Plan Review Details - Permit 06020741
Plan Review Stops For Permit 06020741
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-02 Cont ID  
Sent By adarroug Date 2006-03-02 Time 19:39 Rev Time 0.00
Received By adarroug Date 2006-03-02 Time 19:39 Sent To M
Notes
2006-03-02 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-21 Cont ID  
Sent By tgordon Date 2006-02-21 Time 08:17 Rev Time 0.00
Received By tgordon Date 2006-02-19 Time 12:36 Sent To  
Notes
2006-02-19 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-03-06 Cont ID  
Sent By tgordon Date 2006-03-06 Time 11:36 Rev Time 0.25
Received By tgordon Date 2006-03-06 Time 11:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-21 Cont ID  
Sent By tgordon Date 2006-02-21 Time 08:06 Rev Time 0.25
Received By tgordon Date 2006-02-21 Time 08:06 Sent To  
Notes
2006-02-21 00:00:00*** DENIED ***
 1) PLEASE SHOW SIZES OF RETURN AIR
 TRANSFER GRILLS,BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 2)PLEASE LABEL ALL ROOMS (LIVING ROOM,
 BEDROOM, KITCHEN, ECT.).
  
 3)ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved