Plan Review Details - Permit 06020978
Plan Review Stops For Permit 06020978
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-04-11 Cont ID  
Sent By amorse Date 2006-04-11 Time 07:16 Rev Time 0.50
Received By amorse Date 2006-04-11 Time 07:16 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-24 Cont ID  
Sent By amorse Date 2006-03-24 Time 07:14 Rev Time 0.50
Received By amorse Date 2006-03-24 Time 07:14 Sent To PC
Notes
2006-03-24 00:00:00 
  
 DENIED
  
 1) THE CLAIMED VALUATION ON THE POOL
 PERMIT APPLICATION IS LOW. FOR
 PERMITTING PURPOSES, OUR VALUATION
 REFERENCE ISMARSHALL-SWIFT AND MEANS
 COST ANALYSIS SERVICES PER 108.3 FBC*
 THE PERMIT VALUE WILL BE ADJUSTED TO
 REFLECT THIS AND FEES WILL BE DUE
  
 2) THE NOTES ON THE DRAWING THAT PERTAIN
 TO SAFETY REQUIREMENTS OF R4101.17 ARE
 JUST THAT AND AS SUCH SHALL BE IN PLACE
 AT POOL FINAL INSPECTION PER 4101.19 FBC
 THESE NOTES ARE A STATEMENT AND ARE
 REQUIRED REGUARDLESS OF SIGNATURES
 REMOVE SIGNATURE LINES AND REFERENCES TO
 ACTCEPTANCE BY OWNERS OR ADD THE
 REQUIREMENTS TO GENERAL NOTES
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-04-10 Cont ID  
Sent By btrobaug Date 2006-04-10 Time 13:52 Rev Time 0.33
Received By btrobaug Date 2006-04-10 Time 13:52 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-03-10 Cont ID  
Sent By btrobaug Date 2006-03-10 Time 17:55 Rev Time 0.33
Received By btrobaug Date 2006-03-10 Time 17:52 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2006-04-10 Cont ID  
Sent By mperson Date 2006-04-10 Time 14:55 Rev Time 0.00
Received By mperson Date 2006-04-10 Time 14:55 Sent To B
Notes
2006-04-10 00:00:00NOTE: GAS PERMIT REQUIRED. GAS
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT
 APPLICATION. ALL GAS INSPECTIONS TO BE
 COMPLETE BEFORE FINAL POOL INSPECTION

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-03-14 Cont ID  
Sent By mperson Date 2006-03-14 Time 16:41 Rev Time 0.00
Received By mperson Date 2006-03-14 Time 16:41 Sent To  
Notes
2006-03-14 00:00:00NOTE: SEPERATE PLANS AND PERMIT REQUIRED

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-03 Cont ID  
Sent By adarroug Date 2006-04-03 Time 13:26 Rev Time 0.00
Received By adarroug Date 2006-04-03 Time 13:26 Sent To E
Notes
2006-04-03 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 11:29 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 11:29 Sent To E
Notes
2006-03-09 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-24 Cont ID  
Sent By amorse Date 2006-03-24 Time 07:15 Rev Time 0.00
Received By amorse Date 2006-02-24 Time 09:58 Sent To  
Notes
2006-02-24 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-04-10 Cont ID  
Sent By mperson Date 2006-04-10 Time 14:51 Rev Time 0.33
Received By mperson Date 2006-04-10 Time 14:51 Sent To B
Notes
2006-04-10 00:00:00 
  
 ******PROVISO******
 FBC-2004 424.2.15, GAS PIPING SHALL
 COMPLY WITH FBC-2004 FUEL GAS. SEPERATE
 PLANS AND PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-14 Cont ID  
Sent By mperson Date 2006-03-14 Time 15:47 Rev Time 0.33
Received By mperson Date 2006-03-14 Time 15:47 Sent To B
Notes
2006-03-14 00:00:00DENIED
 REFERENCE: FBC-2004 R4101 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW:
  
 1) COMPLY WITH FBC-2004 SEC. R4101 PRI-
 VATE SWIMMING POOLS. (ADD TO NOTES)
 2) PAGE 3 OF 4 STATES "MAXIMUM
 UNDERWATER LENGTH OF VENT PIPING 30
 FEET, PAGE 1 OF 4 VENT PIPE APPEARS TO
 BE LONGER THAN 30 FEET. PLEASE SUPPLY
 ENGINEERED TABLE FOR "VENT PIPE MAXIMUM
 LENGTH" INDICATING PUMP SIZE, AVERAGE
 FLOW (GPM), AND MAXIMUM LENGTH OF 1-1/2"
 PVC VENT PIPE, FROM WHERE IT STARTS TO
 WHERE IT TERMINATES. COMPLY WITH 3 SE-
 COND RELEASE.
 3) FBC-2004R4101.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.(ADD TO NOTES, AND DETAILS
 REQUIRED)
 4) FBC-2004 R4101.9 WATER SUPPLY, LOCAL
 ORD. #2853, BACKFLOW REQUIRED ON WATER
 SERVICE. (ADD TO NOTES)
 5) FBC-2004 R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL REQUIRED)
 6) FBC-2004 R4101.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF.(MANUFACTURE CUT SHEETS SUBMITTAL
 REQUIRED)
 7) FBC-2004 R4101.15 GAS PIPING SHALL
 COMPLY WITH FBC-2004 FUEL GAS. SEPERATE
 PLANS AND PERMIT REQUIRED.(ADD TO NOTES)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721
  

Review Stop Z ZONING
Rev No 1 Status P Date 2006-03-08 Cont ID  
Sent By mmclean Date 2006-03-08 Time 17:10 Rev Time 0.00
Received By mmclean Date 2006-03-08 Time 17:10 Sent To I
Notes
2006-03-08 00:00:00NOTE: POOL EQUIPMENT CAN ONLY ENCROACH
 4FT INTO SETBACK.