Plan Review Details - Permit 06020769
Plan Review Stops For Permit 06020769
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-03-17 Cont ID  
Sent By amorse Date 2006-03-17 Time 07:37 Rev Time 0.33
Received By amorse Date 2006-03-17 Time 07:37 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-03-07 Cont ID  
Sent By amorse Date 2006-03-07 Time 08:45 Rev Time 0.50
Received By amorse Date 2006-03-07 Time 08:45 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-13 Cont ID  
Sent By btrobaug Date 2006-03-13 Time 14:36 Rev Time 0.33
Received By btrobaug Date 2006-03-13 Time 14:18 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-03-01 Cont ID  
Sent By btrobaug Date 2006-03-01 Time 14:53 Rev Time 0.33
Received By btrobaug Date 2006-03-01 Time 14:33 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-03-03 Cont ID  
Sent By mperson Date 2006-03-03 Time 15:06 Rev Time 0.00
Received By mperson Date 2006-03-03 Time 15:06 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-10 Cont ID  
Sent By adarroug Date 2006-03-10 Time 14:25 Rev Time 0.00
Received By adarroug Date 2006-03-10 Time 14:25 Sent To E
Notes
2006-03-10 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-28 Cont ID  
Sent By adarroug Date 2006-02-28 Time 17:45 Rev Time 0.00
Received By adarroug Date 2006-02-28 Time 17:45 Sent To E
Notes
2006-02-28 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-07 Cont ID  
Sent By amorse Date 2006-03-07 Time 08:45 Rev Time 0.00
Received By amorse Date 2006-02-19 Time 11:31 Sent To  
Notes
2006-02-19 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-03-20 Cont ID  
Sent By mperson Date 2006-03-20 Time 11:05 Rev Time 0.33
Received By mperson Date 2006-03-20 Time 11:05 Sent To B
Notes
2006-03-20 00:00:00 
  
 ******PROVISO******
 COMPLY WITH FBC-2004 SEC. R4101 PRIVATE
 SWIMMING POOLS
 ****************************************
  
 ******PROVISO******
 EXTERNAL HARTFORD LOOP REQUIRED ON POOL
 HEATER
 ****************************************
 ****************************************

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-03-16 Cont ID  
Sent By mperson Date 2006-03-16 Time 11:42 Rev Time 0.33
Received By mperson Date 2006-03-16 Time 11:42 Sent To B
Notes
2006-03-16 00:00:00**DENIED 2ND TIME**
 REFERENCE:FBC-2004 R4101 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW:
  
 1) PRINT AND SUBMITTAL OF HEAT PUMP NEED
 TO BE CORRELATED. HEAT PUMP SUBMITTAL
 INDICATES ELECTRIC AND THE PRINT
 INDICATES GAS PLEASE CORRELATE.
 2) PER SEC. R4101.6.6.5 PLEASE PROVIDE
 THE MAKE AND MODEL NUMBER OF THE CLEANER
 FITTING. (ADD TO PRINT, OR SUBMIT
 DETAIL)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-03 Cont ID  
Sent By mperson Date 2006-03-03 Time 15:07 Rev Time 0.33
Received By mperson Date 2006-03-03 Time 15:07 Sent To B
Notes
2006-03-03 00:00:00DENIED
 REFERENCE: FBC-2004 R4101 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATIOM REQUIRED FOR PLAN REVIEW.
  
 1) COMPLY WITH FBC-2004 SEC. R4101
 PRIVATE SWIMMING POOLS.(ADD TO NOTES)
 2) FBC-2004 R4101.6.6.3 ENTRAPMENT AD-
 VOINANCE PLEASE SUBMIT AN 1-1/2" ATMOS-
 PHERIC VENT LENGTH CHART WITH PUMP SIZE
 AND TOTAL LENGTH OF VENT TO COMPLY WITH
 3 SECOND RELEASE.
 3) FBC-2004 R4101.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.(DETAILS NEEDED)
 4) FBC-2004 R4101.12.1
 PRESSURE TESTS. PER MANUFACTURE
 RECOMMENDATIONS, NO AIR TEST SHALL BE
 APPROVED FOR PVC PIPE AND FITTINGS. (ADD
 TO NOTES)
 5) FBC-2004 4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL REQUIRED)
 6) FBC-2004 R4101.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN HEATER WHEN PUMP IS SHUT OFF.
 (MANUFACTURE CUT SHEETS REQUIRED)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX(561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721
  

Review Stop Z ZONING
Rev No 1 Status P Date 2006-02-27 Cont ID  
Sent By mmclean Date 2006-02-27 Time 16:56 Rev Time 0.00
Received By mmclean Date 2006-02-27 Time 16:56 Sent To I
Notes
2006-02-27 00:00:00NOTE: THE POOL MUST SIT 25FT BEYOND THE
 FRONT SETBACK.