Plan Review Stops For Permit 06020819 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2006-03-17 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-03-16 |
Time |
18:08 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2006-03-17 |
Time |
10:17 |
Sent To |
|
|
Notes |
2006-03-17 00:00:00 | PERMIT APPLIED TO EXT#0001 FOR 1004 13TH | | ST A 20 UNIT APARTMENT BUILDING. | 2006-02-17 00:00:00 | EXT REQUIRED FOR 1004 13TH ST |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2006-03-22 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-03-22 |
Time |
11:59 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-03-22 |
Time |
11:59 |
Sent To |
PC |
|
Notes |
2006-03-22 00:00:00 | NON COBUUSTIBLE ACCORDING DOOR INSTALLED | | TO SEPERATE WATER HEATER FROM CLOSET. | | PES |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2006-03-16 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-03-16 |
Time |
18:09 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-03-16 |
Time |
18:07 |
Sent To |
|
|
Notes |
2006-03-17 00:00:00 | PAUL SCHMITZ | | [email protected] | | FBC 2004 PLUMBING CODE PLAN REVIEW | | FBC2004 FUEL GAS CODEPLAN REVIEW | | FBC 2004 BUILDING CODE PLAN REVIEW | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | 1) PRODUCT APPROVALS DENIED, SEE | | ENCLOSED MEMO, RE: MULTI UNIT RESIDENTAL | | STRUCTURES. | | | | 1609.1.4 PROTECTION OF OPENINGS. | | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR | | GLAZING THAT RECEIVES POSITIVE PRESSURE | | IN THE LOWER 60 FEET (18.3 M) IN | | BUILDINGS SHALL BE ASSUMED TO BE | | OPENINGS AND THE BALANCE OF GLAZED | | OPENINGS IN THE REST OF THE BUILDING | | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH | | GLAZING THAT RECEIVES POSITIVE PRESSURE | | IS IMPACT RESISTANT OR PROTECTED WITH AN | | IMPACT RESISTANT COVERING MEETING THE | | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND | | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 | | AND 203 REFERENCED THEREIN AS FOLLOWS: | | 1. GLAZED OPENINGS LOCATED WITHIN 30 | | FEET (9.1 M) OF GRADE SHALL MEET THE | | REQUIREMENTS OF THE LARGE MISSILE TEST. | | 2. GLAZED OPENINGS LOCATED MORE THAN 30 | | FEET (9.1 M) ABOVE GRADE SHALL MEET THE | | PROVISIONS OF THE SMALL MISSILE TEST. | | 3. STORAGE SHEDS THAT ARE NOT DESIGNED | | FOR HUMAN HABITATION AND THAT HAVE A | | FLOOR AREA OF 720 SQUARE FEET (67 M2) OR | | LESS ARE NOT REQUIRED TO COMPLY WITH THE | | MANDATORY WINDBORNE DEBRIS IMPACT | | STANDARDS OF THIS CODE. | | 4. OPENINGS IN SUNROOMS, BALCONIES OR | | ENCLOSED PORCHES CONSTRUCTED UNDER | | EXISTING ROOFS OR DECKS ARE NOT REQUIRED | | TO BE PROTECTED PROVIDED THE SPACES ARE | | SEPARATED FROM THE BUILDING INTERIOR BY | | A WALL AND ALL OPENINGS IN THE | | SEPARATING WALL ARE PROTECTED IN | | ACCORDANCE WITH SECTION 1609.1.4 ABOVE. | | SUCH SPACES SHALL BE PERMITTED TO BE | | DESIGNED AS EITHER PARTIALLY ENCLOSED OR | | ENCLOSED STRUCTURES. | | | | END OF COMMENTS, QUESTIONS 561-805-6692 | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-03-11 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-03-11 |
Time |
07:44 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-03-11 |
Time |
07:38 |
Sent To |
|
|
Notes |
2006-03-11 00:00:00 | PAUL SCHMITZ | | [email protected] | | FBC 2004 PLUMBING CODE PLAN REVIEW | | FBC2004 FUEL GAS CODEPLAN REVIEW | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | DENIED | | 1) PREVIOUS NOTES DATED 2-23-06 LETTER | | FROM ENGINEER, ON CRACKED PRIMETER BEAM. | | A) REQUIRE TWO ORIGINAL SIGNED AND | | SEALED LETTERS, NO COPIES OF SEAL. | | B) THE LETTER FROM THE ENGINEER | | ADDRESSING THE FIRST FLOOR APARTMENT | | FRONT DOOR. | | "IS NOT THE BEAM IN QUESTION" | | THE PICTURES ATTACHED, SHOW THE SECOND | | FLOOR, NORTH EAST APARTMENT WINDOW, WITH | | THE BEAM CRACKED AND THE MASONARY BLOCK | | BLOWN OUT. | | 2) PRODUCT APPROVALS FOR WINDOWS AND | | DOORS DENIED. | | PROVIDE STATE PRODUCT APPROVALS. | | DETAIL SPECIFICS TO THIS APPLICATION. | | INCLUDE INSTALLATION INSTRUCTIONS. | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-02-23 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-02-23 |
Time |
10:24 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-02-23 |
Time |
10:18 |
Sent To |
|
|
Notes |
2006-02-23 00:00:00 | PLUMBING PLAN REVIEW EXAMINER | | PAUL SCHMITZ 561-805-6692 | | [email protected] | | FBC PLUMBING 2004 | | FBC FUEL GAS 2004 | | DENIED | | CALLED STEWART LEDIS RE: | | 1)ENGINEER OF RECORD TO INSPECT CRACKED | | PRIMETER BEAM. | | 2)PROVIDE A SIGNED A SEALED LETTER ON | | HOW TO REPAIR CRACKED BEAM. | | 3)SEC R310.1.1 MINIMUM OPENING AREA. | | ALL EMERGENCY ESCAPE AND RESCUE OPENINGS | | SHALL HAVE A MINIMUM NET CLEAR OPENING | | OF 5.7 SQUARE FEET. | | 4)PRODUCT APPROVAL ON ALL WINDOWS | | REPLACED,DUE TO EXPLOSION OR HURRICANE | | DAMAGE. | | END OF COMMENTS QUESTIONS 561-805-6692 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
N |
Date |
2006-02-21 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2006-02-21 |
Time |
09:23 |
Rev Time |
0.30 |
Received By |
jleahy |
Date |
2006-02-21 |
Time |
09:21 |
Sent To |
|
|
Notes |
2006-02-21 00:00:00 | NO ELECTRIC SHOWN OR ELECTRICAL | | CONTRACTOR. | | | | HAVE CONTRACTOR BRING IN PLANS WHEN | | APPYING FOR PERMIT, SHOW ALL WORK | | NEW EXISTING ECT.ECT. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2006-02-23 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2006-02-23 |
Time |
15:40 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2006-02-23 |
Time |
15:30 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2006-03-16 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-03-16 |
Time |
10:48 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-03-16 |
Time |
10:46 |
Sent To |
|
|
Notes |
2006-03-16 00:00:00 | PAUL SCHMITZ | | [email protected] | | FBC 2004 PLUMBING CODE PLAN REVIEW | | FBC2004 FUEL GAS CODEPLAN REVIEW | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | DENIED | | | | 1) GAS WATER HEATERS LOCATED IN CLOSETS | | IN EACH UNIT NOT APROVED. | | SECTION 303 APPLIANCE LOCATION | | 303.1 GENERAL. | | APPLIANCES SHALL BE LOCATED AS REQUIRED | | BY THIS SECTION, SPECIFIC REQUIREMENTS | | ELSEWHERE IN THIS CODE AND THE | | CONDITIONS OF THE EQUIPMENT AND | | APPLIANCE LISTING. | | 303.2 HAZARDOUS LOCATIONS. | | APPLIANCES SHALL NOT BE LOCATED IN A | | HAZARDOUS LOCATION UNLESS LISTED AND | | APPROVED FOR THE SPECIFIC INSTALLATION. | | 303.3 PROHIBITED LOCATIONS. | | APPLIANCES SHALL NOT BE LOCATED IN, OR | | OBTAIN COMBUSTION AIR FROM, ANY OF THE | | FOLLOWING ROOMS OR SPACES: | | 1. SLEEPING ROOMS. | | 2. BATHROOMS. | | 3. TOILET ROOMS. | | 4. STORAGE CLOSETS. | | 5. SURGICAL ROOMS. | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
P |
Date |
2006-02-17 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-02-17 |
Time |
14:09 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-02-17 |
Time |
14:08 |
Sent To |
E |
|
Notes |
2006-02-17 00:00:00 | PLUMBING PLAN REVIEW EXAMINER | | PAUL SCHMITZ 561-805-6692 | | [email protected] | | FBC PLUMBING 2004 | | FBC FUEL GAS 2004 | | 1)SEE GAS PERMIT # 06020834 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-03-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-03-10 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-03-10 |
Time |
11:49 |
Sent To |
|
|
Notes |
2006-03-10 00:00:00 | TO "PSCHMITZ" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-02-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-02-17 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-02-17 |
Time |
14:14 |
Sent To |
G |
|
Notes |
2006-02-24 00:00:00 | TO "PSCHMITZ" DESK |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2006-02-17 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-02-17 |
Time |
15:04 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-02-17 |
Time |
15:04 |
Sent To |
P |
|
Notes |
2006-02-17 00:00:00 | NO MECHANICAL PLANS OR CONTRACTOR | | INDICATED WITH PERMIT APPLICATION. | | PLEASE PROVIDE PLANS, EQUIPMENT SCHEDULE | | & ENERGY CALCULATIONS WITH MECHANICAL | | PERMIT APPLICATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2006-03-16 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-03-16 |
Time |
11:50 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-03-16 |
Time |
11:50 |
Sent To |
B |
|
Notes |
2006-03-16 00:00:00 | | | PAUL SCHMITZ | | [email protected] | | FBC 2004 PLUMBING CODE PLAN REVIEW | | FBC2004 FUEL GAS CODEPLAN REVIEW | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | PROVISO | | SEPERATE PERMIT FOR PLUMBING. | | IF ANY CHANGES TO PLUMBING LAYOUT, PLANS | | WITH NEW LAYOUT AND ISOMETRIC REQUIRED | | WITH PERMIT APPLICATION. | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2006-02-24 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-02-24 |
Time |
07:44 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-02-17 |
Time |
13:17 |
Sent To |
|
|
Notes |
2006-02-17 00:00:00 | PLUMBING PLAN REVIEW EXAMINER | | PAUL SCHMITZ 561-805-6692 | | [email protected] | | FBC PLUMBING 2004 | | FBC FUEL GAS 2004 | | FBC BUILDING 2004, CH 11 | | 1) ALL WORK PER CITY CODES, SUBJECT TO | | FIELD INSPECTOR. | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|