Plan Review Details - Permit 06020366
Plan Review Stops For Permit 06020366
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-02-10 Cont ID  
Sent By alange Date 2006-02-10 Time 10:07 Rev Time 0.33
Received By alange Date 2006-02-10 Time 10:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-08 Cont ID  
Sent By rmcdouga Date 2006-02-08 Time 10:36 Rev Time 0.00
Received By rmcdouga Date 2006-02-08 Time 10:36 Sent To  
Notes
2006-02-08 00:00:00DENIED
  
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE.
  
 2) THE MAXIMUM DESIGN PRESSURE FOR THE
 PRODUCT LISTED IN THE NOA IS TOO LOW FOR
 ROOF ZONES 2 AND 3.
  
 3) LIMITATION #1 IN THE NOA ALLOWS
 DESIGN PRESSURES TO BE INCREASED BY
 RATIONAL ANALYSIS BY INCREASING THE
 NUMBER OF FASTENERS. HOWEVER, ALL
 RATIONAL ANALYSIS COMPUTATIONS SHALL BE
 PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER,
 REGISTERED ARCHITECT OR REGISTERED ROOF
 CONSULTANT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714