Plan Review Details - Permit 06020403
Plan Review Stops For Permit 06020403 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2006-04-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-04-20 |
Time |
15:08 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-04-20 |
Time |
15:08 |
Sent To |
Z |
|
Notes |
2006-04-20 00:00:00 | PROVISO | | REVISE LIGHT POLE CALCS | | SEP PERMITS PIER, PAVILION |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-04-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-04-17 |
Time |
15:18 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-04-17 |
Time |
15:18 |
Sent To |
|
|
Notes |
2006-04-17 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | NOTE - NEW PLAN SUBMITTED FOR THE | | PAVILION | | | | 1.)THE LIGHT POLE CALCULATIONS REFER | | TO ASCE7-95.CORRECT REFERENCE IS | | ASCE7-02, FBC35. | | | | 2.)THE SEAL FOR AF WEBBER PE IS NOT | | LEGIBLE.THE SEAL IS TO BE DATED, | | FAC61G15-23.002. | | | | 3.)THE SEAL FOR AF WEBBER PE IS | | EXPIRED.IT SHOULD STATE "LICENSE" | | RATHER THAN "CERTIFICATE" | | FAC61G15-23.002 EFFECTIVE JAN. 1, 2006. | | | | 4.)AS NOTED IN PREVIOUS REVIEW, THE | | PIER, PLAY AREA, ACCESSIBLE PARKING, | | WILL REQUIRE SEPARATE PERMITS. | | | | 5.)CERTIFICATE OF AUTHORIZATION | | REQUIRED FOR BUD DESIGN & ENGINEERING | | SERVICES, INC.FAC61G15-23.002. | | | | 6.)SEE PREVIOUS LIST.THE LANDSCAPE | | ARCHITECT HAS SEALED THE NEW SHEETS BUT | | ON LM1 THE SEAL IS STILL ILLEGIBLE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-03-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-03-22 |
Time |
12:02 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-03-22 |
Time |
12:02 |
Sent To |
|
|
Notes |
2006-03-22 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | 1.)NO INFORMATION WAS PROVIDED FOR THE | | PIER, PLAY AREA, EXERCISE EQUIPMENT, | | ACCESSIBLE PARKING AND THE PAVILION. | | SEPARATE PERMITS REQUIRED. | | | | 2.)SEE ATTACHED INFORMATION REGARDING | | TITLE II, ADAAG AND GUIDELINES FOR | | DESIGN.ADDITIONAL INFORMATION IS | | AVAILABLE FROM THE ACCESS BOARD.NOTE | | THAT THESE GUIDELINES ARE NOT | | REQUIREMENTS.FROM ADA WEBSITE - "THE | | ABSENCE OF SPECIFIC PROVISIONS IN THE | | CURRENT STANDARDS DOES NOT MEAN THAT | | FACILITIES OR PLAY AREAS ARE EXEMPT FROM | | THE PROVISION OF ACCESS; RATHER, IT | | MEANS FACILITIES AND AREAS ARE NOT HELD | | TO A SPECIFIC LEVEL OF ACCESS UNDER THE | | CURRENT STANDARD."THE OWNER AND | | DESIGNER ARE TO DETERMINE LEVEL OF | | ACCESS. | | | | 3.)ALL ELEMENTS ARE TO BE ON AN | | ACCESSIBLE ROUTE.NONE IS SHOWN FOR THE | | DOG PARK AREA, PLAY AREA, VOLLEYBALL | | COURT. | | | | 4.)THE LANDSCAPE ARCHITECT'S SEAL IS | | TO BE LEGIBLE, FS481.306. | | | | 5.)NOTE THAT A PORTION OF THIS LOT | | APPEARS TO BE IN A HIGH HAZARD FLOOD | | ZONE. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2006-04-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-04-14 |
Time |
07:23 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-04-14 |
Time |
06:59 |
Sent To |
|
|
Notes |
2006-04-14 00:00:00 | ************ REDLINED ************ | | | | | | 1) PLEASE SEE THE "EQUIPMENT GROUNDING | | CONDUCTOR" IS STILL BEING SHOWN FROM | | METER TO THE FIRST MEANS OF DISCONNECT. | | RESPONSE LTR FROM ENGINEER, MENTIONED | | THIS WAS REMOVED PER NOTES, HOWEVER THIS | | IS SHOWN ON RISER ON ALL THREE SETS. | | PLEASE SEE 250.6, 250.24B, THE "EQUIP | | GRNDING" IS ONLY INSTALLED AFTER THE | | FIRST MEANS OF DISC. | | | | | | 2) PLEASE SEE THE PLANS NOW INDICATE A | | STRUCTURE WITH LT, THIS STRUCTURE WILL | | BE REQUIRED TO HAVE A MEANS OF DISC FOR | | LT AND ANY ELECTRICAL TO THIS STRUCTURE. | | THIS CAN BE A TOGGLE SW AND CAN BE | | LOCATED HIGHER ON STRUCTURE TO | | ALLEAVITATE INADVERTANT SWITCHING OF LT. | | 225.31 | | | | ** PLEASE KNOW, THE ABOVE WERE REDLINED | | ON PLANS AND THERE IS NO NEED FOR | | CORRECTIONS AT THIS TIME. | | ** PLEASE REVISE IF PLANS COME BACK OR | | ARE REVISED FOR ANY OTHER ELECTRICAL. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-03-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-03-14 |
Time |
17:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-03-14 |
Time |
12:58 |
Sent To |
|
|
Notes |
2006-03-14 00:00:00 | ****** UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE AN "EQUIPMENT | | GROUNDING CONDUCTOR" IS NOT INSTALLED | | UNTIL AFTER THE FIRST MEANS OF | | DISCONNECT. PLEASE SEE 250.6 THE | | GROUNDING OF ELECTRICAL SYSTEMS, CIRCUIT | | CONDUCTORS, SURGE ARRESTERS, AND | | CONDUCTIVE NON?CURRENT-CARRYING | | MATERIALS AND EQUIPMENT SHALL BE | | INSTALLED AND ARRANGED IN A MANNER THAT | | WILL PREVENT OBJECTIONABLE CURRENT OVER | | THE GROUNDING CONDUCTORS OR GROUNDING | | PATHS. | | | | 2)NOTE: PLEASE SEE PANEL SCHEDULE AND | | CONDUCTORS FOR SERVICESEEM TO INDICATE | | THAT THE SERVICE WILL BE A SINGLE PHASE | | INSTALLATION. PLEASE SEE ONLY THREE | | CONDUCTORS ARE COMING FROM METER TO MCB | | PANEL, YET LOAD CALCULATIONS MENTIONS | | THE SERVICE BEING 120/208V 3-PHASE. | | PLEASE SEE LOAD CALCUALTIONS ARE DONE TO | | SINGLE PHASE?? | | PLEASE CORRELATE ALL OF THE ABOVE. | | 215.5. IF 3-PHASE, PLEASE ADJUST CALCS | | AND CONDUCTORS. | | | | 3)NOTE: PLEASE SEE PLANS MENTIONS NEW | | CEILING LT, HOWEVER NO CEILING OR | | STRUCTURE COULD B E LOCATED. | | | | 4)NOTE: PLEASE SUBMIT SIGNED,DATED AND | | SEALED ENGINEERED WIND LOAD CALCULATIONS | | FOR POLES WITH LT FIXTURES. THESE ARE | | REQUIRED AT THIS TIME AND WILL BE | | REVIEWED BY THE STRUCTUAL PLANS | | REVIEWER. PLEASE SEE MIN NDESIGN SHALL | | MEET FBC 2004 140MPH. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-04-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-04-13 |
Time |
16:57 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-04-13 |
Time |
16:57 |
Sent To |
|
|
Notes |
2006-04-13 00:00:00 | TO "COMM" BD#26 --EXPIDITED PERMIT-- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-03-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-03-22 |
Time |
12:23 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-02-10 |
Time |
13:41 |
Sent To |
|
|
Notes |
2006-03-15 00:00:00 | EXPEDITE PLAN REVIEW PER ROBERT BROWN. | | | | | 2006-03-13 00:00:00 | TO "COMM" BD#3 | 2006-02-10 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2006-04-15 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-04-15 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-04-15 |
Time |
16:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2006-03-16 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-03-16 |
Time |
17:14 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-03-16 |
Time |
17:14 |
Sent To |
|
|
Notes |
2006-03-16 00:00:00 | PAUL SCHMITZ | | [email protected] | | FBC 2004 PLUMBING CODE PLAN REVIEW | | AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | DENIED | | 1) SHT L3IRRIGATION | | IF THE DESIGN PROFESSIONAL IS AN | | ARCHITECT OR ENGINEER LEGALLY REGISTERED | | UNDER THE LAWS OF THIS STATE REGULATING | | THE PRACTICE OF ARCHITECTURE AS PROVIDED | | FOR IN CHAPTER 481, FLORIDA STATUTES, | | PART I, OR ENGINEERING AS PROVIDED FOR | | IN CHAPTER 471, FLORIDA STATUTES, THEN | | HE OR SHE SHALL AFFIX HIS OR HER | | OFFICIAL SEAL, SIGNATURE AND DATE TO | | SAID DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA, AS REQUIRED BY | | FLORIDA STATUTE. IF THE DESIGN | | PROFESSIONAL IS A LANDSCAPE ARCHITECT | | REGISTERED UNDER THE LAWS OF THIS STATE | | REGULATING THE PRACTICE OF LANDSCAPE | | ARCHITECTURE AS PROVIDED FOR IN CHAPTER | | 481, FLORIDA STATUTES, PART II, THEN HE | | OR SHE SHALL AFFIX HIS OR HER SEAL, | | SIGNATURE AND DATE TO SAID DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA AS | | DEFINED IN SECTION | | 481.303(6)(A)(B)(C)(D), FS. | | | | 2) SHT L3 LOCAL ORDINANCE #2583-95 | | BACK FLOW PREVENTER REQUIRED ON THE | | WATER SERVICE TO THE IRRIGATION SYSTEM. | | | | END OF COMMENTS, QUESTIONS 561-805-6692 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2006-04-21 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2006-04-21 |
Time |
07:24 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2006-04-21 |
Time |
07:24 |
Sent To |
B |
|
Notes |
2006-04-21 00:00:00 | RE-STAMP OF PLANS. | | | | GIVEN TO JENNIFER PER SAMANTHA HILL |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2006-03-16 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2006-03-16 |
Time |
08:47 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2006-03-16 |
Time |
08:47 |
Sent To |
|
|
Notes |
|
|
|