Plan Review Details - Permit 06011138
Plan Review Stops For Permit 06011138
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-25 Cont ID  
Sent By alange Date 2006-08-25 Time 08:36 Rev Time 0.00
Received By alange Date 2006-08-25 Time 08:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-02-16 Cont ID  
Sent By alange Date 2006-02-16 Time 16:34 Rev Time 0.50
Received By alange Date 2006-02-16 Time 16:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-24 Cont ID  
Sent By btrobaug Date 2006-08-24 Time 08:41 Rev Time 0.50
Received By btrobaug Date 2006-08-24 Time 07:52 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-09 Cont ID  
Sent By btrobaug Date 2006-02-09 Time 11:03 Rev Time 0.50
Received By btrobaug Date 2006-02-09 Time 09:58 Sent To M
Notes
2006-02-09 00:00:00 
 THE VALUE ON THE APPLICATION MUST
 REFLECT THE TOTAL VALUE OF LABOR AND
 MATERIAL PER 108.3 FBC.( COST OF
 GENERATOR ,ATS,SLAB, ETC.)
  
  
 1}INDICATE FEEDER FROM PANEL "N" TO ATS
 IN PANEL "N" SCHEDULE. THIS IS TO
 PREVENT AN INADVERTENT POWER UP OF THE
 GENERATOR PANEL, CURRENTLY LABLED "L",
 WHILE ATTEMTING TO DE-ENERGISE IT WITH
 THE BREAKER, AND RE ENERGIZING IT WITH
 THE GENERATOR.
  
 2} SHOW PANEL "S" ON THE RISER PER 215.5
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-02-15 Cont ID  
Sent By mperson Date 2006-02-15 Time 14:40 Rev Time 0.33
Received By mperson Date 2006-02-15 Time 14:40 Sent To B
Notes
2006-02-15 00:00:00NOTE: SEPERATE PLANS AND PERMIT REQUIRED
 FOR GAS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-22 Cont ID  
Sent By adarroug Date 2006-08-22 Time 14:55 Rev Time 0.00
Received By adarroug Date 2006-08-22 Time 14:55 Sent To E
Notes
2006-08-22 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-12 Cont ID  
Sent By adarroug Date 2006-08-12 Time 14:14 Rev Time 0.00
Received By adarroug Date 2006-08-12 Time 14:14 Sent To Z
Notes
2006-08-12 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-02 Cont ID  
Sent By adarroug Date 2006-02-02 Time 15:16 Rev Time 0.00
Received By adarroug Date 2006-02-02 Time 15:16 Sent To E
Notes
2006-02-02 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-02-16 Time   Rev Time 0.00
Received By adarroug Date 2006-01-31 Time 13:59 Sent To  
Notes
2006-01-31 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-08-24 Cont ID  
Sent By tgordon Date 2006-08-24 Time 09:10 Rev Time 0.20
Received By tgordon Date 2006-08-24 Time 09:10 Sent To B
Notes
2006-08-24 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURE'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING, AND PROVIDE MANUFACTURE'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-02-13 Cont ID  
Sent By tgordon Date 2006-02-13 Time 15:16 Rev Time 0.15
Received By tgordon Date 2006-02-13 Time 15:16 Sent To P
Notes
2006-02-13 00:00:00*** PROVISO ***
 1)GENERATOR EXHUST MUST BE TEN FEET AWAY
 FROM ANY BUILDING OPENINGS (WINDOWS,
 DOORS, ROOF & EAVE VENTS), AND TEN FEET
 AWAY FROM ADJECENT BUILDING OPENS. PER
 2004 FBC/M 401.5.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-02-15 Cont ID  
Sent By mperson Date 2006-02-15 Time 14:39 Rev Time 0.00
Received By mperson Date 2006-02-15 Time 14:39 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2006-08-19 Cont ID  
Sent By mmclean Date 2006-08-19 Time 06:59 Rev Time 0.00
Received By mmclean Date 2006-08-19 Time 06:59 Sent To I
Notes
2006-08-19 00:00:00DENIED,
 1. THE FOOTPRINT OF THE SURVEY & PARTIAL
 SITEPLAN DOES NOT MATCH.
 2. PLEASE PROVIDE AND UPDATED SURVEY
 SHOWING THE CORRECTED FOOTPRINT OF THE
 EXISTING STRUCTURE (SHOWING ANY ADDITION
 THAT CHANGED THE FOOTPRINT TO WHAT THE
 SURVEY IS SHOWING DATED 10/10/90
 3. THE SITEPLAN MUST SHOW ALL THAT
 LOCATED ON THE PROPERTY AND MUST BE A
 FULL SIZE SITEPLAN WITH DIMENSION OF THE
 COMPLETE PROPERTY WITH SETBACKS OF THE
 STRUCTURE (FRONT/SIDE/REAR)
 4. THE SITEPLAN SUBMITTED CANNOT BE USED
 A REVIEW FOR THE PROPOSED WORK AND THE
 SURVEY SUBMITTED IS NOT A CURRENT SURVEY
 (10/10/90)
  
 NOTE: SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-02-02 Cont ID  
Sent By mmclean Date 2006-02-02 Time 13:19 Rev Time 0.00
Received By mmclean Date 2006-02-02 Time 13:19 Sent To I
Notes
2006-02-02 00:00:00DENIED,
 1. NEED TO PROVIDE A COMPLETE SURVEY OR
 SITEPLAN WITH DIMENSION OF LOT WITH
 SETBACKS AND ADDRESS OF PROPERTY.
 2. MUST INDICATE THE SETBACK OF THE
 GENERATOR FROM PROPERTY LINE.
 3. SITEPLAN (PARTIAL) DOES NOT PROVIDE
 INFORMATION NEEDED TO COMPLETE ZONING
 REVIEW.
  
 NOTE: GENERATOR CAN ONLY ENCROACH 4FT
 INTO A SETBACK (CANNOT ENCROACH ON
 PROPERTY LINE).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720