Plan Review Details - Permit 06021076
Plan Review Stops For Permit 06021076
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-05-06 Cont ID  
Sent By shill Date 2006-05-06 Time 17:19 Rev Time 0.00
Received By shill Date 2006-05-06 Time 17:19 Sent To  
Notes
2006-05-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 FOURTH REVIEW.SOME COMMENTS WERE
 ADDRESSED.OTHERS STILL PENDING, SEE
 CHECKED ITEMS BELOW:
  
  
 _XX_6.)FOR THE FLAT DECK, SELECT THE
 APPROVED ASSEMBLY YOU ARE USING.THIS
 CAN BE FOUND BETWEEN PAGES 7 AND 19 OF
 THE NOA.
  
 NEW COMMENT:
  
 7.)IF YOU SELECT AN APPROVED ASSEMBLY
 WHICH REFERS TO PRODUCT LIMITATION #7,
 PROVIDE ENGINEERING AS REQUIRED BY THE
 NOA.SEE PAGE 20, GENERAL LIMITATION 7.
 NOTE THAT ASSEMBLIES WITH GENERAL
 LIMITATION9 CANNOT BE USED.
  
 8.)FILL OUT THE RESUBMITTAL FORM
 COMPLETELY.THE BUILDING PERMIT # BOX
 WAS LEFT BLANK.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-04-21 Cont ID  
Sent By shill Date 2006-04-21 Time 18:50 Rev Time 0.00
Received By shill Date 2006-04-21 Time 18:50 Sent To  
Notes
2006-04-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 THIRD REVIEW.SOME COMMENTS WERE
 ADDRESSED.OTHERS STILL PENDING, SEE
 CHECKED ITEMS BELOW:
  
 _XX_1.)A NOTICE OF COMMENCEMENT
 MUST BE FILED WITH THE CLERK OF COURTS
 BEFORE A PERMIT CAN BE ISSUED.THE NOC
 SUBMITTED DOES NOT CONTAIN THE LEGAL
 DESCRIPTION AS REQUIRED BY FS713.13.
  
 ____2.)CONTRACTOR IS TO PROVIDE THE
 MEAN ROOF HEIGHT ON THE APPLICATION.
  
 ____3.)CONTRACTOR IS TO PROVIDE THE
 ROOF PITCH ON THE APPLICATION.
  
 ____4.)CONTRACTOR IS TO PROVIDE THE
 ROOF DECK TYPE ON THE APPLICATION.
  
 _XX_5.)FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED IN ADDITION TO
 THE EVALUATION REPORT SUBMITTED,
 FAC9B72.WWW.FLORIDABUILDING.ORG
 THE DOCUMENT SUBMITTED WAS A LIST OF ALL
 PRODUCTS FOR THIS TYPE (MODIFIED).
 PRINT THE PRODUCT APPROVAL FOR THIS
 SPECIFIC PRODUCT.
  
 _XX_6.)FOR THE FLAT DECK, SELECT THE
 APPROVED ASSEMBLY YOU ARE USING.
  
 ____7.)THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ____.
  
 ____8.)THE SYSTEM PROVIDED STATES
 LIMITATION #9, ENHANCED FASTENING NOT
 ALLOWED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-24 Cont ID  
Sent By shill Date 2006-02-24 Time 07:40 Rev Time 0.00
Received By shill Date 2006-02-24 Time 07:40 Sent To  
Notes
2006-02-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 FROM PREVIOUS LIST; PACKAGE WAS
 RESUBMITTED WITH NO COMMENTS ADDRESSED:
  
 _XX_1.)A NOTICE OF COMMENCEMENT
 MUST BE FILED WITH THE CLERK OF COURTS
 BEFORE A PERMIT CAN BE ISSUED.THE NOC
 SUBMITTED DOES NOT CONTAIN THE LEGAL
 DESCRIPTION AS REQUIRED BY FS713.13.
  
 _XX_2.)CONTRACTOR IS TO PROVIDE THE
 MEAN ROOF HEIGHT ON THE APPLICATION.
  
 _XX_3.)CONTRACTOR IS TO PROVIDE THE
 ROOF PITCH ON THE APPLICATION.
  
 _XX_4.)CONTRACTOR IS TO PROVIDE THE
 ROOF DECK TYPE ON THE APPLICATION.
  
 _XX_5.)FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED IN ADDITION TO
 THE EVALUATION REPORT SUBMITTED,
 FAC9B72.WWW.FLORIDABUILDING.ORG
 THE DOCUMENT SUBMITTED WAS A LIST OF ALL
 PRODUCTS FOR THIS TYPE (MODIFIED).
 PRINT THE PRODUCT APPROVAL FOR THIS
 SPECIFIC PRODUCT.
  
 _XX_6.)FOR THE FLAT DECK, SELECT THE
 APPROVED ASSEMBLY YOU ARE USING.
  
 ____7.)THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ____.
  
 ____8.)THE SYSTEM PROVIDED STATES
 LIMITATION #9, ENHANCED FASTENING NOT
 ALLOWED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-23 Cont ID  
Sent By shill Date 2006-02-23 Time 12:58 Rev Time 0.00
Received By shill Date 2006-02-23 Time 12:58 Sent To  
Notes
2006-02-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
  
 _XX_1.)A NOTICE OF COMMENCEMENT
 MUST BE FILED WITH THE CLERK OF COURTS
 BEFORE A PERMIT CAN BE ISSUED.THE NOC
 SUBMITTED DOES NOT CONTAIN THE LEGAL
 DESCRIPTION AS REQUIRED BY FS713.13.
  
 _XX_2.)CONTRACTOR IS TO PROVIDE THE
 MEAN ROOF HEIGHT ON THE APPLICATION.
  
 _XX_3.)CONTRACTOR IS TO PROVIDE THE
 ROOF PITCH ON THE APPLICATION.
  
 _XX_4.)CONTRACTOR IS TO PROVIDE THE
 ROOF DECK TYPE ON THE APPLICATION.
  
 _XX_5.)FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED IN ADDITION TO
 THE EVALUATION REPORT SUBMITTED,
 FAC9B72.WWW.FLORIDABUILDING.ORG
 THE DOCUMENT SUBMITTED WAS A LIST OF ALL
 PRODUCTS FOR THIS MANUFACTURER.PRINT
 THE PRODUCT APPROVAL FOR THIS SPECIFIC
 PRODUCT.
  
 _XX_6.)FOR THE FLAT DECK, SELECT THE
 APPROVED ASSEMBLY YOU ARE USING.
  
 ____7.)THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ____.
  
 ____8.)THE SYSTEM PROVIDED STATES
 LIMITATION #9, ENHANCED FASTENING NOT
 ALLOWED.
  
  
  