Plan Review Details - Permit 06020766
Plan Review Stops For Permit 06020766
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2006-05-19 Cont ID  
Sent By amorse Date 2006-05-19 Time 06:52 Rev Time 0.00
Received By amorse Date 2006-05-19 Time 06:51 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-03-24 Cont ID  
Sent By amorse Date 2006-03-24 Time 06:49 Rev Time 0.33
Received By amorse Date 2006-03-24 Time 06:49 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-03-08 Cont ID  
Sent By btrobaug Date 2006-03-08 Time 12:13 Rev Time 0.33
Received By btrobaug Date 2006-03-08 Time 12:07 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-03-10 Cont ID  
Sent By mperson Date 2006-03-10 Time 09:05 Rev Time 0.00
Received By mperson Date 2006-03-10 Time 09:05 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-17 Cont ID  
Sent By adarroug Date 2006-05-17 Time 16:18 Rev Time 0.00
Received By adarroug Date 2006-05-17 Time 16:18 Sent To P
Notes
2006-05-17 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-29 Cont ID  
Sent By adarroug Date 2006-04-29 Time 16:10 Rev Time 0.00
Received By adarroug Date 2006-04-29 Time 16:10 Sent To Z
Notes
2006-04-29 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-07 Cont ID  
Sent By adarroug Date 2006-03-07 Time 11:29 Rev Time 0.00
Received By adarroug Date 2006-03-07 Time 11:29 Sent To E
Notes
2006-03-07 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-24 Cont ID  
Sent By amorse Date 2006-03-24 Time 06:50 Rev Time 0.00
Received By amorse Date 2006-02-19 Time 11:24 Sent To  
Notes
2006-02-19 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-18 Cont ID  
Sent By mperson Date 2006-05-18 Time 14:27 Rev Time 0.33
Received By mperson Date 2006-05-18 Time 14:27 Sent To E
Notes
2006-05-18 00:00:00 
  
 ******PROVISO******
 COMPLY WITH FBC-2001 SEC 424.2 OR
 FBC-2004 RESIDENTIAL SEC. R4101 PRIVATE
 SWIMMING POOLS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-10 Cont ID  
Sent By mperson Date 2006-03-10 Time 09:06 Rev Time 0.33
Received By mperson Date 2006-03-10 Time 09:06 Sent To B
Notes
2006-03-10 00:00:00DENIED
 REFERENCE:FBC-2004 R4101 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW.
  
 1. COMPLY WITH FBC-2004 SEC. 4101
 PRIVATE SWIMMING POOLS. (ADD TO NOTES)
 2. FBC-2004 SEC. R4101.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. NEED EN-
 GINEERED TABLE FOR "VENT PIPE MAXIMUM
 LENGTH" INDICATING PUMP SIZES, AVERAGE
 FLOW (GPM), AND MAXIMUM LENGTH OF 1-1/2"
 PVC VENT PIPE TO COMPLY WITH THREE
 SECOND RELEASE.
 3. FBC-2004 R4101.6.6.5 PROVIDE DETAIL
 OF APPROVED VACUUM OR CLEANER FITTING
 WITH MODEL NUMBER.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)80506730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-16 Cont ID  
Sent By mmclean Date 2006-05-16 Time 16:47 Rev Time 0.00
Received By mmclean Date 2006-05-16 Time 16:47 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-03-02 Cont ID  
Sent By mmclean Date 2006-03-02 Time 10:18 Rev Time 0.00
Received By mmclean Date 2006-03-02 Time 10:17 Sent To I
Notes
2006-03-02 00:00:00DENIED,
 1. NEED TO SHOW THE DECK ON THE TWO COPY
 OF SURVEY WITH SETBACKS.
 (SIDE SETBACK 3FT & REAR 3FT)
 2. NEED TO MEET THE SETBACK FOR POOL
 SIDE INTERIOR 5FT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720