Plan Review Details - Permit 06021125
Plan Review Stops For Permit 06021125
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-07-26 Cont ID  
Sent By jwitmer Date 2006-07-26 Time 12:15 Rev Time 0.56
Received By jwitmer Date 2006-07-26 Time 12:15 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-07-18 Cont ID  
Sent By jwitmer Date 2006-07-18 Time 08:20 Rev Time 0.77
Received By jwitmer Date 2006-07-18 Time 08:20 Sent To PC
Notes
2006-07-18 00:00:00PERMIT: 06021125
 ADD: 501 7TH ST
 CONT: RINKER MATERIALS OF FLORIDA
 TEL: (561)820-8371
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1) 2ND REQUEST,
 FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) COMMENT# 7 FROM THE PREVIOUS REVIEW,
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 NOTE: NO ROOFING SUB-PERMIT APPLIED FOR,
 WILL REQUIRE PRODUCT APPROVAL FOR
 ROOFING MATERIAL TO BE REVIEWED BY THE
 DESIGN PROFESSIONAL BEFORE SUBMISSION TO
 THE CITY FOR REVIEW UNDER SEPERATE
 PERMIT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-01 Cont ID  
Sent By dpalmer Date 2006-07-17 Time 17:18 Rev Time 0.77
Received By jwitmer Date 2006-06-01 Time 07:39 Sent To  
Notes
2006-06-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06021125
 ADD: 501 7TH ST
 CONT: RINKER MATERIALS OF FLORIDA
 TEL: (561)820-8371
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1) 2ND REQUEST,
 FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4) IT APPEARS THAT THERE IS A DOOR AND
 WINDOW IN THIS BUILDING,FL BLD CODE
 1606.1.5: COMPONENTS & CLADDING, PROVIDE
 2 COPIES(3 IF THRESH- OLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING
 REPORTS,MISSING REPORTS ARE AS FOLLOWS:
 A) WINDOW
 B) DOOR
 C) SHUTTERS
 D) ROOFING ASSEMBLIES
  
 5) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8)BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-08 Cont ID  
Sent By jwitmer Date 2006-05-08 Time 10:05 Rev Time 1.55
Received By jwitmer Date 2006-05-08 Time 10:05 Sent To  
Notes
2006-05-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06021125
 ADD: 501 7TH ST
 CONT: RINKER MATERIALS OF FLORIDA
 TEL: (561)820-8371
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 3) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 F) SQ. FT. UNDER ROOF (TOTAL)
 G) OCCUPANT LOAD
 H) FLOOD ZONE
  
 4) IT APPEARS THAT THERE IS A DOOR AND
 WINDOW IN THIS BUILDING,FL BLD CODE
 1606.1.5: COMPONENTS & CLADDING, PROVIDE
 2 COPIES(3 IF THRESH- OLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING
 REPORTS,MISSING REPORTS ARE AS FOLLOWS:
 A) WINDOW
 B) DOOR
 C) SHUTTERS
 D) ROOFING ASSEMBLIES
  
 5) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8)BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-07-17 Cont ID  
Sent By dpalmer Date 2006-07-17 Time 17:18 Rev Time 0.00
Received By dpalmer Date 2006-07-17 Time 17:11 Sent To B
Notes
2006-07-17 00:00:00REDLINED.250.20,250.30,250.66

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-16 Cont ID  
Sent By dpalmer Date 2006-06-16 Time 19:20 Rev Time 0.00
Received By dpalmer Date 2006-06-16 Time 19:08 Sent To  
Notes
2006-06-16 00:00:00**UNSAT ** 2ND REVIEW**
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW AND SOME NEW COMMENTS DUE TO
 PLANS SUBMITTED.
  
 1) NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANEL SCHEDULE FOR MDP. PLEASE SEE
 T-1.
 215.5
  
 2) NOTE: PLEASE INDICATE ALL GROUNDING
 ATTACHMENTS FOR THE TRANSFORMERS ARE
 REQUIRED PER 250.30,250.66 ETC.
 PLEASE SEE T-1 DOES NOT INDICATE THIS
 ATTACHMENT.?
  
 3) NOTE: PLEASE SEE 450.3 FOR MAX OCP
 FOR THE TRANSFORMERS AS SHOWN TO BE
 125%.
 PLEASE SEE MDP 70A 60A FOR T-1 AND PP
 RISER SHOWS 60A FOR T-2.
 PLEASE SEE RISER FOR T-2, IS THIS A
 3-POLE DISC WITH ONLY 2-PHASE'S BEING
 USED?
 THIS IS BEING ASSUMED AT THIS TIME, BUT
 PLEASE CLARIFY.
 PLEASE SEE DISC NOTE #3, 70A'S??
 PLEASE CORRELATE AT STATED IN NOTE #1
 ABOVE.
  
 4) NOTE: PLEASE SEE THE CODES ON 1-E-1
 SHALL BE REFLECTED TO THE 2004 FBC AND
 THE 2002 NEC.
  
 5) NOTE: PLEASE SEE A NOTE OR
 INFORMATION COULD NOT BE LOCATED
 DENOTING ANY CLASS LOCATIONS.
  
 ** PLEASE SEE BUILDING REVIEW COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-29 Cont ID  
Sent By dpalmer Date 2006-03-29 Time 18:05 Rev Time 0.00
Received By dpalmer Date 2006-03-29 Time 17:45 Sent To  
Notes
2006-03-29 00:00:00************** UNSAT ***************
  
 1) NOTE: PLEASE LIST CURRENT CODES IN
 EFFECT, NFPA-70 2002, NFPA-101 2003.
  
 2) NOTE: PLEASE SEE SERVICE GROUNDING
 ELECTRODE SYSTEM. SHOWS BLDG STEEL, IS
 THIS NOT THE FOOTER STEEL OR IS THERE
 BOTH? IF BOTH THEN FOOTER STEEL WILL
 ALSO BE REQUIRED. IF NO "BLDG STEEL",
 PLEASE CALL OUT FOR FOOTER STEEL.
 250.50
  
 3) NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM AT TRANSFORMER PER 250.30,250.66.
 PLEASE INCLUDE SIZE OF THE GEC.
 215.5
  
 4) NOTE: PLEASE SEE MAX OCP FOR
 TRANSFORMER SHALL BE BASED ON 450.3
 PLEASE KNOW, THE KVA FOR T-2 IS NOT
 CLEAR, A MODEL # IS SHOWN WHICH TENDS TO
 LEAD TO THIS TRANSFORMER AS ALSO BEING
 25 KVA? IF SO, IN EITHER CASE PLEASE SEE
 450.3 FOR MAX OCP.
 125%).
  
 5) NOTE: PLEASE SEE T-2, AND SEE 240.21,
 RISER SHOWS "TAPPING" A "TAP". PLEASE
 KNOW THIS NOT PERMITTED. A TAP SHALL
 TERMINTE IN A SINGLE MEANS OF OCP.
 215.5
  
 6) NOTE: PLEASE SEE 250.6,250.24B. AN
 "EQUIPMENT GROUNDING CONDUCTOR" IS BEING
 SHOWN FROM METER TO THE FIRST MEANS OF
 DISCONNECT FOR MDP SERVICE.
 PLEASE KNOW, THIS SHALL ONLY BE
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
 215.5
  
 7) NOTE: PLEASE SEE SEE CONDUCTORS AND
 CONDUIT SHOWN ON MDP RISER FOR FEED TO
 T-1??
 SEEMS TO BE AN ERROR/ OR MISPRINT.
 215.5
  
 8) NOTE: PLEASE SPECIFY ANY AREAS PER
 NEC ART 500.
 PLEASE LIST ANY AREA CHEMICAL FOR FUEL,
 MIXING ETC WHICH MAY CREATE AN CLASS
 LOCATION. PLEASE LIST OR SHOW.
  
 9) NOTE: PLEASE SPECIFY DEPT OF CONDUITS
 PER 300.5 IN AREAS ON SITE PLANS E-1
  
 PLEASE SEE NAY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-06-19 Cont ID  
Sent By mcarsill Date 2006-06-19 Time 12:45 Rev Time 0.00
Received By mcarsill Date 2006-06-19 Time 12:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-05-10 Cont ID  
Sent By mwennerg Date 2006-05-10 Time 14:35 Rev Time 0.00
Received By mwennerg Date 2006-05-10 Time 14:35 Sent To  
Notes
2006-05-10 00:00:00******PROVISO******
  
 1) PLEASE SEE COMMENTS REF: CORRECT CODE
 EDITIONS.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHER
 SHALL BE LOCATED NOT TO EXCEED 75'
 TRAVEL DISTANCE REQUIREMENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-25 Cont ID  
Sent By adarroug Date 2006-07-25 Time 16:32 Rev Time 0.00
Received By adarroug Date 2006-07-25 Time 16:32 Sent To  
Notes
2006-07-25 00:00:00TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-06 Cont ID  
Sent By adarroug Date 2006-07-06 Time 16:50 Rev Time 0.00
Received By adarroug Date 2006-07-06 Time 16:50 Sent To  
Notes
2006-07-06 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-30 Cont ID  
Sent By adarroug Date 2006-05-30 Time 11:08 Rev Time 0.00
Received By adarroug Date 2006-05-30 Time 11:08 Sent To  
Notes
2006-06-15 00:00:00TO "COMM" BD#1
2006-05-30 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 19:48 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 19:48 Sent To  
Notes
2006-03-24 00:00:00TO COMM BOARD # 13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-12 Cont ID  
Sent By adarroug Date 2006-05-08 Time 13:36 Rev Time 0.00
Received By adarroug Date 2006-02-28 Time 18:31 Sent To  
Notes
2006-02-28 00:00:00WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 1 Status P Date 2006-06-29 Cont ID  
Sent By astelly Date 2006-06-29 Time 09:29 Rev Time 0.00
Received By astelly Date 2006-06-29 Time 09:28 Sent To  
Notes
***NONE***