Plan Review Stops For Permit 06020010 |
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2006-02-08 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2006-02-08 |
Time |
06:14 |
Rev Time |
1.00 |
Received By |
mperson |
Date |
2006-02-08 |
Time |
06:14 |
Sent To |
PC |
|
Notes |
2006-02-08 00:00:00 | DENIED | | REFERENCE:FBC-2004 FUEL GAS | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR A GAS PERMIT: | | | | 1. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (NOTE:THERE | | ARE PLACES ON DRAWING WHERE THIS IS | | MISSING.) | | 2) SYSTEM IS SIZED WRONG.PIPING SYSTEM | | SHOULD HAVE BEEN SIZED USING FBC-2004 | | FUEL GAS TABLE- 402.4(2) USING THE 200' | | FOR THE LONGEST RUN. SEE ATTACHED | | TABLE.ALSO NEED TWO COPIES OF APPLIANCE | | SUBMITTALS, ONE FOR JOBSITE AND ONE FOR | | CITY RECORDS. | | 3. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE.(PLEASE IN- | | CATE THIS ON THE DRAWING) | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561)805-6730 | | FAX (561)805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561)805-6721 | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-02-03 |
Time |
08:47 |
Sent To |
|
|
Notes |
2006-02-03 00:00:00 | TO "G" BOX |
|
|
|