Plan Review Details - Permit 06020403
Plan Review Stops For Permit 06020403
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-04-20 Cont ID  
Sent By shill Date 2006-04-20 Time 15:08 Rev Time 0.00
Received By shill Date 2006-04-20 Time 15:08 Sent To Z
Notes
2006-04-20 00:00:00PROVISO
 REVISE LIGHT POLE CALCS
 SEP PERMITS PIER, PAVILION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-17 Cont ID  
Sent By shill Date 2006-04-17 Time 15:18 Rev Time 0.00
Received By shill Date 2006-04-17 Time 15:18 Sent To  
Notes
2006-04-17 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 NOTE - NEW PLAN SUBMITTED FOR THE
 PAVILION
  
 1.)THE LIGHT POLE CALCULATIONS REFER
 TO ASCE7-95.CORRECT REFERENCE IS
 ASCE7-02, FBC35.
  
 2.)THE SEAL FOR AF WEBBER PE IS NOT
 LEGIBLE.THE SEAL IS TO BE DATED,
 FAC61G15-23.002.
  
 3.)THE SEAL FOR AF WEBBER PE IS
 EXPIRED.IT SHOULD STATE "LICENSE"
 RATHER THAN "CERTIFICATE"
 FAC61G15-23.002 EFFECTIVE JAN. 1, 2006.
  
 4.)AS NOTED IN PREVIOUS REVIEW, THE
 PIER, PLAY AREA, ACCESSIBLE PARKING,
 WILL REQUIRE SEPARATE PERMITS.
  
 5.)CERTIFICATE OF AUTHORIZATION
 REQUIRED FOR BUD DESIGN & ENGINEERING
 SERVICES, INC.FAC61G15-23.002.
  
 6.)SEE PREVIOUS LIST.THE LANDSCAPE
 ARCHITECT HAS SEALED THE NEW SHEETS BUT
 ON LM1 THE SEAL IS STILL ILLEGIBLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-22 Cont ID  
Sent By shill Date 2006-03-22 Time 12:02 Rev Time 0.00
Received By shill Date 2006-03-22 Time 12:02 Sent To  
Notes
2006-03-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)NO INFORMATION WAS PROVIDED FOR THE
 PIER, PLAY AREA, EXERCISE EQUIPMENT,
 ACCESSIBLE PARKING AND THE PAVILION.
 SEPARATE PERMITS REQUIRED.
  
 2.)SEE ATTACHED INFORMATION REGARDING
 TITLE II, ADAAG AND GUIDELINES FOR
 DESIGN.ADDITIONAL INFORMATION IS
 AVAILABLE FROM THE ACCESS BOARD.NOTE
 THAT THESE GUIDELINES ARE NOT
 REQUIREMENTS.FROM ADA WEBSITE - "THE
 ABSENCE OF SPECIFIC PROVISIONS IN THE
 CURRENT STANDARDS DOES NOT MEAN THAT
 FACILITIES OR PLAY AREAS ARE EXEMPT FROM
 THE PROVISION OF ACCESS; RATHER, IT
 MEANS FACILITIES AND AREAS ARE NOT HELD
 TO A SPECIFIC LEVEL OF ACCESS UNDER THE
 CURRENT STANDARD."THE OWNER AND
 DESIGNER ARE TO DETERMINE LEVEL OF
 ACCESS.
  
 3.)ALL ELEMENTS ARE TO BE ON AN
 ACCESSIBLE ROUTE.NONE IS SHOWN FOR THE
 DOG PARK AREA, PLAY AREA, VOLLEYBALL
 COURT.
  
 4.)THE LANDSCAPE ARCHITECT'S SEAL IS
 TO BE LEGIBLE, FS481.306.
  
 5.)NOTE THAT A PORTION OF THIS LOT
 APPEARS TO BE IN A HIGH HAZARD FLOOD
 ZONE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-04-14 Cont ID  
Sent By dpalmer Date 2006-04-14 Time 07:23 Rev Time 0.00
Received By dpalmer Date 2006-04-14 Time 06:59 Sent To  
Notes
2006-04-14 00:00:00************ REDLINED ************
  
  
 1) PLEASE SEE THE "EQUIPMENT GROUNDING
 CONDUCTOR" IS STILL BEING SHOWN FROM
 METER TO THE FIRST MEANS OF DISCONNECT.
 RESPONSE LTR FROM ENGINEER, MENTIONED
 THIS WAS REMOVED PER NOTES, HOWEVER THIS
 IS SHOWN ON RISER ON ALL THREE SETS.
 PLEASE SEE 250.6, 250.24B, THE "EQUIP
 GRNDING" IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISC.
  
  
 2) PLEASE SEE THE PLANS NOW INDICATE A
 STRUCTURE WITH LT, THIS STRUCTURE WILL
 BE REQUIRED TO HAVE A MEANS OF DISC FOR
 LT AND ANY ELECTRICAL TO THIS STRUCTURE.
 THIS CAN BE A TOGGLE SW AND CAN BE
 LOCATED HIGHER ON STRUCTURE TO
 ALLEAVITATE INADVERTANT SWITCHING OF LT.
 225.31
  
 ** PLEASE KNOW, THE ABOVE WERE REDLINED
 ON PLANS AND THERE IS NO NEED FOR
 CORRECTIONS AT THIS TIME.
 ** PLEASE REVISE IF PLANS COME BACK OR
 ARE REVISED FOR ANY OTHER ELECTRICAL.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-14 Cont ID  
Sent By dpalmer Date 2006-03-14 Time 17:45 Rev Time 0.00
Received By dpalmer Date 2006-03-14 Time 12:58 Sent To  
Notes
2006-03-14 00:00:00****** UNSAT **********
  
  
 1)NOTE: PLEASE SEE AN "EQUIPMENT
 GROUNDING CONDUCTOR" IS NOT INSTALLED
 UNTIL AFTER THE FIRST MEANS OF
 DISCONNECT. PLEASE SEE 250.6 THE
 GROUNDING OF ELECTRICAL SYSTEMS, CIRCUIT
 CONDUCTORS, SURGE ARRESTERS, AND
 CONDUCTIVE NON?CURRENT-CARRYING
 MATERIALS AND EQUIPMENT SHALL BE
 INSTALLED AND ARRANGED IN A MANNER THAT
 WILL PREVENT OBJECTIONABLE CURRENT OVER
 THE GROUNDING CONDUCTORS OR GROUNDING
 PATHS.
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE AND
 CONDUCTORS FOR SERVICESEEM TO INDICATE
 THAT THE SERVICE WILL BE A SINGLE PHASE
 INSTALLATION. PLEASE SEE ONLY THREE
 CONDUCTORS ARE COMING FROM METER TO MCB
 PANEL, YET LOAD CALCULATIONS MENTIONS
 THE SERVICE BEING 120/208V 3-PHASE.
 PLEASE SEE LOAD CALCUALTIONS ARE DONE TO
 SINGLE PHASE??
 PLEASE CORRELATE ALL OF THE ABOVE.
 215.5. IF 3-PHASE, PLEASE ADJUST CALCS
 AND CONDUCTORS.
  
 3)NOTE: PLEASE SEE PLANS MENTIONS NEW
 CEILING LT, HOWEVER NO CEILING OR
 STRUCTURE COULD B E LOCATED.
  
 4)NOTE: PLEASE SUBMIT SIGNED,DATED AND
 SEALED ENGINEERED WIND LOAD CALCULATIONS
 FOR POLES WITH LT FIXTURES. THESE ARE
 REQUIRED AT THIS TIME AND WILL BE
 REVIEWED BY THE STRUCTUAL PLANS
 REVIEWER. PLEASE SEE MIN NDESIGN SHALL
 MEET FBC 2004 140MPH.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-13 Cont ID  
Sent By adarroug Date 2006-04-13 Time 16:57 Rev Time 0.00
Received By adarroug Date 2006-04-13 Time 16:57 Sent To  
Notes
2006-04-13 00:00:00TO "COMM" BD#26 --EXPIDITED PERMIT--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-22 Cont ID  
Sent By shill Date 2006-03-22 Time 12:23 Rev Time 0.00
Received By shill Date 2006-02-10 Time 13:41 Sent To  
Notes
2006-03-15 00:00:00EXPEDITE PLAN REVIEW PER ROBERT BROWN.
  
  
2006-03-13 00:00:00TO "COMM" BD#3
2006-02-10 00:00:00WAITING FOR "COMM" BD

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-04-15 Cont ID  
Sent By pschmitz Date 2006-04-15 Time 16:13 Rev Time 0.00
Received By pschmitz Date 2006-04-15 Time 16:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-16 Cont ID  
Sent By pschmitz Date 2006-03-16 Time 17:14 Rev Time 0.00
Received By pschmitz Date 2006-03-16 Time 17:14 Sent To  
Notes
2006-03-16 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
 DENIED
 1) SHT L3IRRIGATION
 IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT OR ENGINEER LEGALLY REGISTERED
 UNDER THE LAWS OF THIS STATE REGULATING
 THE PRACTICE OF ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES,
 PART I, OR ENGINEERING AS PROVIDED FOR
 IN CHAPTER 471, FLORIDA STATUTES, THEN
 HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO
 SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY
 FLORIDA STATUTE. IF THE DESIGN
 PROFESSIONAL IS A LANDSCAPE ARCHITECT
 REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF LANDSCAPE
 ARCHITECTURE AS PROVIDED FOR IN CHAPTER
 481, FLORIDA STATUTES, PART II, THEN HE
 OR SHE SHALL AFFIX HIS OR HER SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA AS
 DEFINED IN SECTION
 481.303(6)(A)(B)(C)(D), FS.
  
 2) SHT L3 LOCAL ORDINANCE #2583-95
 BACK FLOW PREVENTER REQUIRED ON THE
 WATER SERVICE TO THE IRRIGATION SYSTEM.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  

Review Stop Z ZONING
Rev No 2 Status P Date 2006-04-21 Cont ID  
Sent By mmclean Date 2006-04-21 Time 07:24 Rev Time 0.00
Received By mmclean Date 2006-04-21 Time 07:24 Sent To B
Notes
2006-04-21 00:00:00RE-STAMP OF PLANS.
  
 GIVEN TO JENNIFER PER SAMANTHA HILL

Review Stop Z ZONING
Rev No 1 Status P Date 2006-03-16 Cont ID  
Sent By mmclean Date 2006-03-16 Time 08:47 Rev Time 0.00
Received By mmclean Date 2006-03-16 Time 08:47 Sent To  
Notes
***NONE***