Plan Review Details - Permit 06020532
Plan Review Stops For Permit 06020532
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-04-10 Cont ID  
Sent By alange Date 2006-04-10 Time 14:12 Rev Time 0.50
Received By alange Date 2006-04-10 Time 14:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-03-15 Cont ID  
Sent By alange Date 2006-03-15 Time 09:39 Rev Time 0.50
Received By alange Date 2006-03-15 Time 09:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-04-06 Cont ID  
Sent By jleahy Date 2006-04-06 Time 10:33 Rev Time 0.45
Received By jleahy Date 2006-04-06 Time 10:33 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-01 Cont ID  
Sent By btrobaug Date 2006-03-01 Time 16:11 Rev Time 0.50
Received By btrobaug Date 2006-03-01 Time 15:45 Sent To M
Notes
2006-03-01 00:00:00 
 PLEASE PROVIDE A SITE DRAWING WITH ALL
 EQUIPMENT SHOWN AT THEIR INTENDED
 LOCATIONS SO THAT DISCONNECT GROUPING
 CAN BE REVIEWED OER 225.33.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-03-06 Cont ID  
Sent By mperson Date 2006-03-06 Time 15:54 Rev Time 0.15
Received By mperson Date 2006-03-06 Time 15:54 Sent To B
Notes
2006-03-06 00:00:00SEE GAS APPLICATION # 06020688

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-03 Cont ID  
Sent By adarroug Date 2006-04-03 Time 15:23 Rev Time 0.00
Received By adarroug Date 2006-04-03 Time 15:23 Sent To E
Notes
2006-04-03 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-17 Cont ID  
Sent By adarroug Date 2006-03-17 Time 16:47 Rev Time 0.00
Received By adarroug Date 2006-03-17 Time 16:47 Sent To Z
Notes
2006-03-17 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-23 Cont ID  
Sent By adarroug Date 2006-02-23 Time 10:38 Rev Time 0.00
Received By adarroug Date 2006-02-23 Time 10:38 Sent To E
Notes
2006-02-23 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-15 Cont ID  
Sent By alange Date 2006-03-15 Time 09:39 Rev Time 0.00
Received By alange Date 2006-02-14 Time 15:47 Sent To  
Notes
2006-02-14 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-04-07 Cont ID  
Sent By tgordon Date 2006-04-07 Time 09:04 Rev Time 0.20
Received By tgordon Date 2006-04-07 Time 09:04 Sent To P
Notes
2006-04-07 00:00:00*** PROVISO ***
 1)GENERATOR EXHUST MUST BE TEN FEET AWAY
 FROM ANY BUILDING OPENINGS (WINDOWS,
 DOORS, ROOF & EAVE VENTS), AND TEN FEET
 AWAY FROM ADJECENT BUILDING OPENS. PER
 2004 FBC/M 401.5.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-03-02 Cont ID  
Sent By tgordon Date 2006-03-02 Time 11:46 Rev Time 0.15
Received By tgordon Date 2006-03-02 Time 11:46 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-03-06 Cont ID  
Sent By mperson Date 2006-03-06 Time 15:53 Rev Time 0.00
Received By mperson Date 2006-03-06 Time 15:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-04-02 Cont ID  
Sent By mmclean Date 2006-04-02 Time 17:50 Rev Time 0.00
Received By mmclean Date 2006-04-02 Time 17:50 Sent To I
Notes
2006-04-02 00:00:00GENERATOR CAN ONLY ENCROACH 4FT INTO A
 SETBACK.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-02-22 Cont ID  
Sent By mmclean Date 2006-02-22 Time 16:41 Rev Time 0.00
Received By mmclean Date 2006-02-22 Time 16:41 Sent To I
Notes
2006-02-22 00:00:00DENIED,
 1. MUST PROVIDE THE DIMENSION OF THE
 PROPOSED GENERATOR
 2. MUST PROVIDE THE SETBACK OF THE
 GENERATOR FROM PROPERTY LINE &
 STRUCTURE.
  
 NOTE: GENERATOR CAN ONLY ENCROACH 4FT
 INTO A SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
 2/22/06 PLANS GIVEN TO ADRIANNA
 MCKENZIE, SURPERVISOR.
 2/22/06PLANS RETURNED TO INCOMING FOR
 FURTHER PROCESSING.