2006-03-14 00:00:00 | DENIED |
| REFERENCE: FBC-2004 R4101 SWIMMING POOLS |
| |
| PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| SUBMITTALS TO REFLECT THE FOLLOWING |
| INFORMATION REQUIRED FOR PLAN REVIEW: |
| |
| 1) COMPLY WITH FBC-2004 SEC. R4101 PRI- |
| VATE SWIMMING POOLS. (ADD TO NOTES) |
| 2) PAGE 3 OF 4 STATES "MAXIMUM |
| UNDERWATER LENGTH OF VENT PIPING 30 |
| FEET, PAGE 1 OF 4 VENT PIPE APPEARS TO |
| BE LONGER THAN 30 FEET. PLEASE SUPPLY |
| ENGINEERED TABLE FOR "VENT PIPE MAXIMUM |
| LENGTH" INDICATING PUMP SIZE, AVERAGE |
| FLOW (GPM), AND MAXIMUM LENGTH OF 1-1/2" |
| PVC VENT PIPE, FROM WHERE IT STARTS TO |
| WHERE IT TERMINATES. COMPLY WITH 3 SE- |
| COND RELEASE. |
| 3) FBC-2004R4101.6.6.5 WHERE PROVIDED, |
| THE VACUUM OR PRESSURE CLEANER FITTING |
| SHALL BE LOCATED AT LEAST 6" AND NOT |
| GREATER THAN 12" BELOW THE MINIMUM OPER- |
| ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| THE SKIMMER.(ADD TO NOTES, AND DETAILS |
| REQUIRED) |
| 4) FBC-2004 R4101.9 WATER SUPPLY, LOCAL |
| ORD. #2853, BACKFLOW REQUIRED ON WATER |
| SERVICE. (ADD TO NOTES) |
| 5) FBC-2004 R4101.14.1 SWIMMING POOL |
| WATER HEATERS SHALL BEAR THE LABEL OF A |
| RECOGNIZED TESTING AGENCY. MANUFACTURE |
| SHEETS REQUIRED. (SUBMITTAL REQUIRED) |
| 6) FBC-2004 R4101.14.2 WATER RETENTION, |
| PROVIDE A POSITIVE MEANS OF RETAINING |
| WATER IN THE HEATER WHEN PUMP IS SHUT |
| OFF.(MANUFACTURE CUT SHEETS SUBMITTAL |
| REQUIRED) |
| 7) FBC-2004 R4101.15 GAS PIPING SHALL |
| COMPLY WITH FBC-2004 FUEL GAS. SEPERATE |
| PLANS AND PERMIT REQUIRED.(ADD TO NOTES) |
| |
| END OF COMMENTS: |
| |