Plan Review Details - Permit 06020693
Plan Review Stops For Permit 06020693
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-03-06 Cont ID  
Sent By lmartine Date 2007-03-06 Time 11:46 Rev Time 0.00
Received By lmartine Date 2007-03-06 Time 11:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-03-05 Cont ID  
Sent By jgomez Date 2007-03-05 Time 08:07 Rev Time 0.50
Received By jgomez Date 2007-03-05 Time 07:35 Sent To Z
Notes
2007-03-05 08:11:20BUILDING SUBMITTAL CHECKLIST:
 1- PRODUCT APPROVAL FOR ROOF SHINGLES SUBMITTED NOA
 01-1127.13 IS EXPIRED. IT EXPIRED ON 02/21/07. PROVIDE
 CURRENT PRODUCT APPROVAL.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 PRODUCT APPROVAL AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-10-18 Cont ID  
Sent By jgomez Date 2006-10-18 Time 13:00 Rev Time 0.40
Received By jgomez Date 2006-10-18 Time 12:33 Sent To PC
Notes
2006-10-18 13:01:44REVISION: CHANGING POURED TIE BEAM TO BOND BEAM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-09-25 Cont ID  
Sent By jgomez Date 2006-09-15 Time 16:54 Rev Time 0.00
Received By lmartine Date 2006-09-15 Time 15:29 Sent To  
Notes
2006-09-15 00:00:00BUILDING REVIEW PROVISO:
 1- PROVIDE PRODUCT APPROVALS FOR ALL
 STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS.
 2- SHINGLES PRODUCT APPROVAL SUBMITTED
 DOESN'T MATCH THE ONE REVIEWED AND
 APPROVED BY THE ENGINEER. PROVIDE
 MATCHING PRODUCT APPROVAL.
 3- PROPERTY IS LOCATED IN FLOOD ZONE
 "C". NOT "B". AS PER COMMUNITY PANEL
 120229 0015 B DATED 3/1/1979. REVISE
 SURVEY AS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-09 Cont ID  
Sent By jgomez Date 2006-08-09 Time 17:06 Rev Time 0.00
Received By jgomez Date 2006-08-09 Time 17:06 Sent To  
Notes
2006-08-09 00:00:00BUILDING REVIEW 3RD CHECKLIST:
 1- ENGINEER TO READ ATTACHED COPY OF
 FLORIDA STATUTE 553.80(2)(B) REGARDING
 CHARGES FOR DESIGN PROFESSIONAL
 DOCUMENTS.
  
 2- NEED RE-RECORDED NOTICE OF
 COMMENCEMENT. NOC IS EXPIRED AFTER 90
 DAYS OF RECORDING IF WORK ISN'T STARTED.
 SEC. 713.9(2) FLORIDA STATUTES.
  
 3- HAND WRITTEN INFORMATION IS NOT
 ACCEPTABLE ON ANY DRAWING. ALL REVISIONS
 OR ADDITIONAL INFORMATION TO BE DONE ON
 ORIGINAL DRAWINGS TO BE PART OF THE
 SIGNED AND SEALED ENGINEER'S DRAWINGS.
  
 4- PROVIDE BATHROOM WITH DOOR THAT
 ALLOWS MIN. 29" CLEAR OPENING. 2'-6"
 WIDE DOOR DOESN'T PROVIDE 29" CLEAR
 OPENING. SEC. R322 2004 RESIDENTIAL CODE
  
 5- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL AS REQUIRED BY DCA RULE 9B-72
 FOR:
 A) ALL STRUCTURAL CONNECTORS SPECIFIED
 ON TRUSS ANCHOR SCHEDULE AND ALL DETAILS
 SHOWN ON PLANS. ONLY 1 PRODUCT APPROVAL
 FOR 1 CONNECTOR WAS SUBMITTED.
  
 B) DOOR AT KITCHEN/CARPORT AREA. SEE
 ELEVATIONS FOR TYPE OF DOOR SHOWN.
  
 6- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS (UPDATE LETTER TO MATCH
 RE-SUBMITTED PRODUCT APPROVALS)AS
 REQUIRED BY SECTION 106.3.3 OF CITY
 AMENDMENTS TO FBC 2004.
  
 7- ENERGY CALCULATIONS CALL FOR MI CASA
 BUILDERS AS THE CONTRACTOR. CONTRACTOR
 STATES THAT A CHANGE OF CONTRACTOR WILL
 TAKE PLACE. IF THERE IS GOING TO BE A
 CHANGE OF CONTRACTOR, THEN THE CHANGE OF
 CONTRACTOR FORM SHALL BE FILLED UP WHEN
 RE-SUBMITTING PERMIT PACKAGE AND CHANGE
 OF CONTRACTOR FEES APPLY. SEE ATTACHED
 CHANGE OF CONTRACTOR FORM.
  
 ***IMPORTANT:
 A NEW PERMIT APPLICATION MUST ACCOMPANY
 THE CHANGE OF CONTRACTOR'S FORM.
  
 8- SOIL TEST REPORT NEEDS THE
 ENGINEERING FIRM CERTIFICATE OF
 AUTHORIZATION NUMBER ON LETTERHEAD AS
 REQUIRED BY SECTION 61G15-23.002 OF
 F.A.C. . SEE ATTACHED COPY.
  
 9- STORM SHUTTERS:
 A) ENGINEER OF RECORD TO REVIEW AND
 APPROVE THE PRODUCT APPROVAL.
  
 B) PROVIDE KEY PLAN.
  
 C) PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE. PROVIDE
 ALL INFORMATION.
 ***NOTE: NEED TO DESCRIBE SPECIFIC
 ANCHOR AND KEEP IN MIND THAT STRUCTURE
 TO BE INSTALLED IS IN CONCRETE BLOCK,
 NOT CONCRETE.
  
 C) THERE IS SOME INFORMATION WRITTEN BY
 HAND ON EXTERIOR ELEVATIONS, SHEET A-1.
 THIS INFORMATION DOESN'T MATCH SIZE AND
 SPACING SHOWN ON PRODUCT APPROVAL.
 BESIDES, DON'T WRITE ON ANY OF THE
 ORIGINAL DWGS BECAUSE WILL VOID THEM.
  
 10- SHEET S-2:
 A) TRUSS ANCHOR SCHEDULE: CONNECTOR
 RT24 IS A WOOD TO WOOD CONNECTOR. NEED
 TO SPECIFY WOOD TO MASONRY CONNECTOR.
  
 B) ADDING STRAP DETAIL:
 * CONNECTORS SIMPSON L50, RT24T AND MSTA
 24 ARE WOOD TO WOOD CONNECTORS. NEED TO
 SPECIFY WOOD TO MASONRY CONNECTORS. SEE
 CATALOGUE FOR PROPER WOOD TO MASONRY
 CONNECTORS AND REVISE AS REQUIRED.
 OTHERWISE, PROVIDE COMPLETE ENGINEERING
 CALCULATIONS AND TESTING TO PROVE
 PROPOSED INSTALLATION. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 11- SHEET D-1:
 A) TYPICAL ONE STORY SECTION:
 * SIZE OF ROOF SHEATHING (5/8" OR
 19/32") AND TYPE OF NAIL (8D RING SHANK
 OR 8D PLANE SHANK) DOESN'T MATCH ROOF
 SHEATHING TABLE ON SAME PAGE.
  
 ** ATTIC VENTILATION NOTE IS NOT CLEAR.
 IS IT 4" CONT. VENT". SPECIFY.
  
 *** CONCRETE SLAB SPECS DON'TMATCH
 FOUNDATION PLAN. IS IT FIBERMESH OR WIRE
 MESH?. REVISE AS REQUIRED.
  
 12- PROVIDE SURVEY WITH ORIGINAL SEAL,
 SIGNATURE AND DATE AS REQUIRED BY
 CHAPTER 472 FLORIDA STATUTES. ALL
 DOCUMENTS SUBMITTED FOR PUBLIC RECORDS
 MUST HAVE ORIGINAL SEAL AND SIGNATURE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-29 Cont ID  
Sent By jgomez Date 2006-06-29 Time 10:30 Rev Time 2.50
Received By jgomez Date 2006-06-29 Time 10:30 Sent To  
Notes
2006-06-29 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 1- WILL NEED RE-RECORDED NOTICE OF
 COMMENCEMENT. RECORDED NOC WILL EXPIRE
 BY 6-30-06 IF WORK IS NOT STARTED BY
 THEN. SEC. 713.13.9(2) FL. STATUTES.
  
 2- REVISE ORIGINAL DWGS. HAND WRITTEN
 REVISIONS ARE NOT ACCEPTABLE. PROVIDE
 BATHROOM WITH DOOR THAT ALLOWS 29" MIN.
 CLEAR OPENING.
 SECTION R322 2004 RESIDENTIAL CODE.
  
 3- SPECIFY ATTIC ACCESS AND LOCATION.
 NOTE: REVISE ORIGINAL DRAWING.
 SEC. R807 2004 RESIDENTIAL CODE.
  
 4- RULE 9B-72 OF DCA REQUIRES FLORIDA OR
 LOCAL PRODUCT APPROVAL FOR:
 A) PRECAST LINTELS. INFORMATION WAS
 NOT SUBMITTED AND BE AWARE THAT DADE
 COUNTY NOA #03-0605.05 IS EXPIRED. NEED
 TO PROVIDE CURRENT ONE.
 B) ALL STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS. INFORMATION SUBMITTED IS NOT A
 PRODUCT APPROVAL REPORT. AND NEED
 PRODUCT APPROVAL FOR ALL CONNECTORS
 SPECIFIED ON PLANS. CHECK TRUSS ANCHOR
 SCHEDULE AND ALL DETAILS TO SEE WHICH
 CONNECTORS ARE SPECIFIED.
 C) ROOF SHINGLES. NOT SUBMITTED.
 D) SLIDING GLASS DOORS. PROVIDE DADE
 COUNTY NOA WITH CLEAR & LEGIBLE DWGS.
 ONE SUBMITTED IS NOT READABLE.
 E) ENTRY DOOR. ONE SUBMITTED IS FOR
 6'-8" HIGH DOORS. NEED FOR 8'-0" HIGH
 DOORS AS SPECIFIED ON PLANS. MAKE SURE
 PRINTS ARE CLEAR AND LEGIBLE.
 F) DOOR AT KITCHEN/CARPORT AREA. NOT
 SUBMITTED. MAKE SURE CORRECT SIZE IS
 SUBMITTED. SEE PLANS.
 G) SINGLE HUNG WINDOWS. NEED UPDATED
 NOA #05-0729.03. GO TO THE DCA WEBSITE
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD
 APPROVED CURRENT NOA. SEARCH FOR FL#6585
  
 5- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING (OR USE STANDARD
 REVIEW STAMP) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS
 TO FBC 2004. NEED TO PROVIDE REVISED
 LIST OF PRODUCT APPROVAL ACCORDING TO
 THE COMMENTS ON ITEM #4 ABOVE.
  
 6- DRAWINGS WERE STAMPED FOR IMPACT FEES
 ON 12-07-05. PERMIT APPLICATION WAS
 SUBMITTED ON 2-15-06. PLANS TO BE
 RE-STAMPED BY PALM BEACH COUNTY TO
 VERIFY THAT NO ADDITIONAL FEES ARE DUE
 SINCE IMPACT FEES CHANGED AFTER JANUARY
 13,2006. BRING BACK PAID RECEIPT AND
 RE-STAMPED PLANS. MAKE SURE THE RE-STAMP
 DRAWINGS ARE THE REVISED ONES.
  
 7- REVISE INFORMATION IN THE ENERGY
 CALCULATIONS: CONTRACTOR IS MI CASA
 BUILDERS, NOT T & F GENERAL CONTRACTING.
  
 8- PROVIDE 2 SIGNED AND SEALED COPIES
 OF THE SOIL TEST REPORT. REPORT IS
 MISSING THE FIRM CERTIFICATE OF
 AUTHORIZATION NUMBER AND THE ENGINEER'S
 LICENSE NUMBER AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTES AND 61G15-23.002 OF
 FLORIDA ADMINISTRATIVE CODE.
  
 9- STORM SHUTTERS: A) PROVIDE FLORIDA
 OR LOCAL PRODUCT APPROVAL FOR STORM
 SHUTTERS TO BE USED. INFORMATION
 SUBMITTED IS INCOMPLETE.
 B) PROVIDE KEY PLAN.
 C) PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE, WHICH HAS
 ALL INFORMATION REQ'D FOR PLAN REVIEW.
  
 10- SHEET A-2, S-1: A) REVISE ORIGINAL
 DRAWING. HAND WRITTEN REVISIONS ARE NOT
 ACCEPTABLE. UPDATE ALL INFORMATION ON
 EMERGENCY EGRESS WINDOWS NOTES. SEE 2004
 RESIDENTIAL CODE AND COMMENTS ON PLANS.
 B) GENERAL NOTES: SPECIFY CURRENT
 FLORIDA BUILDING CODE FOR WHICH BUILDING
 WAS DESIGNED. "AS ADOPTED BY THE COUNTY"
 IS NOT AN SPECIFIC CODE.
 C) DETAIL F1: SHOW GRADE LEVEL TO
 VERIFY COMPLIANCE WITH SEC. R403.1.4
 2004 RESIDENTIAL CODE.
 D) FOUNDATION PLAN: SHOW DROP FROM
 MAIN CONCRETE SLAB TO THE CARPORT AT
 ENTRY DOOR AND KITCHEN DOOR. ALSO AT
 SLIDING GLASS DOORS. SEE PLAN.
 E) SPECIFY CONCRETE SLAB JOINTS OR
 SPECIFY SUPPORTS SPACING FOR WWM AS
 REQUIRED BY SEC. R506.2.4 EXCEPTION #2
 OF 2004 RESIDENTIAL CODE.
 F) DELETE MECHANICAL NOTE IF IT
 DOESN'T APPLY TO THIS PROJECT.
 G) UPDATE REFERENCE INFORMATION FOR
 OPENINGS. SEE 2004 RESIDENTIAL CODE AND
 COMMENTS ON PLANS.
  
 11- SHEET S-2: REVISE ORIGINAL DRAWINGS.
 HAND WRITTEN REVISIONS ARE NOT
 ACCEPTABLE.
 A) TRUSS ANCHOR SCHEDULE: REVISE TYPO.
 CORRECT CONNECTOR IS TAPL16 NOT TALP16.
 B) CONNECTOR A5 IS A WOOD TO WOOD
 CONNECTOR. NEED TO SPECIFY WOOD TO
 MASONRY CONNECTOR. REVISE AS REQUIRED.
 C) SPECIFY WHERE DOES DETAIL F/A-6
 APPLIES TO?. NEW HAND WRITTEN REVISION
 CALLS FOR THIS DETAIL AT WALL BETWEEN
 CARPORT AND KITCHEN AREA. THEREFORE,
 NEED TO REVISE ROOF FRAMING TRUSS LAYOUT
 TO MATCH THIS CONDITION. CURRENT ROOF
 FRAMING PLAN DOESN'T CALL FOR TRUSS
 ABOVE THIS WALL. REVISE AS REQUIRED.
 D) REVISE LENGTH FOR PRECAST LINTEL
 #2. SEE PLANS FOR CORRECT SPAN.
 E) NEW ADDING STRAP DETAIL 1:
 * INCLUDE THIS DETAIL IN THE ORIGINAL
 DRAWING S-2.
 ** CONNECTOR USP RT24T IS A WOOD TO
 WOOD CONNECTOR. NEED TO SPECIFY WOOD TO
 MASONRY CONNECTOR. REVISE AS REQUIRED.
 *** CONNECTOR USP RT24T DOESN'T HAVE
 ENOUGH HOLES TO PUT 12 NAILS ON TRUSS
 SIDE. REVISE AS REQUIRED.
 **** CONNECTOR SIMPSON MSTA 24 IS ALSO
 A WOOD TO WOOD CONNECTOR. NEED TO
 SPECIFY WOOD TO MASONRY CONNECTOR FOR
 PROPOSED INSTALLATION. REVISE AS REQ'D.
  
 12- SHEET D-1: REVISE ORIGINAL DRAWING.
 HAND WRITTEN REVISIONS ARE NOT
 ACCEPTABLE.
 A) DELETE WINDOW MULLION DETAIL IF IT
 DOESN'T APPLY.
 B) TYPICAL 1 STORY SECTION: OVERHANG
 IS SHOWN INCORRECTLY. MISSING THE TRUSS
 LEG THAT ALLOWS PLACEMENT OF ATTIC
 VENTS. REVISE DETAIL AS REQUIRED.
 C) SHOW GRADE LEVEL TO VERIFY
 COMPLIANCE WITH R403.1.4 2004 RES. CODE.
 D) UPDATE ALL REFERENCE STANDARDS
 SPECIFIED IN THEGENERAL NOTES. SEE
 2004 RESIDENTIAL CODE CHAPTER 43 FOR
 PROPER REFERENCE STANDARDS AND EDITION
 THAT ARE ADOPTED BY THE CODE.
 E) NEW TYP. 1 STORY SECTION:
 * PROVIDE THIS INFORMATION ON ORIGINAL
 DRAWING.
 ** CLARIFY ATTIC VENTILATION. IS IT 4"
 VENTS OR 6"X22" VENTS. IF IT'S 4", THEN
 IS IT CONTINUOUS OR NOT?. IF IS 6"X22"
 VENTS, THEN SPECIFY LOCATION. "NO LESS
 THAN 1:150 IS NOT ENOUGH INFORMATION.
 *** WHERE IS THE UPLIFT TABLE?.
  
  
 13- PLEASE RETURN REVIEWED SET AFTER
 CORECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS TO EXPEDITE REVIEW PROCESS.
 THIS WAS NOT DONE ON FIRST RE-SUBMITTAL.
 PROVIDING THIS SET REALLY EXPEDITES THE
 REVIEW TIME.
  
 14- A) PROVIDE SURVEY SHOWING NEW HOUSE
 FOOTPRINT AND SETBACKS. THIS WILL ALSO
 TAKE CARE OF ZONING COMMENTS.
 B) PROVIDE SURVEY WITH ORIGINAL SEAL
 AND SIGNATURE AS REQUIRED BY CHAPTER 472
 OF FLORIDA STATUTES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-17 Cont ID  
Sent By jgomez Date 2006-03-17 Time 17:12 Rev Time 3.00
Received By jgomez Date 2006-03-17 Time 16:57 Sent To  
Notes
2006-03-17 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- PROVIDE BATHROOM WITH DOOR THAT
 ALLOWS 29" MIN. CLEAR OPENING. SECTION
 R322 2004 RESIDENTIAL CODE.
  
 3- SPECIFY ATTIC ACCESS AND LOCATION.
 SEC. R807 2004 RESIDENTIAL CODE.
  
 4- PROVIDE DRAINAGE PLAN AS REQUIRED BY
 SEC. R401.3 2004 RESIDENTIAL CODE.
  
 5- RULE 9B-72 OF DCA REQUIRES FLORIDA OR
 LOCAL PRODUCT APPROVAL FOR:
 A) PRECAST LINTELS.
 B) TRUSS ANCHORS AND ALL STRUCTURAL
 CONNECTORS SPECIFIED IN PLANS. SEE PLANS
 C) ROOF SHINGLES.
 D) SLIDING GLASS DOORS.
 E) ENTRY DOOR.
 F) DOOR AT KITCHEN/CARPORT AREA.
 G) SINGLE HUNG WINDOWS.
  
 ***NOTE:
 DADE COUNTY NOA'S ALONE ARE NOT
 AUTOMATICALLY STATEWIDE FLORIDA PRODUCT
 APPROVALS. GO TO THE DCA FLORIDA WEBSITE
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD
 APPROVED FLORIDA PRODUCT APPROVALS.
 OTHERWISE, MANUFACTURER TO APPLY FOR
 LOCAL PRODUCT APPROVALS.
  
 6- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING (OR USE STANDARD
 REVIEW STAMP) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS
 TO FBC 2004.
  
 7- DRAWINGS WERE STAMPED FOR IMPACT FEES
 ON 12-07-05. PERMIT APPLICATION WAS
 SUBMITTED ON 2-15-06. PLANS TO BE
 RE-STAMPED BY PALM BEACH COUNTY TO
 VERIFY THAT NO ADDITIONAL FEES ARE DUE
 SINCE IMPACT FEES CHANGED AFTER JANUARY
 13,2006.
  
 8- OWES $710.28 FOR UPDATED VALUATION
 AND RADON FEES.
  
 9- REVISE INFORMATION IN THE ENERGY
 CALCULATIONS: A) PERMITTING OFFICE IS
 CITY OF WEST PALM BEACH, NOT PALM BEACH
 COUNTY.
 B) JURISDICTION NUMBER IS 604700, NOT
 601000.
  
 10- PROVIDE 2 SIGNED AND SEALED COPIES
 OF THE SOIL TEST REPORT. ONLY ONE
 SUBMITTED.
  
 11- STORM SHUTTERS: A) PROVIDE FLORIDA
 OR LOCAL PRODUCT APPROVAL FOR STORM
 SHUTTERS TO BE USED.
 B) PROVIDE KEY PLAN.
 C) PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE, WHICH HAS
 ALL INFORMATION REQ'D FOR PLAN REVIEW.
  
 12- SHEET A-2, S-1: A) UPDATE ALL
 INFORMATION ON EMERGENCY EGRESS WINDOWS
 NOTES. SEE 2004 RESIDENTIAL CODE AND
 COMMENTS ON PLANS.
 B) GENERAL NOTES: SPECIFY CURRENT
 FLORIDA BUILDING CODE FOR WHICH BUILDING
 WAS DESIGNED. "AS ADOPTED BY THE COUNTY"
 IS NOT AN SPECIFIC CODE.
 C) DETAIL F1: SHOW GRADE LEVEL TO
 VERIFY COMPLIANCE WITH SEC. R403.1.4
 2004 RESIDENTIAL CODE.
 D) FOUNDATION PLAN: SHOW DROP FROM
 MAIN CONCRETE SLAB TO THE CARPORT AT
 ENTRY DOOR AND KITCHEN DOOR. ALSO AT
 SLIDING GLASS DOORS. SEE PLAN.
 E) SPECIFY CONCRETE SLAB JOINTS OR
 SPECIFY SUPPORTS SPACING FOR WWM AS
 REQUIRED BY SEC. R506.2.4 EXCEPTION #2
 OF 2004 RESIDENTIAL CODE.
 F) DELETE MECHANICAL NOTE IF IT
 DOESN'T APPLY TO THIS PROJECT.
 G) UPDATE REFERENCE INFORMATION FOR
 OPENINGS. SEE 2004 RESIDENTIAL CODE AND
 COMMENTS ON PLANS.
  
 13- SHEET S-2: A) TRUSS ANCHOR SCHEDULE:
 REVISE TYPO. CORRECT CONNECTOR IS TAPL16
 NOT TALP16.
 B) REVISE NUMBER OF FASTENERS
 SPECIFIED FORTAPL16. SEE CATALOGUE.
 OTHERWISE, PROVIDE COMPLETE ENGINEERING
 CALCULATIONS FOR TYPE AND NUMBER OF
 FASTENERS THAT DIFFER FROM THOSE TESTED
 AND PUBLISHED BY THE MANUFACTURER. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 C) CONNECTOR A5 IS A WOOD TO WOOD
 CONNECTOR. NEED TO SPECIFY WOOD TO
 MASONRY CONNECTOR. REVISE AS REQUIRED.
 D) SPECIFY WHERE DOES DETAIL F/A-6
 APPLIES TO?. OR DELETE DETAILS THAT
 DON'T APPLY TO THIS PROJECT.
 E) REVISE LENGTH FOR PRECAST LINTEL
 #2. SEE PLANS FOR CORRECT SPAN.
  
 14- SHEET D-1: A) DELETE WINDOW MULLION
 DETAIL IF IT DOESN'T APPLY.
 B) TYPICAL 1 STORY SECTION: OVERHANG
 IS SHOWN INCORRECTLY. MISSING THE TRUSS
 LEG THAT ALLOWS PLACEMENT OF ATTIC
 VENTS. REVISE DETAIL AS REQUIRED.
 B) SHOW GRADE LEVEL TO VERIFY
 COMPLIANCE WITH R403.1.4 2004 RES. CODE.
 C) UPDATE ALL REFERENCE STANDARDS
 SPECIFIED IN THEGENERAL NOTES. SEE
 2004 RESIDENTIAL CODE CHAPTER 43 FOR
 PROPER REFERENCE STANDARDS AND EDITION
 THAT ARE ADOPTED BY THE CODE.
  
 15- PLEASE RETURN REVIEWED SET AFTER
 CORECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS TO EXPEDITE REVIEW PROCESS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-03-09 Cont ID  
Sent By btrobaug Date 2007-03-09 Time 12:17 Rev Time 0.50
Received By btrobaug Date 2007-03-09 Time 12:01 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-02-27 Cont ID  
Sent By btrobaug Date 2007-02-27 Time 16:18 Rev Time 0.50
Received By btrobaug Date 2007-02-27 Time 16:08 Sent To PC
Notes
2007-02-27 16:09:33 
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 THE RISER INDICATE A METER/MAIN
 COMBINATION, THE PLAN INDICATES A METER,
 SEPARATE MAIN DISCONNECT, AND A PANEL IN
 THE RESIDENCE. PLEASE CORRELATE TO SHOW
 INTENDED INSTALLATION.
  
 THE RESUBMITTED PLAN IS A COPY WITH HAND DRAWN CHANGES
 WHICH IS UNACCEPTABLE FOR RECORD RETENTION PLEASE MAKE
 CHANGES ON A NEW SHEET,WITH DELETED ITEMS REMOVED,
 AND RESUBMIT FOR REVIEW. 106.1.3 FBC AS AMENDED
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-14 Cont ID  
Sent By btrobaug Date 2006-09-14 Time 08:02 Rev Time 0.50
Received By btrobaug Date 2006-09-14 Time 07:41 Sent To P
Notes
2006-09-14 00:00:00 
  
 PROVISO
  
 THIS PROVISO IS ISSUED TO FACILITATE THE
 BUILDING PROCESS, HOWEVER THE PLAN NEEDS
 TO BE CORRECTED AND REVISED PRIOR TO THE
 FIRST ELECTRICAL INSPECTIION. ALLOW AT
 LEAST ONE WEEK PER TRADE. CORRECT THE
 FOLLOWING.
  
 THE RISER INDICATE A METER/MAIN
 COMBINATION, THE PLAN INDICATES A METER,
 SEPARATE MAIN DISCONNECT, AND A PANEL IN
 THE RESIDENCE. PLEASE CORRELATE TO SHOW
 INTENDED INSTALLATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-08-02 Cont ID  
Sent By btrobaug Date 2006-08-02 Time 10:26 Rev Time 0.50
Received By btrobaug Date 2006-08-01 Time 07:28 Sent To M
Notes
2006-08-02 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} NOTE #1 REFERS TO "IAW" PLEASE NOTE
 THAT THE STATE OF FLORIDA HAS ADOPTED
 NFPA 70 OR THE NEC. IF REFERENCING
 ANOTHER CODE TO USE FOR WIRING
 COMPLIANCE, INDICATE WHERE IT IS
 REFERENCED AS REPLACING THE BUILDING
 CODE REFERENCES. ALSO PLEASE INFORM ME
 WHERE I CAN OBTAIN OR READ "IAW" CODES.
 OTHERWISE TAKE ALLREFERENCES TO SAME OFF
 THE DOCUMENTS.
  
 2} DUE TO THE METER LOCATION, A
 DISCONNECT IS REQUIRED PER 225.32.
 INDICATE LOCATION ON PLAN, AND ON THE
 RISER.
  
 3} CIRCUIT #14 NEEDS #12 WIRE IF A 20
 AMP BREAKER IS USED. 310.16.
  
 4} THE PANEL SCHEDULE INDICATES SEPARATE
 WASHER AND DRYER, THE PLAN HAS A
 COMBINATION UNIT, PLEASE CLARIFY.
  
 PLEASE SEE THAT THE APPLIANCE OUTLETS IN
 THE KITCHEN ARE NOT REQUIRED TO BE GFI,
 BUT MUST BE INSTALLED IF ON PLANS.
  
 5} RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A) (1) AND 210.52(A)(2). SEE
 REVIEWED PLAN.
  
 6} BATH ROOMS MUST HAVE RECEPTALES PER
 210.52(D).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-24 Cont ID  
Sent By btrobaug Date 2006-05-24 Time 17:30 Rev Time 0.50
Received By btrobaug Date 2006-05-24 Time 16:31 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-24 Cont ID  
Sent By dpalmer Date 2006-02-24 Time 07:17 Rev Time 0.00
Received By dpalmer Date 2006-02-24 Time 06:34 Sent To M
Notes
2006-02-24 00:00:00*********** UNSAT ************
  
 ** PLEASE KNOW, PLANS ARE NOT COMPLETE
 AT THIS TIME. PLEASE ALSO SEE NUMEROUS
 ELECTRICAL CODE COMPLIANCE NOTES BELOW.
  
  
 1)NOTE: PLEASE SUBMIT AN ELECTRICAL
 RISER DIAGRAM FOR CODE COMPLIANCE,
 SEC'S, AWG'S, GROUNDING ELECTRODE SYSTEM
 ETC ETC
 215.5
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. SHALL BE 20A AND #12 AWG. PER
 210.52D, 210.11C3
  
 4)NOTE: PLEASE SEE BATH RMS MISSING THE
 REQUIRED GFI RECEPT WITHIN 3' OF LAV'S.
 210.52D, 210.8A
  
 5)NOTE: PLEASE SEE MISSING COUNTERSPACE
 GFI'S PER 210.52C1
 PLEASE ALSO SEE WHAT APPEARS TO GFI'S
 BEHIND THE SINK? IF THESE ARE FOR A DISH
 OR DISPOSAL, THEY ARE NOT REQUIED TO BE
 GFI AND SHOULD BE NOTED FOR PURPOSE AND
 LOCATION.
  
 6)NOTE: PLEASE SEE MISSING DISCONNECT
 REQUIRED FOR HWH. 422.31
  
 7)NOTE: PLEASE VERIFY PLANS SHOWS
 STACKABLE WASHRE/DRYER HOWEVER PANEL
 SCHEDULE DOES NOT INDICATE THIS?
 215.5
  
 8)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 SIZE. SHOWS 150 AND 200A'S??
 215.5
  
 9)NOTE: PLEASE SEE MISSING DISCONNECTS
 FOR BOTH THE AHU AND CU. 440.11.
 PLANS APPEAR TO SHOW RECEPTS FOR EACH??
 PLUG IN TYPE UNITS ARE NOT PERMITTED.
 422.31 ETC
  
 10)NOTE: PLEASE LIST "ALL" THE REQUIRED
 ARC FAULT PROTECTED CIRCUIT. PLEASE SEE
 THE FOLLOWING NOTE. PLEASE ALSO SEE
 NOTES ON ELECTRICAL PLANS MENTIONS TO
 CIRCUIT THE SD'S TO THE KITCHEN OR BATH
 LT CIRCUIT? THIS IS OK, HOWEVER IF THE
 SD'S ARE CIRCUITED TO EITHER OFTHESE,
 THEN THEY WOULD BE REQUIRED TO BE AFCI
 PROTECTED CIRCUITS AND SHOULD ALSO BE
 LISTED.
 210.12
  
 11)NOTE: PLEASE SEE PLANS ONLY SEEM TO
 INDICATE ONE ARC FAULT CIRCUIT AND THIS
 IS ALSO SHOWN AS THE ONLY CIRCUIT FOR
 ALL THREE BEDRMS FOR LTS, SD'S FANS, AND
 RECEPTS?? PLEASE SEE 240.4,310.16 ETC AS
 AS SHOWN THIS ONE CIRCUIT WOULD BE
 OVERLOADED.
 215.5
  
 12)NOTE: PLEASE SEE MANY LOCATIONS FOR
 MISSING RECEPTS PER 210.52
  
 13)NOTE: PLEASE SEE MISSING EGRESS LTS,
 CONTROL ETC PER 210.70, LS 101 7.8 ETC
 ALL LOCATIONS ON PLANS.
  
 14)NOTE: PLEASE SEE ALL CIRCUITING ON
 PANEL SCHEDULE SHOWS ALL CIRCUITS AS
 "2-POLE" WHICH INDICATES ALL AS 240V?
 PLEASE CORRECT.
 215.5
  
 15)NOTE: PLEASE BE SURE PLANS REFERENCE
 THE CURRENT CODE. (2002 NEC ).
  
 16)NOTE: PLEASE SEE THE BLDG REVIEW
 COMMENTS AS THE VALUE OF $60K IS WAY
 LOAW FOR VALUATION OF BUILDING THIS NEW
 3/2. FBC 108.3
  
 17)NOTE: PLEASE SEE PLANS ALSO REFERENCE
 THE 2001 FBC, WHEN AS OF OCT 1ST, 2005
 THE STATE OF FLORIDA ADOPTED THE 2004
 FBC.
 PLEASE ADJUST PLANS.
  
 18)NOTE: PLEASE ALSO SEE BLDG REVIEW
 NOTES, AS ONLY PERMIT APPLICATIONS
 SUBMIITTED BEFORE JAN 13, 2006 FALL
 UNDER THE OLD PALM BEACH COUNTY IMAPCT
 FEES, PLEASE KNOW, PLANS WILL BE
 REQUIRED TO GO BACK TO PBC TO BE
 REVIEWED AND RE-STAMPED AS PLANS WERE
 NOT SUBMITTED UNTIL FEB 15, 2006.
  
 ** PLEASE KNOW, DUE TO THE EXTENT OF
 ELECTRICAL COMMENTS, THERE MAY BE
 FURTHER COMMENTS ONCE PLANS ARE
 COMPLETED.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-02-27 Cont ID  
Sent By adarroug Date 2007-02-27 Time 15:22 Rev Time 0.00
Received By adarroug Date 2007-02-27 Time 15:22 Sent To B
Notes
2007-02-27 15:22:36TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-02-27 Cont ID  
Sent By adarroug Date 2007-02-27 Time 15:22 Rev Time 0.00
Received By adarroug Date 2007-02-27 Time 15:21 Sent To E
Notes
2007-02-27 15:21:50TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-12-15 Cont ID  
Sent By adarroug Date 2006-12-15 Time 11:02 Rev Time 0.00
Received By adarroug Date 2006-12-15 Time 11:02 Sent To M
Notes
2006-12-15 11:02:55TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-10-18 Cont ID  
Sent By adarroug Date 2006-10-18 Time 09:12 Rev Time 0.00
Received By adarroug Date 2006-10-18 Time 09:12 Sent To B
Notes
2006-10-18 09:13:03TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 09:55 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 09:55 Sent To E
Notes
2006-09-08 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-01 Cont ID  
Sent By adarroug Date 2006-09-01 Time 16:29 Rev Time 0.00
Received By adarroug Date 2006-09-01 Time 16:29 Sent To Z
Notes
2006-09-01 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 12:44 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 12:44 Sent To E
Notes
2006-07-31 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-22 Cont ID  
Sent By adarroug Date 2006-07-22 Time 14:20 Rev Time 0.00
Received By adarroug Date 2006-07-22 Time 14:20 Sent To Z
Notes
2006-07-22 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-22 Cont ID  
Sent By adarroug Date 2006-05-22 Time 12:47 Rev Time 0.00
Received By adarroug Date 2006-05-22 Time 12:47 Sent To E
Notes
2006-05-22 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-05 Cont ID  
Sent By adarroug Date 2006-05-05 Time 11:34 Rev Time 0.00
Received By adarroug Date 2006-05-05 Time 11:34 Sent To E
Notes
2006-05-05 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-17 Cont ID  
Sent By jgomez Date 2006-03-17 Time 18:48 Rev Time 0.00
Received By jgomez Date 2006-02-17 Time 08:53 Sent To  
Notes
2006-02-17 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2006-12-27 Cont ID  
Sent By pkrauss Date 2006-12-27 Time 15:45 Rev Time 0.00
Received By pkrauss Date 2006-12-27 Time 15:36 Sent To  
Notes
2006-12-27 15:46:27MECHANICAL PLANS SUBMITTED AND REVIEWED UNDER THE
 MECHANICAL PERMIT

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2006-09-25 Cont ID  
Sent By lmartine Date 2006-09-25 Time 10:31 Rev Time 0.00
Received By lmartine Date 2006-09-25 Time 10:31 Sent To  
Notes
2006-09-25 00:00:00SEPARATE MECHANICAL PLANS AND PERMIT
 REQUIRED, SEE NOTARIZED LETTER
  
  
 OKLM

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-08-02 Cont ID  
Sent By tgordon Date 2006-08-02 Time 15:42 Rev Time 0.35
Received By tgordon Date 2006-08-02 Time 15:42 Sent To P
Notes
2006-08-02 00:00:00*** DENIED ***
 1) AS REQUESTED IN LAST TWO REVIEWS,
 SUPPLY AIR DUCT (FLEX) TO LIVING ROOM
 NEEDS TO BE SIZED.
  
 2) AS REQUESTED IN LAST TWO REVIEWS,
 SUPPLY AIR GRILL IN HALL (FOYER) NEEDS
 TO BE SIZED.
  
 3) SEE ATTACHED NOTICE FS 553.80(2)(B)
 FOUR TIMES THE FEE.
  
 4) SOME SUPPLY AIR DUCTS ARE SHOWING 2
 DIFFERENT SIZES FOR THEM (SEE HIGH
 LIGHTS ON MECHANICAL PLANS), PLEASE
 CORRECT.
  
 5) PLEASE EXPLAIN OR REMOVE 18"X30"
 SUPPLY AIR GRILL UNDER AIR HANDLER.
  
 6) PLEASE SUBMIT MANUAL D CALCULATIONS
 FOR RESIDENTIAL DUCT DESIGN, PER 2004
 FBC/R M1601.1 AND FBC 13-610.1.ABC.1,
 (AS MOST SUPPLY AIR DUCTS ARE SIZED AT
 9") (SEE ATTACHED MANUAL D COVER SHEET).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-06-05 Cont ID  
Sent By tgordon Date 2006-06-05 Time 10:56 Rev Time 0.30
Received By tgordon Date 2006-06-05 Time 10:56 Sent To B
Notes
2006-06-05 00:00:00*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 2-27-06
 NOTE #2, MOST SUPPLY AIR DUCTS (FLEX)
 ARE NOT SIZED PLEASE CORRECT. SEE
 KITCHEN, LIVING ROOM, MASTER BEDROOM,
 MASTER BATHROOM, BEDROOM 2,FOYER.
  
 2) AS REQUESTED IN LAST REVIEW 2-27-06
 NOTE #3, SUPPLY AIR GRILL IN HALL NEEDS
 TO BE SIZED. SEE FOYER.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-27 Cont ID  
Sent By tgordon Date 2006-02-27 Time 16:30 Rev Time 0.30
Received By tgordon Date 2006-02-27 Time 16:30 Sent To B
Notes
2006-02-27 00:00:00*** DENIED ***
 1) IS AHU IN A CLOSET OR IN THE ATTIC?
 AHU MOUNTING DETAIL ON MECH. PLAN SHOWS
 AS A CLOSET, PLEASE NOTE ON MECH. PLAN.
  
 2) MOST SUPPLY AIR DUCTS (FLEX) ARE NOT
 SIZED PLEASE CORRECT.
  
 3) SUPPLY AIR GRILL IN HALL NEEDS TO BE
 SIZED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-08-09 Cont ID  
Sent By jleech Date 2006-08-09 Time 07:11 Rev Time 0.00
Received By jleech Date 2006-08-09 Time 07:11 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-06-02 Cont ID  
Sent By jleech Date 2006-06-02 Time 14:39 Rev Time 0.00
Received By jleech Date 2006-06-02 Time 14:39 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-02-27 Cont ID  
Sent By jleech Date 2006-02-27 Time 08:14 Rev Time 0.00
Received By jleech Date 2006-02-27 Time 08:14 Sent To M
Notes
2006-02-27 00:00:00DENIED;
 1.RISER DIAGRAM DOES NOT MATCH FLOOR
 PLAN .
 2.KITCHEN SINK MISSING FROM RISER
 DIAGRAM.
 3.RISER DIAGRAM NOT DRAWN PROPERLY. USE
 30 60 TRIANGLE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2006-09-05 Cont ID  
Sent By mmclean Date 2006-09-05 Time 14:37 Rev Time 0.00
Received By mmclean Date 2006-09-05 Time 14:37 Sent To I
Notes
2006-09-05 00:00:00NOTE:SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.

Review Stop Z ZONING
Rev No 3 Status F Date 2006-07-29 Cont ID  
Sent By mmclean Date 2006-07-29 Time 09:37 Rev Time 0.00
Received By mmclean Date 2006-07-29 Time 09:37 Sent To I
Notes
2006-07-29 00:00:00DENIED, 2ND REQUST:
 1. THE PROPOSED DRIVEWAY HAS EXCEED THE
 ZONING REQUIRMENTS FOR LANDSCAPE WITHIN
 THE FIRST 25FT FRONT SETBACK.
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
 3. CAN ONLY HAVE A 10FT WIDE DRIVEWAY TO
 MAINTAIN THE 75% OF LANDSCAPE.
  
  
 NOTE:
 THE PROPOSED A/C EQUIPMENT SHALL NOT BE
 CLOSER THAN 1FT FROMSIDE PROPERTY
 LINE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2006-05-19 Cont ID  
Sent By mmclean Date 2006-05-19 Time 11:27 Rev Time 0.00
Received By mmclean Date 2006-05-19 Time 11:27 Sent To I
Notes
2006-05-19 00:00:00DENIED,
 1. NEED TO IDENTIFY THE PROPERTY LINE
 (AS SHOWN ON SURVEY) AND IDENTIFY THE
 FRONT SETBACK CLEARLY.
 2. THE PROPOSED DRIVEWAY HAS EXCEED THE
 ZONING REQUIRMENTS FOR LANDSCAPE WITHIN
 THE FIRST 25FT FRONT SETBACK.
 NOTE:
 MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
 3. CAN ONLY HAVE A 10FT WIDE DRIVEWAY TO
 MAINTAIN THE 75% OF LANDSCAPE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-02-23 Cont ID  
Sent By mmclean Date 2006-02-23 Time 13:21 Rev Time 0.00
Received By mmclean Date 2006-02-23 Time 13:21 Sent To  
Notes
2006-02-23 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF CURRENT
 SURVEY WITH SETBACKS OF THE PROPOSED
 STRUCTURE
 2. MUST PROVIDE THE DIMENSION OF
 PROPOSED DRIVEWAY/WALKWAY (LENGTH &
 WIDTH)
 3. THE SETBACK FOR SF11
 A. FRONT: 20FT OR 20% OF LOT DEPTH
 (18FT), WHICHEVER IS LESS
 B. REAR:TEN FT OR 10% OF LOT DEPTH,
 WHICHEVER IS LESS
 C. SIDE: FIVE FEET MINIMUM, 10FT TOTAL
 4. SITEPLAN/LANDSCAPE PLANS HAS
 INSUFFICENT INFORMATION FOR COMPLETION
 OF REVIEW.
  
 MICHELLE MCLEAN
 ZONING TECHICIAN
 805-6720