Plan Review Details - Permit 06011259
Plan Review Stops For Permit 06011259
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-08 Cont ID  
Sent By mjacobs Date 2006-09-08 Time 13:54 Rev Time 0.00
Received By mjacobs Date 2006-09-08 Time 13:12 Sent To  
Notes
2006-09-08 00:00:00 

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-12 Cont ID  
Sent By mjacobs Date 2006-05-12 Time 18:52 Rev Time 0.00
Received By mjacobs Date 2006-05-12 Time 16:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-14 Cont ID  
Sent By mjacobs Date 2006-04-14 Time 10:39 Rev Time 0.00
Received By mjacobs Date 2006-04-14 Time 06:07 Sent To PC
Notes
2006-04-14 00:00:001) A DETAIL DRAWING OF THE NEW BATHROOM
 IS REQUIRED SHOWING ALL THE REQUIREMENTS
 FOR ACCESSIBILITY. SHOW THE DIMENTIONS
 FOR GRAB BARS, CLEAR FLOOR SPACE, TOILET
 PAPER HOLDER ETC.
 DOORS SHALL NOT SWING INTO THE FLOOR
 SPACE REQUIRED FOR ANY FIXTURE.
 SEC.11-4.23.2
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) PLEASE STATE THE DIMENTIONS OF ALL
 OPENINGS/PASS-THROUGH ON DRAWINGS.
  
 4) SUBMIT THE ELEVATION DRAWINGS FOR THE
 LOUNGE/RECEPTION OR
 ADMINISTRATION,REPAIR LAB AND ALL OTHER
 WORK AREAS SHOWING THE HEIGHT OF THE
 SINKS AND COUNTER TOPS ETC. OF THESE
 AREAS.SEE FBC SEC.11-7
  
 5) 11-4.13.6 MANEUVERING CLEARANCES AT
 DOORS .
 MINIMUM MANEUVERING CLEARANCES AT DOORS
 THAT ARE NOT AUTOMATIC OR POWER-ASSISTED
 SHALL BE AS SHOWN IN FIGURE 11-25 . THE
 FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE LEVEL AND CLEAR.
  
 6)IS THIS BUSINESS ON THE FIRST OR
 SECOND FLOOR. IF IT IS LOCATED ON THE
 SECOND FLOOR INDICATE THE ACCESSIBILITY
 TO THE AREA FOR THE HANDI-CAP. IF
 ELEVATORS ARE PROVIDED,STATE THE SIZE
 OF THE DOOR OPENINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-09-08 Cont ID  
Sent By dpalmer Date 2006-09-08 Time 18:13 Rev Time 0.00
Received By dpalmer Date 2006-09-08 Time 18:02 Sent To  
Notes
2006-09-08 00:00:00REV FOR EXT LT LOCATIONS.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-07-15 Cont ID  
Sent By dpalmer Date 2006-07-15 Time 09:21 Rev Time 0.00
Received By dpalmer Date 2006-07-15 Time 09:04 Sent To  
Notes
2006-07-15 00:00:00PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-06-20 Cont ID  
Sent By dpalmer Date 2006-06-20 Time 18:26 Rev Time 0.00
Received By dpalmer Date 2006-06-20 Time 17:22 Sent To PC
Notes
2006-06-20 00:00:00********* UNSAT 4TH REVIEW **********
  
 ** PLEASE SEE NOTES FROM PREVIOUS
 REVIEWS DATED 3/6/06,5/09/06 6/11/06
  
 1) NOTE: PLEASE SEE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1,.1.2, .1.3 ETC
 13-415.1.ABC.3, 13-415.1.AB.1 ,
 13-415.2.ABC.1 ETC.
 PLEASE SEE MISSING ENERGY CODE
 COMPLIANCE FORMS (FORM C) 2004, SEE
 ABOVE.
  
  
 PLEASE SEE THAT DETAILS AND NOTES ADDED
 TO PLANS ARE FROM THE 2001 FBC CHAPTER
 13.
 PLEASE SEE THAT THE NOTES AND DESIGN DO
 NOT APPLY AS THE DESIGN SHALL BE UNDER
 THE 2004 FBC. PLEASE SEE THAT THE REST
 OF THE PLANS AND DESIGN ARE ALREADY
 UNDER THE 2004 FBC.
 MAY NOT USE 2001 FBC FOR CHAPTER 13 AND
 THE 2004 FOR ALL OTHER AREAS.
  
 2) NOTE: PLEASE SEE ONLY COPY OF THE NEW
 ELECTRICAL E-1 WAS SUBMITTED AND THE
 E-2WHICH IS IN SETS WASFROM THE
 PREVIOUS SETS WHICH STILL CONTAINS THE
 OLD SEAL WHICH IS NOT ACCEPTABLE. PLEASE
 SEE NOTE #4.
 MIN OF TWO SETS ARE REQUIRED, SIGNED,
 DATED AND SEALED BY SAID ARCHITECTS; AND
 ENGINEER'S OF RECORD.
 PLEASE ALSO SEE THAT ALL PLANS SHALL BE
 CLEAR AND VISABLE WITH ALL INFORMATION.
 PLEASE KNOW THAT PLANS CONTAIN MANY
 HANDRAWN ITEMS WHICH ARE NOT EASILY READ
 AND PLANS NEED TO BE RE-DONE.
 PLEASE SEE FBC ADMIN SECT 106.1.3
 106.1.2,106.3.5 ETC
  
 3) NOTE: " IMPORTANT"
 PLEASE SEE PREVIOUS REVIEW NOTES ALSO
 REQUESTED THAT WHEN PLANS ARE SUBMITTED,
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ANY OF THE SHEETS WHICH ARE STAMPED BY A
 TRADE AS "PASSED", THEN THOSE WILL STILL
 REMAIN IN NEW SETS. ONLY ONE SET OF ALL
 OLD/VOIDED REMOVED SHEETS SHALL BE
 SUBMITTED FOR REFERENCE.
 ** PLEASE KNOW, THIS WILL HELP TO
 EXPEDITE THE PLAN REVIEW PROCESS AS WE
 WILL NOT BE ABLE TO MAKE ALL SHEETS INTO
 COMPLETE SETS AND COULDDELAY THE
 PROJECT UNTIL THIS IS DONE.
  
 4) NOTE: PLEASE SEE NOTE FROM 2ND REVIEW
 WHEN PLANS CAME BACK SEALED WITH A SEAL
 CONTAINING THE WORDING "CERTIFICATE" .
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G15-23.001 WHICH CHANGED THE
 REQUIREMENT IN FEB 04 TO REQUIRE THE
 WORDING OF "LICENSE" IN SAID SEAL.
 PLEASE KNOW, AN EXTENSION WAS GRANTED BY
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEER'S TO THE DATE OF DEC 31, 2005.
 PLEASE SEE THE SHEET E-2 IS STILL THE
 OLD SHEET CONTAINING THE OLD SEAL.
  
 5) NOTE: PLEASE PROVIDE UPDATED PLUMBING
 SHEETS AS THE SHEETS IN SETS WHICH WERE
 ALREADY STAMPED BY THE PLUMBING REVIEW
 NOW CONTAIN "WHITE-OUT" AND HANDRAWN
 CHANGES. PLEASE KNOW THESE SHEETS WHICH
 WERE ALREADY STAMPED HAVE NOW BEEN
 "VOIDED". PLEASE KNOW UNDER FS 481, 471
 NO "WHITE-OUT" IS PERMITTED ON PLANS IN
 ANY MANNER.
  
 6) NOTE: PLEASE KNOW BASED ON REPEAT
 COMMENTS FOR CODE COMPLIANCE THREE OR
 MORE TIMES FOR THE SAME CODE REQUIREMENT
 A FEE HAS BEEN ASSESSED AS REQUIRED
 UNDER FLORIDA STATUES 553.80(2)(B).
 PLEASE SEE THAT THE FS REQUIRES THIS FEE
 TO THE DESIGN PROFESSIONAL.
 PLEASE KNOW THE FEE MUST BE PAID BEFORE
 THE PLANS ARE RESUBMITTED FORNEXT
 REVIEW.
 THE AMOUNT OF $2203.20 IS NOW OWED.
 ** PLEASE KNOW ONE COPY OF EACH OF ALL
 OLD ELECTRICAL SHEETS ARE BEING RETAINED
 BY THE BUILDING OFFICAL FOR FILE AS THE
 BUILDING OFFICAL MAY SUBMIT FOR PEIR
 REVIEW BY THE FBPE'S AND BOARD'S LEGAL
 COUNSEL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-06-11 Cont ID  
Sent By dpalmer Date 2006-06-11 Time 16:31 Rev Time 0.00
Received By dpalmer Date 2006-06-11 Time 16:11 Sent To PC
Notes
2006-06-11 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE NOTES DATED 3/6/06
  
 PLEASE PROVIDE LIGHTING CONTROOLS AS
 REQUIRED UNDER THE 2004 FBC CHAPTER 13
 13-415.1.ABC.1.1,.1.2,.1.3.
 PLEASE SPECIFY THE TIME SCHEDULING, THE
 LOCATION OF THE OVER RIDE DEVICES.
 PLEASE SEE A MAX OF 4HRS IS PERMITTED
 FOR MANUAL OVERIDES, AND 30MIN FOR OCC
 SENSORS.
 PLEASE SEE AREAS CONTAINING SEPARATE
 SPACES W/ FLR TO CEILING HEIGHT
 PARTITIONS WHICH REQUIRE CONTROL IN EACH
 AREA.
  
 2) NOTE: PLEASE SEE ALL INFORMATION ON
 PLANS SHALL BE CLEAR AND VISABLE.
 FBC 106.3 ADMIN SEC. AS ADOPTED BY THE
 CITY OF WEST PALM BEACH
  
 3) NOTE: PLEASE COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT THE NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONLY ONE COPY OF THE OLD/VOIDED REMOVED
 SHEETS NEED BE SUBMITTED FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-09 Cont ID  
Sent By btrobaug Date 2006-05-09 Time 18:40 Rev Time 0.33
Received By btrobaug Date 2006-05-09 Time 18:37 Sent To  
Notes
2006-05-09 00:00:00 
  
  
 PLEASE SEE FAC 61G15-23.002 FOR THE
 ENGINEERS SEAL REQUIREMINTS AS OF 1
 JANUARY,2006.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-06 Cont ID  
Sent By dpalmer Date 2006-03-06 Time 18:40 Rev Time 0.00
Received By dpalmer Date 2006-03-06 Time 18:09 Sent To  
Notes
2006-03-06 00:00:00******UNSAT ********
  
 ** PLEASE SEE COMMENTS BELOW AND
 COMMENTS FROM OTHER TRADES DUE TO THE
 CHANGE IN OCCUPANCY AS NOTED FOR MEETING
 THE CURRENT CODES.
  
  
 1)NOTE: PLEASE HAVE PLANS REFERENCE THE
 CURRENT CODES, 2003 NFPA-101, 2002
 NFPA-72, AND 2002 NFPA-70.
  
 3)NOTE: PLEASE SEE RISER INDICATES 3/0'S
 FOR 225A'S? PLEASE SEE 310.16, WHERE
 3/0'S ARE ONLY RATED FOR 200A'S.
  
 4)NOTE: PLEASE SHOW LOCATIONS OF ALL
 EXISITNG ELECTRICAL PANELS/EQUIPMENT.
 215.5, 110.26,240.24,408.7
  
 5)NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1& .2, CONTROL OF
 LIGHTING.
 13-413.1ABC.1, VOLTAGE DROP, PROVIDE
 INFORMATION.
 13-415.1AB.1
 PLEASE PROVIDE, SCHEDULING, CIRCUITING
 ETC.
  
 6)NOTE: PLEASE SEE LOAD CALCUALTIONS
 WHICH SHOWS LOADS: 180A'S IS LESS THAN
 208A'S?? PLEASE SEE 208A SERVICE COULD
 NOT BE LOCATED ON ANY PLANS/RISER.
 (MISPRINT).?
  
 7)NOTE: PLEASE PROVIDE A MORE SPECIFIC
 DETAIL OF LOADS.
 215.5/220
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. ONE SET OF
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERNECE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-09-11 Cont ID  
Sent By mawillia Date 2006-09-11 Time 12:22 Rev Time 0.00
Received By mawillia Date 2006-09-11 Time 12:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-05-15 Cont ID  
Sent By nmccray Date 2006-05-15 Time 13:31 Rev Time 0.00
Received By nmccray Date 2006-05-15 Time 13:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-03-16 Cont ID  
Sent By mwennerg Date 2006-03-16 Time 14:08 Rev Time 0.00
Received By mwennerg Date 2006-03-16 Time 14:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-09-20 Cont ID  
Sent By adarroug Date 2006-09-20 Time 14:27 Rev Time 0.00
Received By adarroug Date 2006-09-20 Time 14:27 Sent To M
Notes
2006-09-20 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-06 Cont ID  
Sent By adarroug Date 2006-09-06 Time 15:57 Rev Time 0.00
Received By adarroug Date 2006-09-06 Time 15:57 Sent To  
Notes
2006-09-08 00:00:00TO "BOB"#14
2006-09-06 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-11 Cont ID  
Sent By adarroug Date 2006-07-11 Time 15:57 Rev Time 0.00
Received By adarroug Date 2006-07-11 Time 15:57 Sent To  
Notes
2006-07-13 00:00:00TO "BOB"#12
2006-07-11 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-20 Cont ID  
Sent By adarroug Date 2006-06-20 Time 10:49 Rev Time 0.00
Received By adarroug Date 2006-06-20 Time 10:49 Sent To E
Notes
2006-06-20 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-05 Cont ID  
Sent By adarroug Date 2006-06-05 Time 15:07 Rev Time 0.00
Received By adarroug Date 2006-06-05 Time 15:07 Sent To E
Notes
2006-06-05 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-03 Cont ID  
Sent By adarroug Date 2006-05-03 Time 16:51 Rev Time 0.00
Received By adarroug Date 2006-05-03 Time 16:51 Sent To  
Notes
2006-05-08 00:00:00TO "BOB"#5
2006-05-03 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-04-14 Time   Rev Time 0.00
Received By adarroug Date 2006-02-01 Time 19:09 Sent To  
Notes
2006-04-11 00:00:004/11/06-MOVED TO "BOB"#1--PER "RBROWN"
 ADARROUGH
2006-03-06 00:00:00TO "COMM" BD#8
2006-02-01 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pkrauss Date 2006-09-28 Time 08:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-03-12 Cont ID  
Sent By hmoser Date 2006-03-12 Time 12:35 Rev Time 0.00
Received By hmoser Date 2006-03-12 Time 12:35 Sent To  
Notes
2006-03-12 00:00:00PASS PRIVISO
 PLAESE REFER TO SECTION 606.2.2 AND
 SECTION 601.4.1 FBC(M) 2004.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-07-15 Cont ID  
Sent By jleech Date 2006-07-15 Time 09:48 Rev Time 0.00
Received By jleech Date 2006-07-15 Time 09:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-15 Cont ID  
Sent By jleech Date 2006-05-15 Time 07:53 Rev Time 0.00
Received By jleech Date 2006-05-15 Time 07:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-12 Cont ID  
Sent By jleech Date 2006-04-12 Time 10:39 Rev Time 0.00
Received By jleech Date 2006-04-12 Time 10:39 Sent To  
Notes
2006-04-12 00:00:00DENIED;
 1.UNISEX TOILET ROOM IS REQUIRED TO BE
 HANDICAP. FBC-2004 CHAPTER 11 SEC.
 11-4.1.3(11). DOOR SWING SHALL COMPLY
 WITH SEC.11-4.22.2, DOOR SWING CANNOT
 ENTER THE CLEAR FLLOR SPACE OF A
 FIXTURE.
 2.SANITARY RISER DIAGRAM; AIR ADMITANCE
 VALVES CAN BE USED ONLY ON THE TOP 4
 FLOORS WITHOUT A RELIEF VENT FBC-2004
 PLUMBING SEC. 917.3.1.
 3.WATER RISER DIAGRAM; WATER HAMMER
 ARRESTORS ARE REQUIRED ON LOUNGE SINK,
 SEC 604.9. WATER HAMMER ARRESTORS, TO BE
 INSTALLED PER MANUFACTURE'S
 RECOMMENDATIONS, AS CLOSE TO THE SOURCE
 AS POSSIBLE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695