Plan Review Details - Permit 06020459
Plan Review Stops For Permit 06020459
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-03-13 Cont ID  
Sent By alange Date 2006-03-13 Time 11:09 Rev Time 0.33
Received By alange Date 2006-03-13 Time 11:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-04-03 Cont ID  
Sent By jleahy Date 2006-04-03 Time 14:02 Rev Time 0.45
Received By jleahy Date 2006-04-03 Time 14:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-01 Cont ID  
Sent By btrobaug Date 2006-03-01 Time 14:21 Rev Time 0.50
Received By btrobaug Date 2006-03-01 Time 14:11 Sent To M
Notes
2006-03-01 00:00:00 
 PROVIDE A LOAD CALCULATION FOR THE
 INTENDED GENERATOR LOAD AND SHOW
 CIRCUITS SERVED.
 702.5 CAPACITY AND RATING.
 AN OPTIONAL STANDBY SYSTEM SHALL HAVE
 ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE
 OPERATED AT ONE TIME. OPTIONAL STANDBY
 SYSTEM EQUIPMENT SHALL BE SUITABLE FOR
 THE MAXIMUM AVAILABLE FAULT CURRENT AT
 ITS TERMINALS. THE USER OF THE OPTIONAL
 STANDBY SYSTEM SHALL BE PERMITTED TO
 SELECT THE LOAD CONNECTED TO THE SYSTEM.
  
 SUBMIT MANUFACTURERS SPECIFICATIONS FOR
 THE TRANSFER SWITCH.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-03-06 Cont ID  
Sent By mperson Date 2006-03-06 Time 15:25 Rev Time 0.15
Received By mperson Date 2006-03-06 Time 15:25 Sent To B
Notes
2006-03-06 00:00:00NOTE: GAS PERMIT REQUIRED. GAS
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT
 APPLICATION. ALL GAS INSPECTIONS TO BE
 COMPLETE BEFORE FINAL RES-GEN INSPECTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-25 Cont ID  
Sent By adarroug Date 2006-02-25 Time 11:57 Rev Time 0.00
Received By adarroug Date 2006-02-25 Time 11:57 Sent To E
Notes
2006-02-25 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-13 Cont ID  
Sent By alange Date 2006-03-13 Time 11:10 Rev Time 0.00
Received By alange Date 2006-02-13 Time 17:25 Sent To  
Notes
2006-02-13 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-03-02 Cont ID  
Sent By tgordon Date 2006-03-02 Time 11:41 Rev Time 0.15
Received By tgordon Date 2006-03-02 Time 11:41 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-03-06 Cont ID  
Sent By mperson Date 2006-03-06 Time 15:24 Rev Time 0.00
Received By mperson Date 2006-03-06 Time 15:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-02-24 Cont ID  
Sent By mmclean Date 2006-02-24 Time 11:25 Rev Time 0.00
Received By mmclean Date 2006-02-24 Time 11:25 Sent To I
Notes
***NONE***