Plan Review Details - Permit 06011123
Plan Review Stops For Permit 06011123
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-02-22 Cont ID  
Sent By jwitmer Date 2007-02-22 Time 16:47 Rev Time 2.22
Received By jwitmer Date 2007-02-22 Time 16:39 Sent To  
Notes
2007-02-22 16:56:20BUILDING PLAN REVIEW
 PERMIT: 06011123
 ADD: 2100 45TH STREETSUITE???
 CONT: RALPH DELLA-PIETRA, INC
 TEL: (561)745-8555
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) NEITHER THE PLANS NOR THE PERMIT APPLICATION
 INDICATE WHICH SUITE
 THE WORK WILL BE COMPLETED WITHIN? 106.1.2*
 ADMINISTRATIVE CODE,
 ADDITIONAL INFORMATION REQUIRED.
  
 4) DESIGN PARAMETERS
 4A) 2004 FBC CORRECT THE CODE SECTION
 4B) DESIGNED TO ASCE 7-98 CORRECT
  
 5) LS-1 INDICATES THIS IS A TYPE V-B PLEASE SHOW THE
 AREA INCREASES THAT WERE TAKEN FOR THIS STRIP MALL TO
 CLASSIFY THIS TENANT SPACE AS A
 TYPE V-B? NOTES INDICATE THAT THERE IS NO FIRE
 SPRINKLERS SO ONLY THE FRONTAGE INCREASE CAN BE TAKEN.
 SECTION 506.1.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-28 Cont ID  
Sent By alange Date 2006-09-28 Time 14:36 Rev Time 0.00
Received By alange Date 2006-09-28 Time 14:36 Sent To  
Notes
2006-09-28 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.PRODUCT APPROVALS REQUIRED FOR
 EXTERIOR DOORS.
  
 3.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 4.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
  
 6. ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2005 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.SEE ASCE-7-98
 SHOULD BE ASCE-7-02
  
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-20 Cont ID  
Sent By alange Date 2006-04-20 Time 08:09 Rev Time 0.00
Received By alange Date 2006-04-20 Time 08:09 Sent To  
Notes
2006-04-20 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.PRODUCT APPROVALS REQUIRED FOR
 EXTERIOR DOORS AND STORE FRONT.
  
 3.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 4.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 5.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 6. ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2005 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 7.SHOW CONSTRUCTION TYPE AND TYPE OF
 OCCUPANCY ON PLANS.106.3.5.1.1 WPB
 AMMENDMENT TO THE FBC
  
 8.SPECIFY INTERIOR FINISHES USED. FBC
 803.5
  
 9.OUTDATED ENGINNER SEAL USED. NEW
 SEAL SHALL SHOW "LICENSED" NOT
 CERTIFICATE. FAC61G1-16.001
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-02-03 Cont ID  
Sent By dpalmer Date 2007-02-03 Time 19:18 Rev Time 0.00
Received By dpalmer Date 2007-02-03 Time 17:37 Sent To  
Notes
2007-02-03 19:19:48*** UNSAT 3RD REVIEW ***
  
 1) NOTE: PLEASE SEE PREVIOUS TWO REVIEWS WHICH
 REQUESTED ENERGY CALCULATIONS, PERFORMANCE LIGHTING
 LEVELS.
 PLEASE SEE THE LIGHTING OVER RIDE DEVICES MUST BE
 LOCATED AT ENTRANCES OF INGRESS INTO THE BUILDING WHERE
 AN OCCUPANT MAY ENTER AFTER HOURS. PLEASE SEE THAT ANY
 MANUAL OVER RIDE DEVICE MUST BE READILY ACCESSIBLE.
 PLEASE SEE SOME MEANS FOR OVER RIDING LIGHTING AT ALL
 LOCATIONS OF ENTRANCE.
 PLEASE SEE SOME DEVICES ON PLANS SEEM TO BE SHOWN AS A
 STANDARD WALL SWITCH AS INDICATED ON SYMBOL LEGEND.
 PLEASE SEE PLANS MENTIONS A TIME CLOCK, HOWEVER IS THIS
 A ASTRONOMICAL TC?
  
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3
 PLEASE SEE THE PLANS SUBMITTED DO NOT CONTAIN THESE.
 PLEASE SEE FBC 13-415.1.AB.1, 13-415.2 ETC
  
 2) NOTE: PLEASE SEE 210.12 FOR LOADS TO BE FIGURED AND
 SHOWN PER 220.12.
 PLEASE SEE THE MINIMUM VA PER FT SHALL BE FIGURED FOR
 SERVICE/FEEDERS.
 PREVIOUS TWO REVIEWS.
  
 3) NOTE: PLEASE CLARIFY NOTE ON PLANS WHICH MENTIONS
 ALL LIGHTING IS EXISTING. HOW IS THIS POSSIBLE WHEN
 THIS IS A NEW BUILD OUT?
  
 4) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE A NOTICE
 TO FS 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR
 CODE COMPLIANCE THREE OR MORE TIMES FOR THE SAME
 COMMENTS.
 PLEASE SEE A FEE OF $1680.00 IS NOW ASSESSED AND WILL
 BE REQUIRED TO BE PAID BEFORE NEXT RE-SUBMITTAL.
 PLEASE KNOW THIS FEE MAY ALSO BE FOR ANY OTHER TRADE
 WHICH MAY HAVE THE SAME COMMENT THREE OR MORE TIMES.
 PLEASE SEE BUILDING REVIEW COMMENTS.
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-19 Cont ID  
Sent By dpalmer Date 2006-09-19 Time 20:12 Rev Time 0.00
Received By dpalmer Date 2006-09-19 Time 19:30 Sent To  
Notes
2006-09-19 00:00:00********UNSAT 2ND REVIEW *********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED, ALONG
 WIHT NEW COMMENTS BASED ON PLANS
 SUBMITTED.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AND NEW
 NOTES ARE ADDED TO THE BOTTOM.
  
 1)NOTE: OK.
  
 2)NOTE:OK, MOST CODES ADDED, HOWEVER
 PLEASE BE SURE THE ELECTRICAL PLANS ALSO
 STATE THE 2004 FBC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASEBE SURE ALL CURRENT
 CODES FOR THE FOLLOWING ARE REFERENCED
 ON ELECTRICAL PLANS.
 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72.
 PLEASE SEE SHEETSWHICH REFLECT THE
 2001 FBC.
 PLEASEKNOW, THE STATE OF FLORIDA
 ADOPTED THE 2004 FBC ON OCT 1ST, 2005
  
 3)NOTE: OK.
  
 4)NOTE:NO, PLEASE VERIFY AS THE
 DISONNECT IS BEING NOTED AS BEING FUSED
 AND 10K IS NOT COMMEN FOR THE AIC
 RATINSGS FOR FUSES. PLEASE SEE NEW
 COMMENTS ALSO.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE THE AIC RATINGS
 FOR THE NEW FUSES FOR MAINS. 110.9,215.5
  
 5)NOTE: OK. SEE NEW NOTES.
  
 6)NOTE: NO, PLEASE SEE NO SYSTEM WAS
 SUBMITTED AND SHOWN AS REQUIRED. A TC
 NOTED FOR LTS, DOES NOT GIVE ALL
 INFORMATION AS NEEDED. PLEASE PROVIDE
 THE SYSTEM, SCHEDULING, ALL OVER-RIDES
 ETC. PLEASE SEE PLANS DO NOT INDICATE
 ANY OVER-RIDE DEVICES, MAX TIMES
 PERMITTED ON THE DEVICES WHICH MAY BE
 INSTALLED.
 PLEASE SEE TAKING THE SECTIONS OF THE
 CODE AND QUOTING THE CODE IS NOT
 ACCEPTABLE IN LEIU OF MIN DESIGNS
 REQUUIRED ON PLANS FOR THE TECHNICAL REQUIREMENTS.
 FBC 106.1, ADMIN SECT.
 NO ENERGY CALCULATIONS, NO LIGHTING
 POWER ALLOWANCES ETC.
 PLEASE SEE NOTES BELOW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13, FOR
 THE NEW REWUIREMENTS FOR COMMERCIAL
 BLDGS.
 PLEASE SEE A WORST CASE CALCUALTION TO
 BE SHOWN FOR VOTLAGE DROP TO MEET THE
 MIN AS SET FORTH IN 13-413.1ABC.1
 PLEASE SEE 13-415.1.ABC.1 & .2 FOR
 INTERIOR LIGHTING SHUTOFF, SPACE
 LIGHTING CONTROLS REQUIRED.PLEASE
 PROVIDE SCHEDULING.
 PLEASE SEE 13.415.1.ABC.1.4 FOR EXTERIOR
 LTS, AND TYPE OF TIME CLOCK REQUIRED .
 PLEASE SEE 13-415.1.ABC.3 TANDEM WIRING.
 PLEASE SEE 13-415.1.AB.1 FOR
 CALCULATIONS.
  
 7)NOTE: OK, HOWEVER SEE LOAD IS SHOWN
 BEING DIVIDED BY 208V? PLEASE SEETHIS IS
 A 120V CIRCUIT, PLEASE ADJUST.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE TH REQUIRED SIGN
 CIRCUIT PER 600.5.PLEASE KNOW, THIS SIGN
 CIORCUIT MAY NOT FEED OTHER AREAS.
  
 8)NOTE: OK, HOWEVER PLEASE SEE THESE
 LOADS DO NOT CORRELATE WITH THE CIRCUITS
 AND LOADS SHOWN ON PANEL SCHEDULES, AND
 THE LOADS ARE ALSO SHOWN AT 208V AND NOT
 120V.??
 PLEASE ADJUST.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY "SHOW" WINDOW
 LIGHTING IS BEING SHOWN AS SIGN
 CIRCUITS?
 PLEASE SEE 220.12
  
 9)NOTE:NO, PLEASE SEE NOTES ABOVE, AS
 THE LOADS WILL CHANGE AND THE LOADS
 SHOWN DO NOT INDICATE ALL CONTINOUS
 LOADS AT 125%.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS, AND SHOW ALL CONTINUOUS
 LOADS AT 125%.
 PLEASE CORRELATE KNOWN RECEPT LOADS WITH
 LOADS SHOWN ON PANEL SCHEDULE.
 220.3,220.10,220.11,220.13,215.3,230.42
 ETC
  
 10)NOTE: OK, AS THE SERVICE IS BEING
 SHOWN AS EXISTING.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE GROUNDING ELECTRODE
 SYSTEM, PLEASE PROVIDE DETAIL PER NEC 250.50,250.52.
  
 11)NOTE: OK.
  
 ***** NEW NOTES ****
  
 12) NOTE: PLEASE CORRELATE RISER WHICH
 INDICATES 350A OCP AND LOAD NOTES
 MENTIONS FUSES @ 300A??
 106.1.2 FBC ADMIN SECT,
  
 13) NOTE: PLEASE SEE 700.12E AS THE EM/
 EXT LTS ARE REQUIRED TO BE FED FROM THE
 NORMAL BRANCH CIRCUITS FEEDING LOCAL
 LIGHTING.
  
 14) NOTE: PLEASE SEE THAT NEW ELECTRICAL
 PANEL LOCATION SHALL INDICATE THIS AA AN ELECTRICAL
 ROOM, NO STORAGE.
 110.26.240.24, 408.7 ETC.
  
 15) NOTE: PLEASE SEE FS 553.80(2)(B)
 WITH RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT CODE COMPLIANT COMMENTS. THIS IS
 ONLY GIVEN ANOTICE AT THIS TIME.
  
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-02 Cont ID  
Sent By dpalmer Date 2006-03-02 Time 12:10 Rev Time 0.00
Received By dpalmer Date 2006-03-01 Time 21:01 Sent To  
Notes
2006-03-02 00:00:00********UNSAT ***********
  
 1)NOTE: PLEASE SEE THE SEAL FOR ENGINEER
 STILL CONTAINS THE WORDING OF
 "CERTIFICATE". PLEASE KNOW, FAC
 61G1-16.001 WHICH REQUIRED THE WORDING
 IN ALL SEALS TO BE CHANGED TO "LICENSE"
 PLEASE KNOW THIS RULING BY THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS WAS
 PASSED ON FEB 5, 2004. AN EXTENSION WAS
 GRANTED TO THE DATE OF 12/31/05,
 WHERE-AS OF JAN 1ST, 2006 SEALS WERE NO
 LONGER ACCEPTABLE WITH THE WORDING OF "CERTIFICATE".
 PLEASE OBTAIN NEW SEAL.
  
 2)NOTE: PLEASEBE SURE ALL CURRENT
 CODES FOR THE FOLLOWING ARE REFERENCED
 ON ELECTRICAL PLANS.
 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72.
 PLEASE SEE SHEETSWHICH REFLECT THE
 2001 FBC.
 PLEASEKNOW, THE STATE OF FLORIDA
 ADOPTED THE 2004 FBC ON OCT 1ST, 2005
  
 3)NOTE: PLEASE SEE PLANS MENTIONS THE
 2005 NEC.
  
 4)NOTE: PLEASE PROVIDE THE AIC RATINGS
 FOR THE NEW FUSES FOR MAINS. 110.9,215.5
  
 5)NOTE: PLEASE SHOW ALL PANEL AND
 SERVICE LOCATIONS. PLEASE VERIFY IF ALL
 MAINS FOR THE ENTIRE BLDG ARE GROUPED.
 230.72
 RISER SHOWS WHAT APPEARS TO BE A SINGLE
 METER EXISTING SERVICE WITH NEW MAIN
 ADDED?, IS THIS THE SERVICE FOR THE
 ENTIRE BLDG?
 PLEASE SHOW AND VERIFY THE ENTIRE
 SERVICE.
  
 6)NOTE: PLEASE SEE FBC CHAPTER 13, FOR
 THE NEW REQUIREMENTS FOR COMMERCIAL
 BLDGS.
 PLEASE SEE A WORST CASE CALCULATION TO
 BE SHOWN FOR VOLTAGE DROP TO MEET THE
 MIN AS SET FORTH IN 13-413.1ABC.1
 PLEASE SEE 13-415.1.ABC.1 & .2 FOR
 INTERIOR LIGHTING SHUTOFF, SPACE
 LIGHTING CONTROLS REQUIRED.PLEASE
 PROVIDE SCHEDULING.
 PLEASE SEE 13.415.1.ABC.1.4 FOR EXTERIOR
 LTS, AND TYPE OF TIME CLOCK REQUIRED .
 PLEASE SEE 13-415.1.ABC.3 TANDEM WIRING.
 PLEASE SEE 13-415.1.AB.1 FOR
 CALCULATIONS.
  
 7)NOTE: PLEASE INDICATE TH REQUIRED SIGN
 CIRCUIT PER 600.5.PLEASE KNOW, THIS SIGN
 CIRCUIT MAY NOT FEED OTHER AREAS.
  
 8)NOTE: PLEASE VERIFY "SHOW" WINDOW
 LIGHTING IS BEING SHOWN AS SIGN
 CIRCUITS?
 PLEASE SEE 220.12
  
 9)NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS, AND SHOW ALL CONTINUOUS
 LOADS AT 125%.
 PLEASE CORRELATE KNOWN RECEPT LOADS WITH
 LOADS SHOWN ON PANEL SCHEDULE.
 220.3,220.10,220.11,220.13,215.3,230.42
 ETC
  
 10)NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM, PLEASE PROVIDE DETAIL PER NEC 250.50,250.52.
  
 11)NOTE: PLEASE PROVIDE ROOM AND ARE
 DESIGNATIONS ON PLANS.
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
  
 ** PLEASE COMPLETETLY REMOVED ANY
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-03-01 00:00:00IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-10-23 Cont ID  
Sent By mawillia Date 2006-10-23 Time 15:21 Rev Time 0.00
Received By mawillia Date 2006-10-23 Time 15:21 Sent To  
Notes
2006-10-23 15:41:22*****UNSAT****
  
  
  
  
 RESPONSES TO PREVIOUS FIRE PLAN REVIEW COMMENT ( #1
 THRU #5 ) RECIEVED AS:
  
 1.)PLEASE DETAIL ON THE PLANS THAT THIS COMMENT HAS
 BEEN ADDRESSED.
  
 2.)OK
  
 3.)OK
  
 4.)SO NOTED.
  
 5.)INTERIOR FINISH FOR WALLS AND CEILINGS IN EXIT
 CORRIDOR SHALL BE CLASS "A" OR CLASS "B".
  
 PLEASE ADDRESS NEW COMMENT ( #6 );
  
 6.)ON SHEET LS-1 IN THE LIFE SAFETY SUMMARY, IT
 STATES THAT THIS IS A REQUIRED SPRINKLERED BUILDING
 WHICH CONTRADICTS TO THE INFORMATION THAT WAS SUBMITTED
 ON THE PLAN/PERMIT APPLICATION AS BEING UNSPRINKLERED.
 PLEASE EXPLAIN AND/OR VERIFY.
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-03-24 Cont ID  
Sent By mwennerg Date 2006-03-24 Time 14:35 Rev Time 0.00
Received By mwennerg Date 2006-03-24 Time 14:35 Sent To  
Notes
2006-03-24 00:00:00******DENIED******
  
 1) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 2) LIFE SAFETY SHALL BE IN COMPLIANCE
 WITH NFPA 101, 2003 EDITION.
  
 3) SHT E-2 ILLUSTRATES FIRE ALARM
 DEVICES, AND SHT LS-1 INDICATES THAT
 THERE IS NO FIRE ALARM. PLEASE ADVISE
 AND MAKE APPROPRIATE CORRECTION.
  
 3) WILL THIS PROJECT HAVE IT'S OWN FIRE
 ALARM SYSTEM, OR WILL IT BE TIED INTO AN
 EXISTING SYSTEM. IF A SEPARATE PANEL IS
 INSTALLED, AND THE BUILDING IS FULLY
 FIRE SPRINKLERED, THE SYSTEM IS REQUIRED
 TO BE UL CERTIFIED FOR CENTRAL STATION
 SERVICE. APPROPRIATE DOCUMENTATION WILL
 BE REQUIRED PRIOR TO OR AT THE TIME OF
 THE FIRE ALARM FINAL INSPECTION.
  
 4) SEPARATE SHOP DRAWINGS ARE REQUIRED
 FOR FIRE SPRINKLER AND OR FIRE ALARM
 SYSTEMS OR REMODEL.
  
 5) PLEASE INDICATE THE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 6) WHERE PROVIDED AND AS PART OF A FIRE
 ALARM SYSTEM, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM WHEN
 ACTIVATED IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-20 Cont ID  
Sent By adarroug Date 2007-01-20 Time 15:19 Rev Time 0.00
Received By adarroug Date 2007-01-20 Time 15:19 Sent To  
Notes
2007-01-31 15:24:44TO "COMM" BD#4
2007-01-20 15:20:23WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-11 Cont ID  
Sent By adarroug Date 2006-09-11 Time 09:30 Rev Time 0.00
Received By adarroug Date 2006-09-11 Time 09:30 Sent To  
Notes
2006-09-15 00:00:00TO "COMM" BD#41
2006-09-11 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-20 Cont ID  
Sent By alange Date 2006-04-20 Time 08:09 Rev Time 0.00
Received By alange Date 2006-01-30 Time 15:52 Sent To  
Notes
2006-03-01 00:00:00TO "COMM" BD#44
2006-01-30 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-02-21 Cont ID  
Sent By hmoser Date 2007-02-21 Time 13:29 Rev Time 0.00
Received By hmoser Date 2007-02-21 Time 13:20 Sent To  
Notes
2007-02-21 13:28:21PLAN DENIED
 PLEASE PROVIDE SUPPLY AND RETURN AIR GRILL SIZE ON
 PLANS .
 PLEASE REFER TO SECTION 307.2.3 AUXILIARY AND SECONDARY
 DRAIN SYSTEMSFBC(M) 2004
 PLEASE REFER TO SECTION 606 SMOKE DETECTION SYSTEM
 CONTROL.FBD(M) 2004
 PLEASE REFER TO SECTION 606.4.1 SUPERVISON .FBC(M)
 2004
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-14 Cont ID  
Sent By hmoser Date 2006-10-14 Time 13:08 Rev Time 0.00
Received By hmoser Date 2006-10-14 Time 11:43 Sent To  
Notes
2006-10-14 13:27:521)PLEASE PROVIDE DUCTWORK SIZE AND GRILL SIZE WITH
 CFM ON PLANS.
 2)PLESE REFER TO SECTION 606 FBC (M) 2004 SMOKE
 DETECTION SYSTEM CONTROL.
 3)PLEASE REFER TO SECTION 606.4.1 SUPERVISION . 4)
 PLEASE PROVIDE DETAIL ON CURB TIEDOWN TO ROOF ON THE
 PLANS.
 5)PLEASE PROVIDE RTU #1 & #2 TIEDOWN TO CURB ON THE
 PLANS.
 6)PLEASE REFER TO SECTION 307 FBC (M) 2004 CONDENSATE
 DISPOSAL.
 7)PLEASE REFER TO SECTION 307.2.3 AUXILIARY AND
 SECONDARY DRAIN SYSTEM.
 8)PLEASE REFER TO TABLE 403.3 REQUIRED OUTDOOR
 VENTILATION.
 9)PLEASE REFER TO NOTES PAGE A/C 1 AND UPDATE TO 2001
 CODE.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hmoser Date 2006-03-23 Time 08:47 Sent To  
Notes
2006-03-23 00:00:00PLANS ARE NOT COMPLETE.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-02-24 Cont ID  
Sent By pschmitz Date 2007-02-24 Time 12:59 Rev Time 0.00
Received By pschmitz Date 2007-02-24 Time 11:43 Sent To  
Notes
2007-02-24 13:00:51PROVISO:
 FIELD INSPECTOR TO CHEECK FOR PUBLIC ACCESS TO REST
 ROOMS

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-01 Cont ID  
Sent By pschmitz Date 2006-04-01 Time 13:38 Rev Time 0.00
Received By pschmitz Date 2006-04-01 Time 13:38 Sent To  
Notes
2006-04-01 00:00:00 
 PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
 UNSAT
  
 1) SHT P-1 SHOW HOW THE REST ROOM
 FACILITIES LOCATED IN THE STORAGE AREA,
 WILL COMPLY WITH, ACCESSILLE ROUTE
 11-4.3 ACCESSIBLE ROUTE.
 11-4.3.1 GENERAL.
 ALL WALKS, HALLS, CORRIDORS, AISLES,
 SKYWALKS, TUNNELS, AND OTHER SPACES THAT
 ARE PART OF AN ACCESSIBLE ROUTE SHALL
 COMPLY WITH SECTION 11-4.3.
 11-4.3.2 LOCATION.
 (1) AT LEAST ONE ACCESSIBLE ROUTE WITHIN
 THE BOUNDARY OF THE SITE SHALL BE
 PROVIDED FROM PUBLIC TRANSPORTATION
 STOPS, ACCESSIBLE PARKING, AND
 ACCESSIBLE PASSENGER LOADING ZONES, AND
 PUBLIC STREETS OR SIDEWALKS TO THE
 ACCESSIBLE BUILDING ENTRANCE THEY SERVE.
 THE ACCESSIBLE ROUTE SHALL, TO THE
 MAXIMUM EXTENT FEASIBLE, COINCIDE WITH
 THE ROUTE FOR THE GENERAL PUBLIC.
 (2) AT LEAST ONE ACCESSIBLE ROUTE SHALL
 CONNECT ACCESSIBLE BUILDINGS,
 FACILITIES, ELEMENTS, AND SPACES THAT
 ARE ON THE SAME SITE.
 11-4.3.3 WIDTH.
 THE MINIMUM CLEAR WIDTH OF AN ACCESSIBLE
 ROUTE SHALL BE 36 INCHES (915 MM) EXCEPT
 AT DOORS (SEE SECTIONS 11-4.13.5 AND
 11-4.13.6). IF A PERSON IN A WHEELCHAIR
 MUST MAKE A TURN AROUND AN OBSTRUCTION,
 THE MINIMUM CLEAR WIDTH OF THE
 ACCESSIBLE ROUTE SHALL BE AS SHOWN IN
 FIGURE 11-7(A) AND FIGURE 11-7(B).
 2) SEC 608 BACK FLOW PREVENTER REQUIRED
 ON WATER SERVIVCE,
 LOCAL ORDINANCE #2853-95
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  

Review Stop Z ZONING
Rev No 1 Status F Date 2007-02-21 Cont ID  
Sent By jroach Date 2007-02-11 Time 13:59 Rev Time 0.00
Received By jroach Date 2007-02-11 Time 13:59 Sent To  
Notes
2007-02-11 14:00:48***ZONING REVIEW NOT REQUIRED***
  
 SITE WORKED COVERED UNDER PERMIT #06011121.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.