Plan Review Details - Permit 06021131
Plan Review Stops For Permit 06021131
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-04-17 Cont ID  
Sent By amorse Date 2006-04-17 Time 11:36 Rev Time 0.33
Received By amorse Date 2006-04-17 Time 11:36 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-24 Cont ID  
Sent By amorse Date 2006-03-24 Time 08:15 Rev Time 0.50
Received By amorse Date 2006-03-24 Time 08:15 Sent To PC
Notes
2006-03-24 00:00:00 
  
 DENIED
  
 1) POOL SAFETY REQUIREMENTS PER R4101.17
 SHALL BE ADDED TO NOTES AND ARE REQUIRED
 TO BE IN PLACE AT POOL FINAL INSPECTION
 PER 4101.19 FBC
  
 2) PROOF OF OWNERSHIP IS REQUIRED PLEASE
 SEE ATTACHED PROPERTY APPRAISERS OWNER
 INFORMATION
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-03-13 Cont ID  
Sent By btrobaug Date 2006-03-13 Time 07:41 Rev Time 0.33
Received By btrobaug Date 2006-03-13 Time 07:36 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-03-15 Cont ID  
Sent By mperson Date 2006-03-15 Time 11:15 Rev Time 0.00
Received By mperson Date 2006-03-15 Time 11:14 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-17 Cont ID  
Sent By adarroug Date 2006-08-17 Time 09:02 Rev Time 0.00
Received By adarroug Date 2006-08-17 Time 09:02 Sent To P
Notes
2006-08-17 00:00:00TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-12 Cont ID  
Sent By adarroug Date 2006-04-12 Time 16:39 Rev Time 0.00
Received By adarroug Date 2006-04-12 Time 16:39 Sent To P
Notes
2006-04-12 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 10:58 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 10:58 Sent To E
Notes
2006-03-24 00:00:00 
  
 DENIED
  
 1) SAFETY REQUIREMENT PER R4101.17 SHALL
 BE ADDED TO DRAWINGS AND SHALL BE IN
 PLACE AT TIME OF POOL FINAL INSPECTION
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
2006-03-09 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-24 Cont ID  
Sent By amorse Date 2006-03-24 Time 08:16 Rev Time 0.00
Received By amorse Date 2006-03-02 Time 12:28 Sent To  
Notes
2006-03-02 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-10-31 Cont ID  
Sent By pschmitz Date 2006-10-31 Time 11:48 Rev Time 0.00
Received By pschmitz Date 2006-10-31 Time 11:48 Sent To PC
Notes
2006-10-31 11:49:59RE SUB LETER FROM ENGINEER OF RECORD FOR PSI TEST ON
 MAIN DRAIN.

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-08-11 Cont ID  
Sent By pschmitz Date 2006-08-11 Time 14:35 Rev Time 0.00
Received By pschmitz Date 2006-08-11 Time 14:34 Sent To  
Notes
2006-08-11 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT: SUBMITTAL DATED 8-7-06
 PREVIOUS NOTE FOR PSI TEST NOT ADDRESSED
  
  
 SUBMITTAL LETTER DATED 7-26-06 DENIED
  
 1)LETTER FROM ENGINEER, SHALL INCLUDE
 THEPSI TEST WAS CONDUCTED, AND THE PSI
 AT THE TIME OF INSPECTION.
 2 A COPY OF A RAISED SEAL FROM THE
 ENGINEER IS NOT ACCEPTABLE.
 TWO LETTERS WITH A RAISED SEAL IS
 REQUIRED.
 3) APPLICATION SUBMITTAL WITH REFERENCE
 TO GARY SALFELDER IS INCORRECT.
 DAVID BISHOP IS THE INSPECTOR ON THE
 INSPECTION LOG.
  
 END OF COMMENTS QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-07-27 Cont ID  
Sent By pschmitz Date 2006-07-27 Time 10:55 Rev Time 0.00
Received By pschmitz Date 2006-07-27 Time 10:55 Sent To  
Notes
2006-07-27 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
  
 SUBMITTAL LETTER DATED 7-26-06 DENIED
  
 1)LETTER FROM ENGINEER, SHALL INCLUDE
 THEPSI TEST WAS CONDUCTED, AND THE PSI
 AT THE TIME OF INSPECTION.
 2 A COPY OF A RAISED SEAL FROM THE
 ENGINEER IS NOT ACCEPTABLE.
 TWO LETTERS WITH A RAISED SEAL IS
 REQUIRED.
 3) APPLICATION SUBMITTAL WITH REFERENCE
 TO GARY SALFELDER IS INCORRECT.
 DAVID BISHOP IS THE INSPECTOR ON THE
 INSPECTION LOG.
  
 END OF COMMENTS QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-04-14 Cont ID  
Sent By mperson Date 2006-04-14 Time 11:33 Rev Time 0.33
Received By mperson Date 2006-04-14 Time 11:33 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-15 Cont ID  
Sent By mperson Date 2006-03-15 Time 11:15 Rev Time 0.33
Received By mperson Date 2006-03-15 Time 11:15 Sent To B
Notes
2006-03-15 00:00:00DENIED
 REFERENCE:FBC-2004 424.2 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW:
  
 1. ON SHEET 1 OF 2 THE V/L - VACUUM LINE
 W/LOCK CAP AND THE A/V - ATMOSPHERIC
 VENT ARE MIS-LABELED ON THE POOL
 DRAWING. PLEASE CORRECT.
  
 END OF COMMENTS:
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS

Review Stop Z ZONING
Rev No 1 Status P Date 2006-03-08 Cont ID  
Sent By mmclean Date 2006-03-08 Time 15:47 Rev Time 0.00
Received By mmclean Date 2006-03-08 Time 15:47 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved