Plan Review Details - Permit 06021006
Plan Review Stops For Permit 06021006
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-09-26 Cont ID  
Sent By lursu Date 2006-09-26 Time 12:02 Rev Time 0.00
Received By lursu Date 2006-09-26 Time 12:02 Sent To  
Notes
2006-09-26 00:00:00NEW ADDRESS WILL BE ISSUED TO THE
 APARTMENT BUILDNG IN THE BACK BASED ON
 THE MAIN ENTRANCE FROM 11TH ST.THE
 REVISED PLANS MUST REFLECT THE NEW
 ADDRESS OF 609 11TH ST.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-11-15 Cont ID  
Sent By shill Date 2006-11-15 Time 11:43 Rev Time 0.00
Received By shill Date 2006-11-15 Time 11:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-09-11 Cont ID  
Sent By shill Date 2006-09-11 Time 14:08 Rev Time 0.00
Received By shill Date 2006-09-11 Time 14:07 Sent To  
Notes
2006-09-11 00:00:00****PROVISO****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 PROVIDE SPEC SHEET FOR 2 HOUR BLOCK
  
 INTERIOR FINISHES TO COMPLY WITH FBC
 TABLE 803.5.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-08-08 Cont ID  
Sent By shill Date 2006-08-08 Time 08:50 Rev Time 0.00
Received By shill Date 2006-08-08 Time 08:42 Sent To  
Notes
2006-08-08 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS REVIEW:
  
 1.)ADDRESSED.
  
 2.)DECLARE OCCUPANCY, FBC3.
 PLEASE DECLARE ONE OF THE OCCUPANCY
 CLASSIFICATIONS IN THIS CHAPTER, SEE
 FBC3310.BASED ON YOUR DESCRIPTION OF
 USE, IT APPEARS TO BE R2.
  
 ALL OTHER COMMENTS BELOW NOT ADDRESSED
  
 3.)SPECIFY FLOORING ON THE PLAN.SHOW
 COMPLIANCE WITH FBC1207.
  
 4.)ARE ALL FLOOR FINISHES TILE?ARE
 ANY CARPET?SEE FBC EB503.2.NOTE -
 ADDRESSED; TILE FLOORING.
  
 5.)PROVIDE FIRE RESISTANCE
 INFORMATION, EITHER RATED ASSEMBLY OR
 SHOW CALCULATED FIRE RESISTANCE, FOR THE
 TENANT SEPARATIONS BOTH HORIZONTAL AND
 VERTICAL.
  
 6.)ENERGY CALCS ARE NO LONGER IN THE
 PACKAGE.
  
 7.)SPECIFY INTERIOR FINISH
 CLASSIFICATION, FBC EB503.1, FBC803.5.
  
 8.)THE PLANS SHOW LAUNDRY FACILITIES
 UNDER THE STAIRS.WAS THIS PERMITTED?
 PROVIDE PERMIT INFORMATION, PLUMBING AND
 ELECTRIC.
  
 NEW COMMENT:
  
 SEE ATTACHED FS553.80(2)(B).

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-06-12 Cont ID  
Sent By shill Date 2006-06-12 Time 16:17 Rev Time 0.00
Received By shill Date 2006-06-12 Time 16:15 Sent To  
Notes
2006-06-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)DECLARE LEVEL OF ALTERATION, FBC EB
 3.
  
 2.)DECLARE OCCUPANCY, FBC3.
  
 3.)SPECIFY FLOORING ON THE PLAN.SHOW
 COMPLIANCE WITH FBC1207.
  
 4.)ARE ALL FLOOR FINISHES TILE?ARE
 ANY CARPET?SEE FBC EB503.2.
  
 5.)PROVIDE FIRE RESISTANCE
 INFORMATION, EITHER RATED ASSEMBLY OR
 SHOW CALCULATED FIRE RESISTANCE, FOR THE
 TENANT SEPARATIONS BOTH HORIZONTAL AND
 VERTICAL.
  
 6.)THE ENERGY CALC FORM SUBMITTED IS
 FOR ONE AND TWO FAMILY AND REFERS TO TWO
 UNITS.THIS IS A FOUR UNIT (COMMERCIAL
 RESIDENTIAL) STRUCTURE.FBC13-4.
  
 7.)SPECIFY INTERIOR FINISH
 CLASSIFICATION, FBC EB503.1, FBC803.5.
  
 8.)THE PLANS SHOW LAUNDRY FACILITIES
 UNDER THE STAIRS.WAS THIS PERMITTED?
 PROVIDE PERMIT INFORMATION, PLUMBING AND
 ELECTRIC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-03-28 Cont ID  
Sent By shill Date 2006-03-25 Time 14:20 Rev Time 0.00
Received By shill Date 2006-03-25 Time 14:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-19 Cont ID  
Sent By shill Date 2006-03-19 Time 12:36 Rev Time 0.00
Received By shill Date 2006-03-19 Time 12:36 Sent To  
Notes
2006-03-19 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)ARE THE CABINETS BEING INSTALLED
 SAME SIZES, SAME LOCATIONS?IF NOT,
 PROVIDE A PLAN.
  
 2.)THE FLORIDA STATE PRODUCT APPROVAL
 IS FOR THE FBC2001.PLEASE PROVIDE THIS
 FOR FBC2004. FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED, FAC9B72.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-12-12 Cont ID  
Sent By btrobaug Date 2006-12-12 Time 12:08 Rev Time 1.00
Received By btrobaug Date 2006-12-12 Time 07:37 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-10-20 Cont ID  
Sent By btrobaug Date 2006-10-20 Time 15:21 Rev Time 0.50
Received By btrobaug Date 2006-10-20 Time 14:58 Sent To  
Notes
2006-10-20 15:21:33 
  
 NONCOMPLIANT
  
 THE LOAD CALCULATION AFTER DEMANDS, IS 240 AMPS. THE
 SERVICE CONDUCTORS ARE RATED AT 230 AMPS. NOTE THIS IS
 A QUADRAPLEX AND TABLE 310.15(B)(6) DOES NOT APPLY.
 PLEASE
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-19 Cont ID  
Sent By btrobaug Date 2006-09-19 Time 18:00 Rev Time 0.50
Received By btrobaug Date 2006-09-19 Time 17:41 Sent To PC
Notes
2006-09-19 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE SERVICE CONDUCTORS ARE NOT LARGE
 ENOUGH FOR THE CALCULATD LOAD. SEE TABLE
 310.16, 250 MCM IS REQUIRED FOR 240
 AMPS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-03 Cont ID  
Sent By btrobaug Date 2006-08-03 Time 13:40 Rev Time 1.00
Received By btrobaug Date 2006-08-03 Time 09:40 Sent To  
Notes
2006-08-03 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT A PANEL SCHEDULE FOR ALL
 UNITS, 106.3.5.4 FBC, AS AMMENDED.
  
 2} THERE ARE WASHERS AND DRYERS ON THE
 PLAN, NONE IN THE CALCS OR ON THE
 SCHEDULES.
  
 3} THERE ARE WATER HEATERS SHOWN OUTSIDE
 OF UNITS 1 AND 3, BESIDES THE ONES SHOWN
 INSIDE.
  
 4} IF THE WATER HEATERS AND
 WASHER/DRYERS ARE FOR COMMON USE OF ALL
 APARTMENTS, A HOUSE PANEL IS REQUIED.
  
 5} PROVIDE A RISER DIAGRAM PER 215.5.
  
 THE NEXT COMMENTS ARE FROM A PREVIOUS
 REVIEW. THE NUMBERS REFLECT THE COMMENT
 NUMBERS FROM THAT REVIEW.
  
 5} THE PANEL SCHEDULE INDICATES ONE
 SMALL APPLIANCE CIRCUIT AND THE CALC'S
 INDICATE THREE. SEE 210.11(C)(1).
  
 6} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN
 BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-09 Cont ID  
Sent By btrobaug Date 2006-06-09 Time 17:59 Rev Time 0.75
Received By btrobaug Date 2006-06-09 Time 17:02 Sent To  
Notes
2006-06-09 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1}THERE ARE FLOOR PLANS ON SHEET 3/5
 AND SHEET 5/5. REMOVE THE ONE NO TTO BE
 REVIEWED. PREFERABLE USE THE SCALE ON
 SHEET 3/5.
  
 2} THERE IS ONLY ONE FLOOR, TWO UNITS,
 ON THE PLAN. PROVIDE DRAWINGS FOR ALL
 UNITS AND INDICATE UNIT NUMBERS.
  
 3} THERE IS A SMOKE DETECTOR MISSING IN
 ONE UNIT, AND A KITCHEN GFI IN ANOTHER.
 UNITS HAVE NO DESIGNATIION, SEE REVIEWED
 PLAN FOR REDLINES.
  
 4} THERE IS A BATH GFI MISSING .
  
 5} THE PANEL SCHEDULE INDICATES ONE
 SMALL APPLIANCE CRCUIT AND THE CALC'S
 INDICATE THREE. SEE 210.11(C)(1).
  
 6} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN
 BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-11-07 Cont ID  
Sent By mawillia Date 2006-11-07 Time 11:31 Rev Time 0.00
Received By mawillia Date 2006-11-07 Time 11:31 Sent To  
Notes
2006-11-07 11:40:33*****APPROVED***** W/REMINDERS
  
  
  
 1.BUILDING ADDRESS ON THE ELEVATION SHEET STILL
 SHOWING 607 INSTEAD OF 609 AS INDICATED IN THE TITLE
 BLOCK OF THE PLANS.
  
 2.SINCE THIS BUILDING WILL BE ADDRESSED ON 11TH
 STREET, THE NUMERICAL ADDRESS MUST APPEAR ON THE SOUTH
 ELEVATION SO THAT IT IS VISIBLE FROM 11TH STREET.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722OFFICE
 561-644-7326CELL

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2006-09-21 Cont ID  
Sent By mawillia Date 2006-09-21 Time 11:43 Rev Time 0.00
Received By mawillia Date 2006-09-21 Time 11:43 Sent To  
Notes
2006-09-21 00:00:00*****UNSAT*****
  
  
  
  
 1.) PLEASE BE ADVISED THAT THE 11TH
 STREET ADDRESS DOES NOT REFLECT DIRECT
 ACCESS TO THE STRUCTURE. A HENRIETTA
 AVENUE ADDRESS WILL BE ASSIGNED FOR THE
 BUILDING SO THAT EMERGENCY RESPONSE WILL
 NOT BE DELAYED. THIS NEW ADDRESS SHOULD
 BE ON THE SUBMITTED SHOP DRAWINGS/PLANS
 AND PERMIT. AS PER WEST PALM BEACH CODE,
 THE NUMERICAL ADDRESS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND 1" IN WIDTH;
 INDIVIDUAL APARTMENTS, SUITES, OR UNIT
 NUMBERS SHALL BE NO LESS THAN 3" IN
 HEIGHT.
  
  
  
  
 ALL OTHER COMMENTS/CONCERNS OF PREVIOUS
 FIRE PLAN REVIEWS HAVE BEEN ADDRESSED
 AND/OR CORRECTED.
  
  
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722 (OFFICE)
 "644-7326 (CELL)

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-08-11 Cont ID  
Sent By mwennerg Date 2006-08-11 Time 11:13 Rev Time 0.00
Received By mwennerg Date 2006-08-11 Time 11:13 Sent To  
Notes
2006-08-11 00:00:00***DENIED***
  
 1) PLEASE NOTE THAT THE EXIT DOORS AT
 THE SECOND LEVEL APPEAR TO CONFLICT WITH
 THE STAIRWELL DOORS. THIS ARRANGEMENT
 INTERUPTS CONTINUOUS EVACUATION DURING
 AN EMERGENCY SITUATION. PLEASE SEE NFPA
 101, 2003 EDITION SEC. 7.2.1.4.4.
  
 2) PLEASE NOTE THAT COMMENTS FROM THE
 FIRST FIRE REVIEW HAVE NOT BEEN
 ADDRESSED. THE NOTES WILL BE INCLUDED
 WITH THIS REVIEW.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-06-19 Cont ID  
Sent By mcarsill Date 2006-06-19 Time 14:52 Rev Time 0.00
Received By mcarsill Date 2006-06-19 Time 14:49 Sent To  
Notes
2006-06-19 00:00:001. BUILDING SHALL HAVE ADDRESS ON PROPER
 ELEVATION. PLEASE CONTACT 804-4724 FOR
 PROPER SIZE OF ADDRESS NUMBERS.
  
 2. FLOOR PLAN IS MISSING A SMOKE
 DETECTOR FROM BEDROOM # 1 BUT IS SHOWN
 ON THE ELECTRICAL DRAWING. PLEASE REVISE
 PLANS.
  
 3. PLANS DO NOT INDICATE ANY EXISTING
 PORTABLE FIRE EXTINGUISHERS LOCATED ON
 THE EXTERIOR OR INTERIOR OF THE UNITS.
 PLEASE ADVISE.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-20 Cont ID  
Sent By adarroug Date 2006-10-20 Time 15:28 Rev Time 0.00
Received By adarroug Date 2006-10-20 Time 15:28 Sent To  
Notes
2006-10-27 13:48:37TO "BOB"#3
2006-10-20 15:29:52
 />
 

WAITING FOR "BOB"--NEEDS

 STYLE="FONT-WEIGHT:600">B,F,AND P

 STYLE="FONT-WEIGHT:600">PER
 "BTROBAUG"

 

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 13:47 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 13:47 Sent To  
Notes
2006-09-08 00:00:00WAITING FOR "BOB"
 TO "BOB"#9

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-22 Cont ID  
Sent By adarroug Date 2006-07-22 Time 14:33 Rev Time 0.00
Received By adarroug Date 2006-07-22 Time 14:33 Sent To  
Notes
2006-08-02 00:00:00ON "BOB" # 7
2006-07-22 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-01 Cont ID  
Sent By adarroug Date 2006-06-01 Time 14:19 Rev Time 0.00
Received By adarroug Date 2006-06-01 Time 14:19 Sent To  
Notes
2006-06-01 00:00:00TO "BOB"#16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-01 Cont ID  
Sent By adarroug Date 2006-06-01 Time 14:03 Rev Time 0.00
Received By adarroug Date 2006-06-01 Time 14:03 Sent To B
Notes
2006-06-01 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-28 Cont ID  
Sent By shill Date 2006-03-19 Time 14:16 Rev Time 0.00
Received By shill Date 2006-02-25 Time 12:34 Sent To  
Notes
2006-02-25 00:00:00TO "MISC" BOX#1

Review Stop P PLUMBING
Rev No 4 Status N Date 2006-11-09 Cont ID  
Sent By kstevens Date 2006-11-09 Time 10:57 Rev Time 0.00
Received By kstevens Date 2006-11-09 Time 10:57 Sent To  
Notes
2006-11-09 11:04:37REVISION SUBMITTED WAS A COPY OF THE
 APPROVED PLUMBING ISOMETRIC. NO REVIEW
 NECESSARY, NO CHANGES NOTED.

Review Stop P PLUMBING
Rev No 3 Status N Date 2006-10-03 Cont ID  
Sent By kstevens Date 2006-10-03 Time 07:33 Rev Time 0.00
Received By kstevens Date 2006-10-03 Time 07:33 Sent To  
Notes
2006-10-03 00:00:00REVISION SUBMITTED WAS A COPY OF THE
 APPROVED PLUMBING ISOMETRIC. NO REVIEW
 NECESSARY, NO CHANGES NOTED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-08-05 Cont ID  
Sent By pschmitz Date 2006-08-05 Time 11:57 Rev Time 0.00
Received By pschmitz Date 2006-08-05 Time 11:57 Sent To  
Notes
2006-08-05 00:00:00RE-SUB PER PREVIOUS NOTES

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-13 Cont ID  
Sent By jleech Date 2006-06-13 Time 08:15 Rev Time 0.00
Received By jleech Date 2006-06-13 Time 08:15 Sent To  
Notes
2006-06-13 00:00:00DENIED;
 1.A BACKFLOW PREVENTOR IS REQUIRED ON
 THE WATER SERVICE IF THE UNITS ARE NOT
 INDIVIDUALLY METERED. PLEASE INDICATE ON
 PLANS.
 2.LIST FIREW STOP MATERIAL TO BE USED,
 AND LIST THE UL LISTINGS.
 3.THERMAL EXPANTION PROTECTION IS
 REQUIRED ON WATER HEATER IF A BACKFLOW
 PREVENTOR IS INSTALLED PER SEC.607.3.
 4.ADD NOTE "ALL NEW PIPING SHALL BE
 TESTED PER FBC-2004 PLUMBING SEC.312.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695