2006-09-19 00:00:00 | ********UNSAT 2ND REVIEW ********* |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW STILL NEED TO BE ADDRESSED, ALONG |
| WIHT NEW COMMENTS BASED ON PLANS |
| SUBMITTED. |
| PLEASE SEE NOTES BELOW ARE TAKEN |
| DIRECTLY FROM PREVIOUS REVIEW AND NEW |
| NOTES ARE ADDED TO THE BOTTOM. |
| |
| 1)NOTE: OK. |
| |
| 2)NOTE:OK, MOST CODES ADDED, HOWEVER |
| PLEASE BE SURE THE ELECTRICAL PLANS ALSO |
| STATE THE 2004 FBC. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASEBE SURE ALL CURRENT |
| CODES FOR THE FOLLOWING ARE REFERENCED |
| ON ELECTRICAL PLANS. |
| 2002 NFPA-70, 2003 NFPA-101, 2002 |
| NFPA-72. |
| PLEASE SEE SHEETSWHICH REFLECT THE |
| 2001 FBC. |
| PLEASEKNOW, THE STATE OF FLORIDA |
| ADOPTED THE 2004 FBC ON OCT 1ST, 2005 |
| |
| 3)NOTE: OK. |
| |
| 4)NOTE:NO, PLEASE VERIFY AS THE |
| DISONNECT IS BEING NOTED AS BEING FUSED |
| AND 10K IS NOT COMMEN FOR THE AIC |
| RATINSGS FOR FUSES. PLEASE SEE NEW |
| COMMENTS ALSO. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE PROVIDE THE AIC RATINGS |
| FOR THE NEW FUSES FOR MAINS. 110.9,215.5 |
| |
| 5)NOTE: OK. SEE NEW NOTES. |
| |
| 6)NOTE: NO, PLEASE SEE NO SYSTEM WAS |
| SUBMITTED AND SHOWN AS REQUIRED. A TC |
| NOTED FOR LTS, DOES NOT GIVE ALL |
| INFORMATION AS NEEDED. PLEASE PROVIDE |
| THE SYSTEM, SCHEDULING, ALL OVER-RIDES |
| ETC. PLEASE SEE PLANS DO NOT INDICATE |
| ANY OVER-RIDE DEVICES, MAX TIMES |
| PERMITTED ON THE DEVICES WHICH MAY BE |
| INSTALLED. |
| PLEASE SEE TAKING THE SECTIONS OF THE |
| CODE AND QUOTING THE CODE IS NOT |
| ACCEPTABLE IN LEIU OF MIN DESIGNS |
| REQUUIRED ON PLANS FOR THE TECHNICAL REQUIREMENTS. |
| FBC 106.1, ADMIN SECT. |
| NO ENERGY CALCULATIONS, NO LIGHTING |
| POWER ALLOWANCES ETC. |
| PLEASE SEE NOTES BELOW. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE FBC CHAPTER 13, FOR |
| THE NEW REWUIREMENTS FOR COMMERCIAL |
| BLDGS. |
| PLEASE SEE A WORST CASE CALCUALTION TO |
| BE SHOWN FOR VOTLAGE DROP TO MEET THE |
| MIN AS SET FORTH IN 13-413.1ABC.1 |
| PLEASE SEE 13-415.1.ABC.1 & .2 FOR |
| INTERIOR LIGHTING SHUTOFF, SPACE |
| LIGHTING CONTROLS REQUIRED.PLEASE |
| PROVIDE SCHEDULING. |
| PLEASE SEE 13.415.1.ABC.1.4 FOR EXTERIOR |
| LTS, AND TYPE OF TIME CLOCK REQUIRED . |
| PLEASE SEE 13-415.1.ABC.3 TANDEM WIRING. |
| PLEASE SEE 13-415.1.AB.1 FOR |
| CALCULATIONS. |
| |
| 7)NOTE: OK, HOWEVER SEE LOAD IS SHOWN |
| BEING DIVIDED BY 208V? PLEASE SEETHIS IS |
| A 120V CIRCUIT, PLEASE ADJUST. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE INDICATE TH REQUIRED SIGN |
| CIRCUIT PER 600.5.PLEASE KNOW, THIS SIGN |
| CIORCUIT MAY NOT FEED OTHER AREAS. |
| |
| 8)NOTE: OK, HOWEVER PLEASE SEE THESE |
| LOADS DO NOT CORRELATE WITH THE CIRCUITS |
| AND LOADS SHOWN ON PANEL SCHEDULES, AND |
| THE LOADS ARE ALSO SHOWN AT 208V AND NOT |
| 120V.?? |
| PLEASE ADJUST. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE VERIFY "SHOW" WINDOW |
| LIGHTING IS BEING SHOWN AS SIGN |
| CIRCUITS? |
| PLEASE SEE 220.12 |
| |
| 9)NOTE:NO, PLEASE SEE NOTES ABOVE, AS |
| THE LOADS WILL CHANGE AND THE LOADS |
| SHOWN DO NOT INDICATE ALL CONTINOUS |
| LOADS AT 125%. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SUBMIT COMPLETE LOAD |
| CALCULATIONS, AND SHOW ALL CONTINUOUS |
| LOADS AT 125%. |
| PLEASE CORRELATE KNOWN RECEPT LOADS WITH |
| LOADS SHOWN ON PANEL SCHEDULE. |
| 220.3,220.10,220.11,220.13,215.3,230.42 |
| ETC |
| |
| 10)NOTE: OK, AS THE SERVICE IS BEING |
| SHOWN AS EXISTING. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE GROUNDING ELECTRODE |
| SYSTEM, PLEASE PROVIDE DETAIL PER NEC 250.50,250.52. |
| |
| 11)NOTE: OK. |
| |
| ***** NEW NOTES **** |
| |
| 12) NOTE: PLEASE CORRELATE RISER WHICH |
| INDICATES 350A OCP AND LOAD NOTES |
| MENTIONS FUSES @ 300A?? |
| 106.1.2 FBC ADMIN SECT, |
| |
| 13) NOTE: PLEASE SEE 700.12E AS THE EM/ |
| EXT LTS ARE REQUIRED TO BE FED FROM THE |
| NORMAL BRANCH CIRCUITS FEEDING LOCAL |
| LIGHTING. |
| |
| 14) NOTE: PLEASE SEE THAT NEW ELECTRICAL |
| PANEL LOCATION SHALL INDICATE THIS AA AN ELECTRICAL |
| ROOM, NO STORAGE. |
| 110.26.240.24, 408.7 ETC. |
| |
| 15) NOTE: PLEASE SEE FS 553.80(2)(B) |
| WITH RESPECT TO DESIGN PROFESSIONALS AND |
| REPEAT CODE COMPLIANT COMMENTS. THIS IS |
| ONLY GIVEN ANOTICE AT THIS TIME. |
| |
| |
| ** PLEASE SEE ANY OTHER POSSIBLE |
| COMMENTS FROM OTHER TRADES WHICH MAY |
| AFFECT ELECTRICAL PLANS. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |