR 62,000
 TOTAL BTU'S, PLANS ARE CALLING FOR
 66,000 TOTAL BTU'S. THE PLANS CAN NOT
 CALL FOR MORE BTU'S THAN THE ENERGY
 CAL'S, PLEASE CORRECT.
  
 3) PLEASE NOTE THAT THE SECOND FLOOR,
 PLAN IS FLIPED.
  
 4) PLEASE SHOW THE DUCT (FLEX) SIZES FOR
 BEDROOM #2 AND #3.
  
 5) PLEASE SHOW THE HEATER SIZE FOR AHU
 #2, COPPER LINE SIZES, AND CONDENSATE
 DRAIN LINE LOCATIONS FOR BOLTH SYSTEMS.
  
 6) PLEASE SHOW ON ALL SHEETS JOB
 ADDRESS, COMPANY INFOMATION WITH PHONE
 NUMBER, AND LICENSE NUMBER.
  
 7)ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 8)CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  