Plan Review Stops For Permit 06020366 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2006-02-10 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-02-10 |
Time |
10:07 |
Rev Time |
0.33 |
Received By |
alange |
Date |
2006-02-10 |
Time |
10:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-02-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2006-02-08 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2006-02-08 |
Time |
10:36 |
Sent To |
|
|
Notes |
2006-02-08 00:00:00 | DENIED | | | | 1) SPECIFY THE MEAN ROOF HEIGHT OF THE | | STRUCTURE. | | | | 2) THE MAXIMUM DESIGN PRESSURE FOR THE | | PRODUCT LISTED IN THE NOA IS TOO LOW FOR | | ROOF ZONES 2 AND 3. | | | | 3) LIMITATION #1 IN THE NOA ALLOWS | | DESIGN PRESSURES TO BE INCREASED BY | | RATIONAL ANALYSIS BY INCREASING THE | | NUMBER OF FASTENERS. HOWEVER, ALL | | RATIONAL ANALYSIS COMPUTATIONS SHALL BE | | PREPARED, SIGNED AND SEALED BY A FLORIDA | | REGISTERED PROFESSIONAL ENGINEER, | | REGISTERED ARCHITECT OR REGISTERED ROOF | | CONSULTANT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|
|
|