Plan Review Details - Permit 06020621
Plan Review Stops For Permit 06020621
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-02 Cont ID  
Sent By tgordon Date 2006-03-02 Time 10:38 Rev Time 0.00
Received By tgordon Date 2006-02-16 Time 12:09 Sent To  
Notes
2006-02-16 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-03-02 Cont ID  
Sent By tgordon Date 2006-03-02 Time 10:35 Rev Time 0.15
Received By tgordon Date 2006-03-02 Time 10:35 Sent To  
Notes
2006-03-02 00:00:00CORRECTIONS MADE TO PLANS. DUE TO
 CONDITIONS OF HOUSE RETURNS CAN NOT BE
 IN EACH BEDROOM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-16 Cont ID  
Sent By tgordon Date 2006-02-16 Time 15:34 Rev Time 0.30
Received By tgordon Date 2006-02-16 Time 15:34 Sent To  
Notes
2006-02-16 00:00:00*** DENIED ***
 1) NEED TO PROVIDE RETURN AIR TO
 BEDROOMS AND DEN.BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 2) MUST SHOW THE RETURN AIR GRILL TO AHU
 AND SIZE OF GRILL.
  
 3) DUCT (FLEX) GOING TO TRIANGLE IS NOT
 SIZED, AND APPEARS TO BE GOING TO THE
 GRILL IN THE BATHROOM, PLEASE CORRECT.
  
 4) PLANS MUST HAVE ON THEM JOB ADDRESS,
 COMPANY ADDRESS, CO. PHONE NUMBER, SND
 CO. LIC. NUMBER. SEE NOTE #5.
  
 5)ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 6) PLEASE USSE LARGE ENOUGH PAPER SO WE
 MAY PUT CITY STAMPS AND COMMENTS ON
 THEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.