Plan Review Details - Permit 06020959
Plan Review Stops For Permit 06020959
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-03-07 Cont ID  
Sent By shill Date 2006-03-07 Time 09:30 Rev Time 0.00
Received By shill Date 2006-03-07 Time 09:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-24 Cont ID  
Sent By shill Date 2006-02-24 Time 08:04 Rev Time 0.00
Received By shill Date 2006-02-24 Time 08:04 Sent To  
Notes
2006-02-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
  
 _XX_1.)A NOTICE OF COMMENCEMENT
 MUST BE FILED WITH THE CLERK OF COURTS
 BEFORE A PERMIT CAN BE ISSUED.THE NOC
 PROVIDED IS EXPIRED; OVER 90 DAYS
 WITHOUT COMMENCING WORK, FS713.13(2).
  
 ____2.)CONTRACTOR IS TO PROVIDE THE
 MEAN ROOF HEIGHT ON THE APPLICATION.
  
 ____3.)CONTRACTOR IS TO PROVIDE THE
 ROOF PITCH ON THE APPLICATION.
  
 ____4.)CONTRACTOR IS TO PROVIDE THE
 ROOF DECK TYPE ON THE APPLICATION.
  
 ____5.)FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED IN ADDITION TO
 THE EVALUATION REPORT SUBMITTED,
 FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX_6.)FOR THE FLAT DECK, SELECT THE
 APPROVED ASSEMBLY YOU ARE USING.
  
 ____7.)THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ____.
  
 ____8.)THE SYSTEM PROVIDED STATES
 LIMITATION #9, ENHANCED FASTENING NOT
 ALLOWED.
  
 ____9.)PROVIDE AN ENGINEER?S LETTER
 TO CONFIRM THAT THE ROOF WHICH CURRENTLY
 HAS SHINGLES INSTALLED CAN ACCOMMODATE
 THE ADDITIONAL WEIGHT OF THE PROPOSED
 TILE.
  
  
  