Plan Review Details - Permit 06020143
Plan Review Stops For Permit 06020143
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-05-18 Cont ID  
Sent By rmcdouga Date 2006-05-18 Time 16:49 Rev Time 0.00
Received By rmcdouga Date 2006-05-18 Time 16:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-03-17 Cont ID  
Sent By rmcdouga Date 2006-03-17 Time 11:52 Rev Time 0.00
Received By rmcdouga Date 2006-03-17 Time 11:51 Sent To  
Notes
2006-03-17 00:00:00DENIED
  
 1) THE APPROVED ASSEMBLY SELECTED FROM
 THE NOA FOR THE POLYGLASS MODIFIED
 SYSTEM HAS AN UPLIFT OF -45PSF. THE
 REQUIRED UPLIFT IN THE CORNERS IS -89
 PSF. THE SELECTED ASSEMBLY'S UPLIFT IS
 TOO LOW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-03-07 Cont ID  
Sent By rmcdouga Date 2006-03-07 Time 11:37 Rev Time 0.00
Received By rmcdouga Date 2006-03-07 Time 11:38 Sent To  
Notes
2006-03-07 00:00:00DENIED
  
 1) THE ASSEMBLY SUBMITTED FOR THE POLY
 GLASS MODIFIED SYSTEM PAGE 44 OF THE
 PRODUCT APPROVAL IS FOR USE UNDER A TILE
 ROOF WHEN THE DESIGN PRESSURE FOR THE
 TILE IS USED FOR UPLIFT. SELECT THE
 CORRECT TYPE OF APPLICATION FROM THE
 NOA.
  
 2) IF THE DESIGN PRESSURE FOR THE
 ASSEMBLY THAT IS TO BE INSTALLED IS LESS
 THAN -89PSF, THEN ENHANCED FASTENING OF
 THE UNDERLYMENT WILL BE REQUIRED IF
 ALLOWED BY LIMITATIONS ( LIMITATION #9
 DOES NOT ALLOW IT). LIMITATION #7 DOES
 ALLOW ENHANCED FASTENING IN ACCORDANCE
 WITH RAS 117, BUT THE CALCULATIONS MUST
 BE DONE BY AN ARCHITECT, ENGINEER OR
 REGISTERED ROOF CONSULTANT AND SIGNED
 AND SEALED CALCULATIONS ARE REQUIRED TO
 BE SUBMITTED BEFORE A PERMIT IS ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-09 Cont ID  
Sent By rmcdouga Date 2006-02-09 Time 13:50 Rev Time 0.00
Received By rmcdouga Date 2006-02-09 Time 13:50 Sent To  
Notes
2006-02-09 00:00:00SECOND REVIEW
  
 1) SUBMIT THE SHEETS FROM THE POLYGLASS
 MODIFIED BITUMEN SYSTEM NOA THAT SPECIFY
 THE APPROVED ASSEMBLY THAT WILL BE
 INSTALLED. THE DESIGN PRESSURES FOR THE
 ASSEMBLY ARE LISTED ON THESE SHEETS.
  
 2) THIS NOA (#03-0130.08) FOR FL985-R1
 REQUIRES ENHANCED FASTENING CALCULATIONS
 USING RAS 117 TO BE PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED ENGINEER,
 ARCHITECT OR REGISTERED ROOF CONSULTANT.
 READ LIMITATION #7 ON PAGE 45 ON NOA.
  
 3) IF LIMITATION #9 IS SPECIFIED AT THE
 DESIGN PRESSURE LISTED FOR THE ASSEMBLY
 THEN NO INCREASE IN PRESSURES ARE
 ALLOWED. SEE LIMITATION #9 ON PAGE 45 OF
 THE NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-02 Cont ID  
Sent By rmcdouga Date 2006-02-02 Time 16:07 Rev Time 0.00
Received By rmcdouga Date 2006-02-09 Time 13:50 Sent To  
Notes
2006-02-02 00:00:00DENIED
  
 1) THE DESIGN PRESSURE FROM THE NOA OF
 -45 PSF FOR THE MODIFIED ROOF SYSTEM
 ASSEMBLY DOES NOT MEET THE REQUIRED
 UPLIFT OF -89 PSF. LIMITATION #9 DOES
 NOT ALLOW FOR ENHANCED FASTENING TO
 INCREASE THE DESIGN PRESSURE.
  
 2) THE PRODUCT APPROVALS FOR THE GAF
 SHINGLES HAVE BEEN UPDATED TO THE 2004
 FBC ON THE STATE WEBSITE. SUBMIT THE
 UPDATED VERSIONS. FL183-R1 AND NOA
 04-0820.01.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-09 Cont ID  
Sent By adarroug Date 2006-02-09 Time 11:28 Rev Time 0.00
Received By adarroug Date 2006-02-09 Time 11:28 Sent To B
Notes
2006-02-09 00:00:00TO "RMCDOUGAL" DESK/RESUB