Plan Review Details - Permit 06020372
Plan Review Stops For Permit 06020372
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-05-05 Cont ID  
Sent By mperson Date 2006-05-05 Time 09:18 Rev Time 0.33
Received By mperson Date 2006-05-05 Time 09:18 Sent To PC
Notes
2006-05-05 00:00:00REFERENCE: GEN/RES PERMIT #05110340

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-02-10 Cont ID  
Sent By mperson Date 2006-02-10 Time 13:30 Rev Time 1.00
Received By mperson Date 2006-02-10 Time 13:29 Sent To PC
Notes
2006-02-10 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT:
  
 1. INDICATE ON THE DRAWING ALL CUT
 SECTIONS OF PIPE AND CORRESPONDING
 LENGTHS PER FBC-2004 FUEL GAS CODE. THE
 ONLY PIPE INDICATED ON DRAWING IS 45' OF
 3/4" PE. DROPS AND RISERS LENGTHS AND
 TYPE OF MATERIAL BEING USED NEED TO BE
 INDICATED ON DRAWING. ALSO VALVES NEED
 TO BE INDICATED ON DRAWING, THERE NEEDS
 TO BE A SHUT OFF VALVE TO GENERATOR.
 2. NEED SPECS ON GENERATOR, ORIGINAL
 GEN-RES PERMIT APPLICATION DENIED AND
 P/U. THEY NEED TO BE RESUBMITTED AND
 PASSED BY ZONING BEFORE GAS PERMIT CAN
 BE ISSUED.
 3. LONGEST LENGTH: DRAWING INDICATES
 45'. IS THIS THE LONGEST LENGTH ON
 SYSTEM?
 4. TYPE OF GAS, (LP OR NATURAL)
 INDICATE ON DRAWING
 5. TOTAL BTU LOAD ON SYSTEM NEEDS TO BE
 INDICATED ON DRAWING
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-5621

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-02 Cont ID  
Sent By adarroug Date 2006-02-10 Time 15:15 Rev Time 0.00
Received By adarroug Date 2006-02-09 Time 17:50 Sent To  
Notes
2006-02-09 00:00:00TO "G" BOX