Plan Review Details - Permit 06020814
Plan Review Stops For Permit 06020814
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2006-06-30 Cont ID  
Sent By lursu Date 2006-06-30 Time 08:29 Rev Time 0.00
Received By lursu Date 2006-06-30 Time 08:29 Sent To  
Notes
2006-06-30 00:00:00BASED ON THE UNITY OF TITLE DONE BY THE
 FIRST EVANGELICAL LUTHERAN CHURCH INC (
 RECORDED ON 07/15/05 ,BK 18914,PG
 0803)AND THE SURVEY SUBMITTED FOR THE
 SITE DATED 06/07/05 RECEIVED BY THE CITY
 ON 06/29/06 A NEW ADDRESS HAS BEEN
 ISSUED TO THE NEW BANK AS 850 BELVEDERE
 RD ( EXT #0001 UNDER THE MAIN ADDRESS OF
 2740 PARKER AVE ,PCN =
 74434333130020010)

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2006-05-23 Cont ID  
Sent By lursu Date 2006-05-23 Time 15:29 Rev Time 0.00
Received By lursu Date 2006-05-15 Time 16:18 Sent To  
Notes
2006-05-23 00:00:00PLAT AND THE REVISED SITE PLAN IS
 NECESSARY .
2006-05-15 00:00:00THE UNITY OF TITLE (RECORDED ON
 07/15/05)WAS RECEIVED BY ME ON 05/12/06
 FOR THE FOLLOWING PARCELS:
 74 43 43 33 12 000 0060
 74 43 43 33 07 000 0027
 74 43 43 33 12 000 0010.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-02-23 Cont ID  
Sent By lursu Date 2006-02-23 Time 08:40 Rev Time 0.00
Received By lursu Date 2006-02-23 Time 08:41 Sent To  
Notes
2006-02-23 00:00:00UNITY OF TITLE AND THE PROPOSED PLAT IS
 REQUIRED IN ORDER TO PROCESS A (NEW)
 ADDRESS.CP HAS A RECORD FOR THE EXISTING
 BUILDING AS 846 BELVEDERE( PAPA HAS
 836).WILL THIS BLDG BE DEMOLISHED? IS SO
 THE ADDRESS WILL REMAIN AS 846 IF NOT A
 NEW ADDRESS IS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-07-31 Cont ID  
Sent By shill Date 2007-07-31 Time 07:18 Rev Time 0.00
Received By shill Date 2007-07-31 Time 07:18 Sent To  
Notes
2007-07-31 07:19:03REVISION - LETTER REDUCING DESIGN PRESSURE FOR THE
 BULLET PROOF WINDOW
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-06-26 Cont ID  
Sent By shill Date 2007-06-26 Time 14:32 Rev Time 0.00
Received By shill Date 2007-06-26 Time 14:32 Sent To  
Notes
2007-06-26 14:34:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72.COMPLETE THE APPLICATION WITH ALL REQUIRED
 INFORMATION.ORIGINAL ENGINEERING AND APPLICATION
 REQUIRED.
  
 2.)IMPACT PROTECTION REQUIRED FBC1609.1.4.
  
 3.)SUBMIT AS SEPARATE PERMIT AS PER PROVISO.REFER
 TO THIS PERMIT AS THE MASTER PERMIT.
  
 4.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-11-06 Cont ID  
Sent By shill Date 2006-11-06 Time 16:40 Rev Time 0.00
Received By shill Date 2006-11-06 Time 16:40 Sent To  
Notes
2006-11-06 16:40:45***PROVISO***SEP PERMIT FOR BULLET PROOF GLASS
  
 SUBMIT LIGHT POLE AND LIGHT FIXTURE CALCS & SHOPS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-10-18 Cont ID  
Sent By shill Date 2006-10-18 Time 10:27 Rev Time 0.00
Received By shill Date 2006-10-18 Time 09:10 Sent To  
Notes
2006-10-18 10:34:30****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)FROM PREVIOUS REVIEWS, FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED FOR THE BULLET PROOF GLASS.
 THE MIAMI-DADE NOA IS NO LONGER A PART OF THE PACKAGE.
 IT IS UNCLEAR HOW THE ENGINEER HAS DETERMINED A DESIGN
 PRESSURE OF -71 AFTER REMOVING THE STRESS INCREASE FOR
 STEEL (STARTING AT A DP OF -94) WHEN THE DP ON THE NOA
 IS +-50.ALL ADDITIONAL ENGINEERING SUBMITTED IS TO BE
 SIGNED, SEALED DATED ORIGINALS (PHOTOCOPIES PROVIDED).
 A SECTION OF THE FBC2001 WAS PROVIDED; YOU MUST SHOW
 CODE COMPLIANCE WITH FBC2004.THE ENGINEER'S TITLE
 BLOCK IS TO COMPLY WITH ALL REQUIREMENTS OF
 FAC61G15-23.002.
  
 3.)THE ALUMINUM LIGHTING POLES SPECIFY ASCE7-98 AND
 "FLORIDA BUILDING CODE".DECLARE GOVERNING CODE
 (FBC2004) AND SEE FBC35, INCORRECT ASCE VERSION
 (ASCE7-02).
  
 4.)WHEN RESUBMITTING, HAVE THE DUMPSTER ENCLOSURE
 PERMIT APPLICATION PROCESSED AT THE FRONT DESK.THE
 CONTRACTOR'S SIGNATURE MUST BE EITHER NOTARIZED OR
 VERIFIED IN PERSON.PLEASE CONTACT ME IF YOU NEED
 FURTHER ASSISTANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-12 Cont ID  
Sent By shill Date 2006-07-12 Time 16:42 Rev Time 0.00
Received By shill Date 2006-07-12 Time 16:42 Sent To  
Notes
2006-07-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS REVIEW:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025 FOR MORE
 INFORMATION.
  
 3.)PROVIDE A COPY OF THE RECORDED
 UNITY OF TITLE.
  
 4.)ADDRESSED.
  
 5.)PRODUCT APPROVALS ARE TO BE
 SUBMITTED BY DESIGNER OF RECORD,
 FBC*106.3.3.(EITHER A SHOP DRAWING
 STAMP OR LETTER.)
  
 THE BULLET RESISTANT WINDOW HAS A DESIGN
 PRESSURE LIMITATION OF +-50; S7
 SPECIFIES +66.2/-70.7.
  
 CIRCLE ANCHORING METHOD FOR THE IMPACT
 STOREFRONT AS NOT ALL OF THEM ARE
 COMPLIANT FOR DESIGN PRESSURES SPECIFIED
 ON SHEET S7.
  
 THE ENGINEERING FOR THE ARCH ALUMINUM
 PREPARED BY BROMLEY COOK ENGINEERING IS
 TO BE SIGNED, SEALED, AND DATED.A
 CERTIFICATE OF AUTHORIZATION IS REQUIRED
 FOR BROMLEY-COOK AND THE NUMBER IS TO BE
 PRINTED ON EACH SEALED SHEET,
 FAC61G15-23.002.
  
 6.)ADDRESSED.
  
 7.)COMPLETE A PERMIT APPLICATION FOR
 THE DUMPSTER ENCLOSURE AND PROVIDE WITH
 THE RESUBMITTAL.SEPARATE PLANS ARE NOT
 NECESSARY.
  
 8.)ADDRESSED.
  
 9.)THE PARKING STRIPING IS TO COMPLY
 WITH THE CITY OF WEST PALM BEACH
 STANDARD, SEE ATTACHED DETAIL.
  
 PLEASE REVISE THE DETAIL IN THIS PLAN,
 AND ALSO REVISE THE ISSUED ENGINEERING
 PERMIT TO AVOID CONFUSION IN THE FIELD.
  
 10.-19.)ADDRESSED.
  
 NEW COMMENTS:
  
 20.)THE SURVEY SHOWS THE NEW PROPERTY
 LINE GOING THROUGH THE MIDDLE OF AN
 EXISTING BUILDING.THIS CREATES A
 BUILDING WHICH IS NOT CODE COMPLIANT,
 FBC TABLE 601.PLEASE ADDRESS OR
 CONTACT ME TO DISCUSS.
  
 21.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED IN ADDITION TO THE
 NOAS PROVIDED, FAC9B72.IF A STATE
 PRODUCT APPROVAL IS NOT AVAILABLE,
 PLEASE ADVISE AND A LOCAL PRODUCT
 APPROVAL WILL BE ISSUED.
 WWW.FLORIDABUILDING.ORG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-05 Cont ID  
Sent By shill Date 2006-05-05 Time 17:59 Rev Time 0.00
Received By shill Date 2006-05-05 Time 11:05 Sent To  
Notes
2006-05-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025 FOR MORE
 INFORMATION.
  
 3.)PROVIDE A SURVEY FOR THIS PROPERTY,
 FBC*106.3.4.IF THE IMPROVEMENT CROSSES
 A PROPERTY LINE, A UNITY OF TITLE WILL
 BE REQUIRED.THE RECORDED UNITY OF
 TITLE MUST BE PROVIDED PRIOR TO PERMIT
 ISSUANCE.
  
 4.)THE CONTRACTOR'S INSURANCE IS
 EXPIRED.PLEASE PROVIDE A CURRENT
 INSURANCE CERTIFICATE PRIOR TO PERMIT
 ISSUANCE.
  
 5.)PROVIDE PRODUCT APPROVALS FOR THE
 COMPONENTS AND CLADDING.PRODUCT
 APPROVALS ARE TO BE REVIEWED BY THE
 DESIGNER OF RECORD, FBC*106.3.3.
 PROVIDE FOR ALL COMPONENTS AND CLADDING,
 INCLUDING
  
 IMPACT STOREFRONT
 HOLLOW METAL DOORS
 BULLET RESISTANT VISION WINDOW
 TILE ROOF, CIRCLE METHOD OF ATTACHMENT
 ON THE PRODUCT APPROVAL
  
 6.)THE PLANS SHOW IMPACT GLASS.IF
 THIS IS CHANGED ON THE PLAN TO NON
 IMPACT WITH REMOVABLE SHUTTERS, BE
 ADVISED THAT USE OF REMOVABLE SHUTTERS
 ON COMMERCIAL BUILDINGS MUST BE APPROVED
 BY THE BUILDING OFFICIAL.IF THERE IS A
 CHANGE TO THE PLANS IN REGARDS TO IMPACT
 PROTECTION, FAILURE TO SUBMIT A
 HURRICANE SHUTTER INSTALLATION PLAN WILL
 CAUSE DELAYS IN PERMIT ISSUANCE.THIS
 ITEM IS INFORMATIONAL ONLY.
  
 7.)INFORMATIONAL ONLY; SEPARATE
 PERMITS WILL BE REQUIRED FOR THE SCREEN
 WALL AND THE DUMPSTER ENCLOSURE.
 COMPLETE A PERMIT APPLICATION FOR THE
 DUMPSTER ENCLOSURE AND PROVIDE WITH THE
 RESUBMITTAL.SEPARATE PLANS ARE NOT
 NECESSARY.
  
 8.)THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR SOUTHERN DESIGN GROUP INC. IS
 REQUIRED TO BE ON EACH SHEET,
 FAC61G15-23.002.
  
 9.)THE PARKING STRIPING IS TO COMPLY
 WITH THE CITY OF WEST PALM BEACH
 STANDARD, SEE ATTACHED DETAIL.
  
 10.)DECLARE THE MEAN ROOF HEIGHT SO
 THAT MOMENTS OF RESISTANCE FOR THE ROOF
 TILE CAN BE DETERMINED.
  
 11.)PROVIDE THE DISTANCE BETWEEN THE
 PROPOSED BANK AND THE EXISTING BUILDING,
 FBC TABLE 602.IF THEY ARE ON THE SAME
 LOT, SHOW THE ASSUMED PROPERTY LINE AND
 COMPLIANCE WITH TABLE 602.
  
 12.)THE PROPERTY LINE IS NOT CLEAR ON
 THE SITE PLAN.IF THE SCREEN WALL 7-SP4
 IS ALONG A PROPERTY LINE, SHOW THE
 PROPERTY LINE ON THE DETAIL.THE FOOTER
 CANNOT ENCROACH THE PROPERTY LINE.SEE
 SP1.SOME OF THE TEXT IS UPSIDE DOWN OR
 IN THE WRONG LOCATIONS.THERE IS A LINE
 SHOWING ?PROPOSED LEASE LINE? WHICH
 SEEMS TO INDICATE ONLY ONE PARCEL.A
 BOUNDARY SURVEY SHOULD HELP TO CLARIFY
 LOT LINES.
  
 13.)A1 STATES THAT THERE IS A 75' MAX
 TRAVEL DISTANCE.DO YOU MEAN COMMON
 PATH OF TRAVEL FBC1013.3?THE TRAVEL
 DISTANCE EXCEEDS 75'.IF YOUR DESIGN
 INTENTION IS TO EXCEED CODE AND RESTRICT
 MAXIMUM TRAVEL DISTANCE TO 75' PLEASE
 REVISE THE PLANS.OTHERWISE REVISE THE
 75' MAX TRAVEL DISTANCE REQUIREMENT
 FBC1015.1.NOTE THAT ONLY ONE EXIT IS
 REQUIRED FBC1014.1 SO THERE IS NO
 REQUIREMENT FOR COMMON PATH OF TRAVEL.
 IT IS ACCEPTABLE TO EXCEED CODE BUT THE
 PLANS SHOULD BE CONSISTENT WITH YOUR
 DESIGN SPECIFICATION.
  
 14.)SHOW THE MANEUVERING CLEARANCE,
 PULL SIDE, FOR DOORS 104, 108, 112,
 FIGURE FBC 11-25, FBC11-4.13.6.
  
 15.)BREAK ROOM SINK IS TO COMPLY WITH
 FBC11-4.24.SHOW ALL DIMENSIONS,
 INCLUDING KNEE CLEARANCE.
  
 16.)THE TELLER COUNTER IS SHOWN AS
 40IN.SEE FBC11-7.2(2) AND SHOW
 COMPLIANCE ON THE PLAN.
  
 17.)S1 SHOWS DISTANCES OF 29FT (EAST
 WALL) AND 16FT (SOUTH WALL) BETWEEN
 GROUT FILLED CELLS.A 4FT DISTANCE IS
 MORE TYPICAL FOR CBS CONSTRUCTION.IF
 THIS IS AN ERROR, PLEASE REVISE THE
 PLANS.IF THIS IS NOT AN ERROR, PLEASE
 CONTACT ME TO DISCUSS.
  
 18.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC, FBC13-103.1.
  
 19.)THE SQUARE FOOT AREA ON THE ENERGY
 CALCS IS 3250, THE PLAN IS 3594.THE
 TWO SHOULD BE CONSISTENT.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-05-29 Cont ID  
Sent By jleahy Date 2007-05-29 Time 17:48 Rev Time 1.00
Received By jleahy Date 2007-05-29 Time 17:48 Sent To  
Notes
2007-05-29 17:50:11PROVISO!PROVIDE LISTING FROM NRTL FOR SYSTEM, AT TIME
 OF FINAL INSPECTION.
  
 QUESTIONS CALL JAKE 644-7291

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-05-11 Cont ID  
Sent By dpalmer Date 2007-05-11 Time 13:45 Rev Time 0.00
Received By dpalmer Date 2007-05-11 Time 13:37 Sent To PC
Notes
2007-05-11 13:45:37** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
  
  
 1) NOTE:PLEASE SEE THAT ANY TRANSFER TYPE DEVICE OR
 EQUIPMENT MUST PROVIDE A FAIL SAFE OPERATION SO THAT NO
 INADVERTENT CONNECTION CAN BE DONE FROM EITHER THE
 UTILITY OR BACK UP POWER SOURCE.
 PLEASE KNOW THAT EXTENDED CONVERSATIONS WITH UL, NEMA
 ANDNUMEROUS MANUFACTURES AND OTHER JURISDICTIONS ON
 TO STATE AND NATIONAL LEVEL HAS ALREADY TAKEN PLACE AND
 THIS SPECIFIC DEVICE DOES NOT MEET THE CODE OR PROVIDE
 THE REQUIRED ACTION BY THE NEC AND CAN NOT BE ACCEPTED
 BY THIS AHJ.
 110.3, 702.6.
 PLEASE SUBMIT THE MANUFACTURE SPEC/CUT SHEETS FOR THE
 NEW EQUIPMENT WHICH WILL PROVIDE THIS OPERATION. 110.3,
 90.7, 100, 702.5
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 08:50 Rev Time 0.00
Received By dpalmer Date 2006-11-02 Time 08:37 Sent To  
Notes
2006-11-02 08:50:17*** ELECTRICAL OK, NEW ENERGY CALCULATIONS OK W/
 ELECTRICAL.
  
  
 ** PLEASE SEE THE LIGHTING WIND LOAD CALCULATIONS
 CONTAIN RAISED SEALS OVER "PHOTO-COPED" SIGNATURE WHICH
 IS NOT PERMITTED PER FS 471.025. MUST BE AN ORIGINAL
 SIGNATURE AND DATE. PLEASE ALSO SEE NO TITLE BLOCK IS
 ON SHEETS EITHER.
 FAC 61G15-23.002, FS 471.023
  
 ** PLEASE KNOW, IF NEW SIGNED, DATED AND SEALED WIND
 LOAD CALCS ALONG WITH CORRECT TITLE BLOCKS CAN BE
 BROUGHT IN BEFORE BUILDING REVIEW IS DONE, THIS MAY NOT
 HOLD UP PROJECT. PLEASE CALL THIS REVIEWER OF THERE ARE
 ANY QUESTIONS ON THIS.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-10-15 Cont ID  
Sent By dpalmer Date 2006-10-15 Time 11:10 Rev Time 0.00
Received By dpalmer Date 2006-10-14 Time 19:43 Sent To  
Notes
2006-10-15 11:10:34*** UNSAT 3RD REVIEW ***
  
 1)NOTE: PLEASE SEE RESPONSE MENTIONS THE NEW AND
 UPDATED ENERGY CALCULATIONS WERE DONE, SIGNED, DATED
 AND SEALED, HOWEVER THE ONLY TWO SETS OF ENERGY
 CALCULATIONS SUBMITTED WERE THE SAME ONES FROM THE
 PREVIOUS REVIEW DATED 6/5/06.
 AS REQUESTED ON PREVIOUS REVIEW PLEASE SUBMIT AND
 ADJUSTAS NOTED IN PREVIOUS REVIEW NOTES.
 FBC 2004 CHAPTER 13 .
  
 ** ADDRESS IN SYSTEM HAS BEEN CORRECTED TO 850
 BELVEDERE RD PER THE ADDRESSING REVIEWER'S REQUEST
 WHICH IS AN EXTENSION OF RTHE PCN FOR 2700 PARKER AVE.
 THE PCN #'S ON ALL APPLICATIONS HAVE BEEN CHANGED TO
 74434333130020010.
  
 ** FYI , THE NOTICE OF COMMENCMENT SUBMITTED HAS SINCE
 EXPIRED AND HAS BEEOME "VOID". PLEASE SEE FS 713.13(2),
 WHEN THE WORK HAS NOT COMMENCED WITHIN 90DAYS OF
 RECORDING SUCH NOC, THE NOC BECOMES INVALID AND MUST BE
 RE-RECORDED.
 ** PLEASE KNOW, THIS RECORDED NOC ONLY NEEDS TO BE
 SUBMITTED ONCE PERMIT IS ISSUED AND READY FOR PICK UP.
  
 ** FYI, PLEASE KNOW, THE NEW PERMIT APPLICATION FOR THE
 CHANGE OF CONTRACTOR NOW HAS ALL THE SUB CONTRACTORS
 SIGNED ON. THESE HAVE BEEN CROSSED OUT AS THEY WERE NOT
 SIGNED ON ORIGINAL APPLICAITON AND WILL BE REQUIRED TO
 PULL SEPARATE SUB PERMITS ONCE PERMIT IS ISSUED. THIS
 WOULD BE THE $50 SUB PERMIT FEE FOR MOST , HOWEVER A
 SEPARATE PERMIT FOR LV AND SECURITY WILL BE REQUIRED
 AND SHALL BE BASED ON THEIR CONTACT/SCOPE OF WORK
 VALUE.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-10-14 19:43:33IN ELEC FOR REVIEW,

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-24 Cont ID  
Sent By dpalmer Date 2006-06-24 Time 12:18 Rev Time 0.00
Received By dpalmer Date 2006-06-24 Time 11:26 Sent To  
Notes
2006-06-24 00:00:00*** UNSAT 2ND REVIEW ***
  
 ** PLEASE SSE SOME COMMENTS FROM
 PREVIOUS REVIEW AND SEE ALSO NEW NOTE
 NOT ON PREVIOUS REVIEW.
  
 1) NOTE: PLEASE SEE TITLE BLOCKS ON
 PLANS SHALL CONTAIN THE ADDRESS OF
 BUILDING/SITE. PLEASE SEE THE RESPONSE
 MENTIONS THIS WAS ADDED TO NORTH
 ELEVATION, HOWEVER THIS IS REQUIRED ON
 ALL SHEETS AND FOR ALL TRADES.
 61G1-16.004,61G15-23.002
 PREVIOUS REVIEW.
  
 2) NOTE: PLEASE SEE SHEETS SIGNED AND
 SEALED BY KILDAY AND ASSOCIATES AND
 NEIL, SMITH AND ASSC.
 PLEASE SEE MISSING REQUIRED INFORMATION
 ON TITLE BLOCKS AS MENTIONED ON PREVIOUS
 REVIEW.
 THESE ARE MISSING THE PRINTED NAME AND
 LICENSE NUMBERS, AND CERTIFICATE OF
 AUTHORIZATION #S' .
 PLEASE KNOW, NEIL AND ASSC IS MISSING
 THE CA# AND KILDAY AND ASSC IS MISSING
 PRINTED NAME, AND CA #.
 61G1-16.004, FS 481.219
  
 3) NOTE: PLEASE SEE THAT NO WIND LOAD
 CALCULATIONS SIGNED, DATED AND SEALED
 WERE SUBMITTED FOR LT POLE/SITE LTS.
 PREVIOUS REVIEW
  
 ** NEW NOTE**
  
 4) NOTE: PLEASE SEE ENERGY CALCULATIONS
 ARE REQUIRED TO BE SIGNED, DATED AND
 SEALED BY THE RESPONSIBLE DESIGNER(S).
 PLEASE KNOW, AS SUBMITTED THESE DO NOT
 SEEM TO COMPLY TO 2004 FBC CHAPTER 13,
 AS CALC SHEETSDO NOT SEEM TO INDICATE
 ALL LIGHTING AND AMOUNTS PERMITTED AND
 USED PER 13-415.1.AB.1 FOR MIN
 CALCULATIONS TO BE SHOWN, PLEASE ALSO
 SEE LIGHTING DENSITIES REQUIRED IN
 CALCULATIONS, 13-415.2.ABC.1 , ONLY ONE
 OF THE TWO METHODS ARE PERMITTED.
 PLEASE SEE TABLES.
  
 ** PLEASE SEE BUIIDING REVIEW COMMENTS
 AS PRODUCT APPROVALS SHOULD NOT BE
 ATTACHED TO PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-20 Cont ID  
Sent By dpalmer Date 2006-03-20 Time 12:05 Rev Time 0.00
Received By dpalmer Date 2006-03-20 Time 07:12 Sent To  
Notes
2006-03-20 00:00:00***** UNSAT ******
  
 1)NOTE: PLEASE SEE COMMENTS WITH RESPECT
 TO ADRESSING OF PROJECT. PLEASE BE SURE
 TO ADD ADDRESS OF LOCATION TO PLANS WHEN
 FINAL ADDRESS IS CONFIRMED BEFORE
 RESUBMITTING PLANS.
 FAC 61G1-16.004
  
 2)NOTE: PLEASE SEE WIND LOADS ARE
 REQUIRED AT THIS TIME FOR REVIEW BY THE
 STRUCTURAL REVIEWER. THESE SHOULD
 INCLUDE POLES W/ FIXTIURES.
  
 3)NOTE: PLEASE SEE MISSING CERTIFICATE
 OF AUTHORIZATION NUMBER ON LANDSCAPE
 PLANS.
 FAC 61G1-16.004, FS 481.0219
 ** PLEASE KNOW, THIS IS NOT FOR JLRD.
  
 4) NOTE: PLEASE BE SURE PLANS REFERENCE
 THE CURRENT CODE AS FOLLOWS.
 2002 NFPA-70(NEC), 2003 NFPA-101, 2002
 NFPA-70
  
 5)NOTE: PLEASE CLARIFY WHAT MEANS IS
 GOING TO BE PROVIDED FOR CONNECTION OF
 PORTABLE GENERATOR ? (IF ANY) WILL THERE
 BE A RECEPT?
 215.5
  
 6)NOTE: PLEASE SEE MISSING FOOTER STEEL
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM.250.50, 250.52
  
 7)NOTE: PLEASE SEE RISER IS SHOWING AN
 "EUIPMENT GROUNDING CONDUCTOR" TO THE
 FIRST MEANS OF DISCONNECT FROM FPL
 TRANSFORMER? THIS APPEARS TO BE A
 MISPRINT.?
 PLEASE SEE 250.6,250.24B, THE "EQUIPMENT
 GROUNDING CONDUCTOR" IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 ** PLEASE BE SURE TO SEE ANY OTHER
 POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE COMPLETELY REMOVE ANY
 OLD/VOIDED SHEETS FROM SETS. ONLY INSERT
 THE NEW REVISED SHEETS INTO SETS. ONE
 COPY OF THE OLD/VOIDED REMOVED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2006-06-20 Cont ID  
Sent By   Date 2006-06-20 Time   Rev Time 0.00
Received By   Date 2006-06-20 Time   Sent To AD
Notes
2006-06-20 00:00:00PLEASE REMOVE REFERENCE TO TOWN OF
 JUPITER THAT APPEARS IN GENERAL NOTES
 FOR INLETS.
  
 NOTE THAT A PRE-CONSTRUCTION MEETING
 MUST BE SCHEDULED WITH CITY UTILITIES.
 PLEASE CONTACT MANNY GONZALEZ (561)
 494-1040.
  
 STEVE SARLEY
 (561) 494-1095

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2006-05-23 Cont ID  
Sent By   Date 2006-05-23 Time   Rev Time 1.50
Received By   Date 2006-05-23 Time   Sent To  
Notes
2006-05-23 00:00:001.113 L.F. CAPH W/40 & 40 L.F. EXF
 TRENCH NOT CLEAR.
  
 2.GENEARL NOTES FOR INLETS REFERS TO
 TOWN OF JUPITER STANDARDS.
  
 3.PLEASE SUBMIT DRAINAGE CALCULATIONS,
 GEOTECHNICAL ENGINEERING REPORT
 INDICATING 'K' VALUE FOR SOILS,
 GROUNDWATER ELEVATION.
  
 4.EXFILTRATION TRENCH DETAIL SHOULD
 INDICATED DEPTH OF DRY TRENCH,
 GROUNDWATER ELEVATION.
  
 5.INVERT ELEVATIONS ARE DIFFICULT TO
 READ, PLEASE MOVE FROM EDGE OF SHEET.
  
 6.PLEASE SHOW CONTROL STRUCTURE IN
 SECTION VIEW ALSO.
  
 7.POLLUTION PREVENTION PLAN SHOULD
 INDICATE LOCATION OF SILT FENCE.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-10-20 Cont ID  
Sent By mwennerg Date 2006-10-20 Time 14:25 Rev Time 0.00
Received By mwennerg Date 2006-10-20 Time 14:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-07-06 Cont ID  
Sent By mwennerg Date 2006-07-06 Time 15:10 Rev Time 0.00
Received By mwennerg Date 2006-07-06 Time 15:10 Sent To  
Notes
2006-07-06 00:00:00***DENIED***
  
 1) COMMENT (5)- PLEASE SEE MECHANICAL
 CODE, 2004 EDITION SEC.606.4.1 (2) THAT
 REQUIRES VISUAL/AUDIBLE SIGNAL BE
 PROVIDED FOR DUCT SMOKE DETECTORS EVEN
 WHEN NO FIRE ALARM SYSTEM EXISTS.
  
 2) COMMENT (6) PLEASE PROVIDE RESPONSE
 EITHER BY ACKNOWLEDGMENT OR NOTE ON
 PLANS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-05-10 Cont ID  
Sent By mwennerg Date 2006-05-10 Time 11:34 Rev Time 0.00
Received By mwennerg Date 2006-05-10 Time 11:34 Sent To  
Notes
2006-05-10 00:00:00******DENIED******
  
 1) PLEASE SEE COMMENTS REGARDING CORRECT
 ADDRESSING OF BUILDING. ADDRESS SHALL BE
 MINIMUM OF 6" IN HEIGHT AND CONTRASTING
 TO BACKGROUND. PLEASE ADD NOTE TO
 ELEVATIONS.
  
 2) LIFE SAFETY NFPA 101, 2003 EDITION
 SHALL BE REFERENCED.
  
 3) PLEASE PROVIDE CLARIFICATION
 REGARDING TRAVEL DISTANCE. IS THIS NOTE
 REFERENCING TRAVEL DISTANCE TO EXITS OR
 COMMON PATH OF TRAVEL? NFPA 101,
 SECTIONS 38.2.5 AND 38.2.6.
  
 4) PLEASE INDICATE THE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS IN TERMS OF CLASS A,B OR C.
  
 5) SHT M-2 MENTIONS A FIRE ALARM SYSTEM.
 (NOTE #4) DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM IN
 ACCORDANCE WITH LOCAL REQUIREMENTS.
 WHERE NO FIRE ALARM IS PROVIDED,
 AUDIBLE/VISUAL DEVICES ARE STILL
 REQUIRED FOR OCCUPANT NOTIFICATION.
  
 6) SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE ALARM SYSTEM.
  
 7) PLEASE CLARIFY NOTE ON SHT E-5 IN
 REFERENCE TO MONITORING OF SMOKE
 DETECTORS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-20 Cont ID  
Sent By adarroug Date 2007-06-20 Time 14:15 Rev Time 0.00
Received By adarroug Date 2007-06-20 Time 14:15 Sent To B
Notes
2007-06-20 14:15:45TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-08 Cont ID  
Sent By adarroug Date 2007-05-08 Time 10:23 Rev Time 0.00
Received By adarroug Date 2007-05-08 Time 10:23 Sent To E
Notes
2007-05-08 10:24:03TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-01 Cont ID  
Sent By adarroug Date 2006-11-01 Time 17:36 Rev Time 0.00
Received By adarroug Date 2006-11-01 Time 17:35 Sent To  
Notes
2006-11-01 17:36:18TO "COMM" BD#56

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-21 Cont ID  
Sent By adarroug Date 2006-09-21 Time 10:52 Rev Time 0.00
Received By adarroug Date 2006-09-21 Time 10:52 Sent To Z
Notes
2006-10-11 14:20:58TO "COMM" BD#63
2006-09-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-09 Cont ID  
Sent By adarroug Date 2006-06-09 Time 11:16 Rev Time 0.00
Received By adarroug Date 2006-06-09 Time 11:16 Sent To  
Notes
2006-06-22 00:00:00TO "COMM" BD#53
2006-06-09 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-23 Cont ID  
Sent By adarroug Date 2006-05-23 Time 16:54 Rev Time 0.00
Received By adarroug Date 2006-02-22 Time 11:52 Sent To  
Notes
2006-04-19 00:00:00TO "COMM" BD#33
2006-02-22 00:00:00WAITING FOR "COMM" BD-A COPY OF APPL.
 SENT TO ADDR.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-10-27 Cont ID  
Sent By pkrauss Date 2006-10-27 Time 13:29 Rev Time 0.00
Received By pkrauss Date 2006-10-27 Time 13:15 Sent To  
Notes
2006-10-27 13:35:21PROVISO:
 DUCT SMOKE DETECTOR ACTIVATION SHALL CASE VISUAL AND
 AUDIBLE SIGNAL IN A NORMALLY OCCUPIED AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-08-07 Cont ID  
Sent By pkrauss Date 2006-08-07 Time 15:28 Rev Time 0.00
Received By pkrauss Date 2006-08-07 Time 13:50 Sent To  
Notes
2006-08-07 00:00:00DENIED:
 FIRST PLAN REVIEW BY HAROLD MOSER
 4-3-06, ALL COMMENTS ADDRESSED.
  
 1.PLAN SHEET M-2 VENTILATION
 CALCULATION REFERS TO ASHRAE 62-89 THIS
 SHOULD READ ASHRAE 62-01.
  
 2.PLAN SHEET M-2 OCCUPANCY
 CLASSIFICATION PLAN INDICATES
 COMMERCIAL, THIS SHOULD READ BUSINESS
 ACCORDING TO 2004 FBC 304.1.
  
 3.PLAN SHEET M-2 MECHANICAL NOTE #4
 INDICATES DUCT SMOKE DETECTOR FOR FAN
 SHUTDOWN.PLEASE NOTE, FAN SHUTDOWN
 SHALL ALSO COMPLY WITH 606.4.1 THE DUCT
 SMOKE DETECTOR SHALL ACTIVATE A VISIBLE
 & AUDIBLE SUPERVISORY SIGNAL AT A
 CONSTANTLY ATTENDED LOCATION OR COMPLY
 WITH EXCEPTION 1 OR 2.
  
 PLANS DO NOT INDICATE IF THE VAULT HAS A
 FIRE RESISTANCE RATING.PLEASE CLARIFY.
 SHOULD CEILING TO THE VAULT BE RATED A
 CEILING DAMPER WILL BE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-03 Cont ID  
Sent By hmoser Date 2006-04-03 Time 11:01 Rev Time 0.00
Received By hmoser Date 2006-04-03 Time 11:01 Sent To  
Notes
2006-04-03 00:00:00PLAN DENIED
 1) PLEASE REFER TO SECTION 302.1.1 2004
 FBC INCIDENTAL USE AREAS, AND TABLE
 302.1.1 REFRIGERAN MACHINERY ROOM 2004
 FBC.
 2) PLEASE REFER TO SECTION 307.2.3
 AUXILIARY AND SECONDARY DRAIN SYSTEM.
 2004 FBC(M)
 3) PLEASE PROVIDE DUCT SIZE FOR BATH
 ROOM EXHAUST ON PLANS.ROOM 114,115.
 4) PLEASE PROVIDE EXHAUST DUCT SIZE FOR
 ROOM 104 ON PLANS
 5) PLEASE REFER TO SECTION 601.4
 BALANCED RETURN AIR 2004 FBC(M).
 6) PLEASE SIZE RETURN AIR DUCT OM PLANS
 ROOMS 120,101,116.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-08 Cont ID  
Sent By pschmitz Date 2006-07-08 Time 09:37 Rev Time 0.00
Received By pschmitz Date 2006-07-28 Time 09:37 Sent To  
Notes
2006-07-28 00:00:00RE-SUB

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-06 Cont ID  
Sent By pschmitz Date 2006-05-06 Time 07:44 Rev Time 0.00
Received By pschmitz Date 2006-05-06 Time 05:03 Sent To  
Notes
2006-05-06 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
 1) SHTA-17 DETAIL 5/17 LOUNGE112
 11-4.24 SINKS.
 11-4.24.1 GENERAL.
 SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION
 11-4.24.
 11-4.24.2 HEIGHT.
 SINKS SHALL BE MOUNTED WITH THE COUNTER
 OR RIM NO HIGHER THAN 34 INCHES (865 MM)
 ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE.
 KNEE CLEARANCE THAT IS AT LEAST 27
 INCHES (685 MM) HIGH, 30 INCHES (760 MM)
 WIDE, AND 19 INCHES (485 MM) DEEP SHALL
 BE PROVIDED UNDERNEATH SINKS.
 11-4.24.4 DEPTH.
 EACH SINK SHALL BE A MAXIMUM OF 6?
 INCHES (165 MM) DEEP.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES
 BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. ( NO DOORS )THE CLEAR
 FLOOR SPACE
 SHALL BE ON AN ACCESSIBLE ROUTE AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485
 MM) UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED UNDER
 SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED SO AS TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER SINKS.
 11-4.24.7 FAUCETS.
 FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE,
 TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED
 MECHANISMS ARE ACCEPTABLE DESIGNS.
  
 2)SHT A-17 DETAIL 3/17 TOILET RM PLAN
 DRINKING FOUNTAIN
 11-4.15.5 CLEARANCES.
 (1) WALL- AND POST-MOUNTED CANTILEVERED
 UNITS SHALL HAVE A CLEAR KNEE SPACE
 BETWEEN THE BOTTOM OF THE APRON AND THE
 FLOOR OR GROUND AT LEAST 27 INCHES (685
 MM) HIGH, 30 INCHES (760 MM) WIDE, AND
 17 INCHES TO 19 INCHES (430 MM TO 485
 MM) DEEP [SEE FIGURE 11-27(A) AND FIGURE
 11-27(B)]. SUCH UNITS SHALL ALSO HAVE A
 MINIMUM CLEAR FLOOR SPACE 30 INCHES BY
 48 INCHES (760 MM BY 1219 MM) TO ALLOW A
 PERSON IN A WHEELCHAIR TO APPROACH THE
 UNIT FACING FORWARD.
  
 3)SHT A-9 ROOF DRAINS SEC 1101.1 SCOPE.
 THE PROVISIONS OF THIS CHAPTER SHALL
 GOVERN THE MATERIALS, DESIGN,
 CONSTRUCTION AND INSTALLATION OF STORM
 DRAINAGE.
 1101.2 WHERE REQUIRED.
 ALL ROOFS, PAVED AREAS, YARDS, COURTS
 AND COURTYARDS SHALL DRAIN INTO A
 SEPARATE STORM SEWER SYSTEM, OR A
 COMBINED SEWER SYSTEM, OR TO AN APPROVED
 PLACE OF DISPOSAL.
  
 4) 1106.2 VERTICAL CONDUCTORS AND
 LEADERS.
 VERTICAL CONDUCTORS AND LEADERS SHALL BE
 SIZED FOR THE MAXIMUM PROJECTED ROOF
 AREA, IN ACCORDANCE WITH TABLE 1106.2.
  
 5)DHT P-1 WATER HEATER
 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED
 PRESSURE CAUSED BY THERMAL EXPANSION
 SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND
 607.3.2.
 CHECK VALVE.
 WHERE A BACKFLOW PREVENTION DEVICE,
 CHECK VALVE OR OTHER DEVICE IS INSTALLED
 ON A WATER SUPPLY SYSTEM UTILIZING
 STORAGE WATER HEATING EQUIPMENT SUCH
 THAT THERMAL EXPANSION CAUSES AN
 INCREASE IN PRESSURE, A DEVICE FOR
 CONTROLLING PRESSURE SHALL BE INSTALLED.
  
 6) 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER
 DISTRIBUTION SYSTEM SHALL BE CONTROLLED
 TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE
 INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED. WATER-HAMMER ARRESTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS.TO BE
 INSTALLED BETWEEN THE LAST TWO FIXTURES,
 NOT IN THE CEILING.
  
 7) MATERIALS: SPECIFI THE TYPE AND
 SCHEDUE OF MATERIAL FOR THE WATER AND
 DRAINAGE PIPING.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2006-11-09 Cont ID  
Sent By jroach Date 2006-11-09 Time 11:57 Rev Time 0.00
Received By jroach Date 2006-11-09 Time 11:57 Sent To  
Notes
2006-11-09 13:43:4511/9/06--TO "SHILL" DESK PER "JROACH"ADARROUGH

Review Stop Z ZONING
Rev No 3 Status F Date 2006-10-24 Cont ID  
Sent By jroach Date 2006-10-24 Time 09:34 Rev Time 0.00
Received By jroach Date 2006-10-24 Time 09:27 Sent To  
Notes
2006-10-24 09:34:15***FAILED***
  
 1) THE DUMPSTER ENCLOSURE, AS SHOWN ON SHEETS SP-4 AND
 SP-2, DOES NOT CONFORM TO THE MINIMUM DIMENSIONS.
 SHEET SP-1 IS CORRECT....ALL PLANS NEED TO BE
 CONSISTENT.
  
 2) THE LANDSCAPE AND SITE PLAN DATA TABLES DO NOT MATCH
 WITH REGARD TO THE FOLLOWING:
  
 2A) LANDSCAPE AREA
  
 2B) IMPERVIOUS/PAVED AREA
  
 3) IMPROVEMENTS PROPOSED ALONG THE SOUTH LEASE LINE
 (INCLUDING A SITE WALL) ARE SHOWN ON SHEET SP-2, BUT
 NOT SP-1.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR
 PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-09 Cont ID  
Sent By jroach Date 2006-07-09 Time 17:10 Rev Time 0.00
Received By jroach Date 2006-07-09 Time 17:10 Sent To  
Notes
2006-07-09 00:00:007/9/06 ***FAILED***
  
 1) THE SITE PLAN DOES NOT PROVIDE A DATA
 TABLE, WHICH SHOULD INDICATE THE
 FOLLOWING:
  
 A) EXISTING ZONING
 B) TOTAL ACRES OF THE PROJECT
 C) TOTAL GROSS BUILDING SQUARE FOOTAGE
 D) PERCENTAGE OF OPEN SPACE,
 LANDSCAPING, BUILDING COVERAGE, AND
 IMPERMEABLE SURFACE
 E) PARKING CALCULATIONS (REQUIRED AND
 PROPOSED)
 F) FLOOR AREA RATIO (FAR)
  
 2) A PARKING STALL DETAIL SHALL BE
 PROVIDED INDICATING STRIPING AND
 DIMENSIONS OF REGULAR AND HANDICAP
 PARKING SPACES.STRIPING AND DIMENSIONS
 SHALL CONFORM TO SECTION 94-485 OF THE
 CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 3) PROVIDE DETAILS REGARDING WHAT
 MECHANICAL EQUIPMENT WILL BE LOCATED ON
 THE SLAB ADJACEN TO THE LOADING ZONE.
 APPROPRIATE SCREENING MAY BE REQUIRED.
  
 4) THE DUMPSTER ENCLOSURE DOES NOT MEET
 THE MINIMUM DIMENSIONAL REQUIREMENTS OF
 SECTION 94-444(B) OF THE CITY OF WEST
 PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 5) LANDSCAPING SHALL BE PROVIDED ON ALL
 SIDES OF THE DUMPSTER ENCLOSURE, WITH
 THE EXCEPTION OF THE GATE.
  
 6) PLANTING IN THE VISIBILITY TRIANGLE
 SHALL BE CLEAR BETWEEN 18 INCHES AND 8
 FEET.THE LANDSCAPE PLANS INDICATE
 SEVERAL TREES/SHRUBS WITHIN THE PARKER
 AVENUE AND BELEVEDERE ROAD
 INGRESS/EGRESS SIGHT TRIANGLES.
  
 7) THE SECTION NUMBER UNDER "NOTES" ON
 SHEET LP-1 OF THE LANDSCAPE PLANS IS
 INCORRECT.
  
 8) LANDSCAPE DETAILS/NOTES INDICATE PALM
 BEACH COUNTY...PLEASE ADJUST
 ACCORDINGLY.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-24 Cont ID  
Sent By credford Date 2006-05-26 Time 4:40 Rev Time 0.00
Received By credford Date 2006-05-26 Time 10:10 Sent To  
Notes
2006-06-02 00:00:00DENIED
  
 1. SITE PLAN IS CONFUSING, NEEDS TO BE
 REPRINTED WITH CLEAR DIMENSION LINES.
  
 2. NO SITE DATA REFERENCING BUILDING
 COVERAGE, PERMEABLE AND IMPERMEABLE
 AREAS, PARKING OR FAR.
  
 3. PLEASE CLARIFY COMMENT ON DEMOLITION
 SHEET SD-1.
  
 4. SURVEY NEEDED.
  
 5. LANDSCAPING BUFFER ON SOUTHERN END
 MISSING.
  
 6. HANDICAP ACCESSIBILITY ON LANDSCAPING
 AND SITE PLANS DO NOT MATCH.
  
 7. INSIDE DIMENSIONS ON THE DUMPSTER
 MUST BE 13?4? X 13?4?.DUMPSTER GATE
 WITH 12?6? OPENING MUST BE SHOWN ON THE
 SITE PLAN.
  
 8. DUMPSTER DRAWINGS DIMENSIONS ARE
 INCONSISTENT.
  
 9. LANDSCAPING NEEDED ON ALL SIDES OF
 THE DUMPSTER.
  
 CAROLYN REDFORD - 561-822-1449
2006-05-23 00:00:00AMY TO GIVE PLANS TO CAROLYN