Plan Review Details - Permit 06011121
Plan Review Stops For Permit 06011121
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2006-05-08 Cont ID  
Sent By lursu Date 2006-05-08 Time 13:37 Rev Time 0.00
Received By lursu Date 2006-05-05 Time 08:33 Sent To  
Notes
2006-05-08 00:00:00NO CORRECTIONS NEEDED.
2006-05-05 00:00:00PROJECT UNDER REVIEW:
 - OWNER CORRECTION ON THE APPLICATION
 - UNIT # ?

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-01-23 Cont ID  
Sent By jwitmer Date 2008-01-23 Time 14:49 Rev Time 0.55
Received By jwitmer Date 2008-01-23 Time 14:49 Sent To PC
Notes
2008-01-23 14:50:00REVISION# 1,STEEL ROOF

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-11-30 Cont ID  
Sent By lmartine Date 2007-11-30 Time 12:07 Rev Time 0.00
Received By lmartine Date 2007-11-30 Time 12:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-10-28 Cont ID  
Sent By lmartine Date 2007-10-28 Time 14:19 Rev Time 0.00
Received By lmartine Date 2007-10-28 Time 14:19 Sent To  
Notes
2007-10-28 14:24:37PROVIDE 2 COPIES SIGNED AND SEALED FLORIDA ENERGY
 EFFICIENCY REPORTS.
  
 SUBMIT APPROVED PLANS TO PALM BEACH COUNTY IMPACT FEE
 OFFICE FOR REVIEW AND STAMPING, RECEIPT WILL BE
 REQUIRED.
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-10-01 Cont ID  
Sent By lmartine Date 2007-10-01 Time 12:45 Rev Time 0.00
Received By lmartine Date 2007-10-01 Time 12:45 Sent To  
Notes
2007-10-01 14:39:09BUILDING REVIEW COMMENTS
  
  
  
  
 1)
 PROVIDE CALCULATED FIRE RESISTANCE OR AN APPROVED
 TESTED ASSEMBLY FOR YOUR (4 HR) FIRE WALL.
 2)
 PROVIDE UPDATED FLORIDA ENERGY EFFICIENCY REPORT.
 3)
 HAVE BOTH SETS OF DRAWINGS STAMPED BY PALM BEACH
 COUNTY IMPACT FEE OFFICE AND PROVIDE COPY OF PAID
 RECEIPT.
 4)
 A RECORDED NOTICE OF COMMENCEMENT WILL BE REQUIRED AT
 TIME OF PERMIT RELEASE.
  
  
  
  
  
  
  
 L. MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-02-23 Cont ID  
Sent By jwitmer Date 2007-02-23 Time 07:41 Rev Time 2.22
Received By jwitmer Date 2007-02-23 Time 07:41 Sent To  
Notes
2007-02-23 07:45:57BUILDING PLAN REVIEW
 PERMIT: 06011121
 ADD: 2100 45TH ST. SUITE#
 CONT: ITASCA CONSTRUCTION
 TEL: (561)241-4999
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
  
 *****BUILDING, PLANS APPEAR TO BE CODE COMPLIANT , ONCE
 PLANS HAVE BEEN REVIEWED BY PALM BEACH COUNTY IMPACT
 FEE OFFICE, THEN THE PLANS CAN BESTAMPED!!!***
  
  
  
  
  
 1) COMPLIED.
  
 2A) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2B) COMPLIED.
  
 3) BUILDING PROVISO:
 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 4)BUILDING PROVISO:
 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 5)COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) PRODUCT APPROVALS
 A-E)COMPLIED.
  
 9F) ROOFING ASSEMBLIES: AT THE THIRD REVIEW NO ROOFING
 PRODUCT APPROVALS WERE SUBMITTED TO BE UNDER A SEPERATE
 PERMIT , REVIEW WITH ASSOCIATED FEES.
  
 10) COMPLIED.
  
 11A) COMPLIED.
 11B) COMPLIED.
 11C)
  
 12)COMPLIED..
  
 13) COMPLIED.
  
 14)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 15) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER CBO
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-02-23 Cont ID  
Sent By jwitmer Date 2007-02-23 Time 07:13 Rev Time 2.22
Received By jwitmer Date 2007-02-23 Time 07:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-03 Cont ID  
Sent By jwitmer Date 2006-10-03 Time 10:04 Rev Time 3.33
Received By jwitmer Date 2006-10-03 Time 09:56 Sent To  
Notes
2006-10-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06011121
 ADD: 2100 45TH ST. SUITE#
 CONT: ITASCA CONSTRUCTION
 TEL: (561)241-4999
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1A)2ND REQUEST, PLEASE PROVIDE WHAT
 SUITE NUMBER WORK WILL COVER UNDER THIS
 PERMIT ON THE PERMIT APPLICATION.
  
 1B) SHEET SP-1 INDICATES NOTES TO
 PROVIDE CURB CUTS AND HANDICAPPED CCESS
 AISLES ALONG FRONTAGE OF BUILDING, IS
 THIS ALSO COVERED UNDER THIS
 PERMIT?PLEASE PROVIDE THIS INFORMATION
 ON THE PERMIT APPLICATION UNDER
 DESCRIPTION OF WORK.
  
 1C) SHEET SP-1 ALSO INDICATES ALONG 45TH
 STREET THE DRIVE APPROACH FOR THIS
 PROPERTY BEING WIDENED, IS THIS WORK
 ALSO TO BE INCLUDED UNDER THIS PERMIT?
 PLEASE PROVIDE THIS INFORMATION ON THE
 PERMIT APPLICATION UNDER DESCRIPTION OF
 WORK
  
 2A) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2B) COMPLIED.
  
 3) BUILDING PROVISO:
 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 4)BUILDING PROVISO:
 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY,
 DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 5) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 5A) COMPLIED.
 5B) COMPLIED.
 5C) 2ND REQUEST, TYPE OF CONSTRUCTION AS
 DEFINED IN CHAPTER 6 AND TABLE 601.
 5D) OCCUPANT LOAD.
 5E) IF AN AUTOMATIC FIRE SPRINKLER
 SYSTEM IS PROVIDED?
 5F) IF AN AUTOMATIC FIRE SPRINKLER
 SYSTEM IS REQUIRED?
 5G) ANY SPECIAL STIPULATIONS &
 CONDITIONS OF THE BUILDING PERMIT.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) PRODUCT APPROVALS
 A) PANEL WALL COMPLIED.
 B) MULLIONS, COMPLIED.
 C) GLAZED SWING DOORS, COMPLIED
 D) HOLLOW METAL DOORS, COMPLIED.
 E) STORM SHUTTERS, COMPLIED.
 F) ROOFING ASSEMBLIES:
 SHEET 21 OF NOA, SUBSYSTEM IS NOT
 HIGHLIGHTED, SEE GENERAL LIMITATION# 7
 FOR LOW PSF.ENHANCED FASTENING ALLOWED
 PROVIDE CALCULATIONS FOR ENHANCED
 FASTENING AS PER RAS 117.
  
 10) COMPLIED.
  
 11A) COMPLIED.
 11B) COMPLIED.
 11C)
  
 12) 2ND REQUEST, EXISTING BUILDING CODE
 2004, 902.2 THE QUESTION 5C IS BASICALLY
 THE SAME QUESTION, WHAT IS THE MINIMUM
 BUILDING TYPE, WITH AREA INCREASES,
 FRONTAGE, AND OR FIRE SPRINKLERS?
 AREA LIMITATION. NO ADDITION SHALL
 INCREASE THE AREA OF AN EXISTING
 BUILDING BEYOND THAT PERMITTED UNDER THE APPLICABLE
 PROVISIONS OF CHAPTER 5.
  
 13) 2ND REQUEST13-101.1.2 ADDITIONS.
 ADDITIONS TO EXISTING COMMERCIAL
 BUILDINGS ARE CONSIDERED NEW BUILDING
 CONSTRUCTION AND SHALL COMPLY WITH
 SUBCHAPTER 13-4 OF THIS CODE AS ALLOWED
 IN SECTION 101.1.1 .
 ADDITIONS TO EXISTING NONRESIDENTIAL
 BUILDINGS THAT ARE UNABLE TO COMPLY WITH
 CODE REQUIREMENTS FOR THE ADDITION ALONE
 MAY COMPLY WITH THE CODE BY BRINGING THE
 ENTIRE BUILDING INTO COMPLIANCE WITH THE REQUIREMENTS
 FOR NEW BUILDINGS.
  
 13-101.1.3 RENOVATIONS.
 RENOVATED COMMERCIAL BUILDINGS SHALL,
 WHEN APPLICABLE (SEE SECTION 202 ),
 COMPLY WITH THE PRESCRIPTIVE
 REQUIREMENTS CONTAINED IN FORM 400 C OR
 WITH METHOD B OF SUBCHAPTER 13-4 FOR
 INSULATION, HVAC SYSTEMS, LIGHTING,
 WATER HEATING SYSTEMS AND EXTERIOR
 ENVELOPE COMPONENTS BEING RETROFITTED OR REPLACED.
 SHELL BUILDING . A COMMERCIAL BUILDING
 THAT IS PERMITTED PRIOR TO DESIGN
 COMPLETION OR WHICH WILL BE FINISHED IN
 SECTIONS AT A TIME AFTER CONSTRUCTION OF
 THE SHELL.
  
 SHELL
 13-400.2.A.2 SHELL BUILDINGS.
 SHELL BUILDINGS SHALL COMPLY WITH THIS
 CODE BY METHOD B OR METHOD C. ONCE ALL ENERGY-RELATED
 DESIGN PARAMETERS ARE
 KNOWN, A METHOD A CALCULATION MAY BE
 RESUBMITTED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-24 Cont ID  
Sent By jwitmer Date 2006-04-24 Time 11:40 Rev Time 0.00
Received By jwitmer Date 2006-05-04 Time 13:28 Sent To  
Notes
2006-04-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06011121
 ADD: 2100 45TH ST. SUITE#
 CONT: ITASCA CONSTRUCTION
 TEL: (561)241-4999
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) PLEASE PROVIDE WHAT SUITE NUMBER
 WORK WILL COVER UNDER THIS PERMIT.
  
 1B) SHEET SP-1 INDICATES NOTES TO
 PROVIDE CURB CUTS AND HANDICAPPED CCESS
 AISLES ALONG FRONTAGE OF BUILDING
 ,ISTHIS ALSO COVERED UNDER THIS PERMIT?
  
 1C) SHEET SP-1 ALSO INDICATES ALONG 45TH
 STREET THE DRIVE APPROACH FOR THIS
 PROPERTY BEING WIDENED, IS THIS WORK
 ALSO TO BE INCLUDED UNDER THIS PERMIT?
  
 2A) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2B) THE WRONG OWNER INFORMATION IS
 LISTED ON THE PERMIT APPLICATION. IF
 RECENTLY SOLD PROVIDE UPDATED
 INFORMATION FOR OWNERSHIP, OTHERWISE
 CORRECT PERMIT APPLICATION TO MATCH NOC.
  
 3) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 4) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 5) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED (2004).
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 -------------------------------------
 G ) SQ. FT. PER FL
 H ) SQ. FT. FOOTPRINT
 I ) SQ. FT. UNDER ROOF (TOTAL)
 J ) OCCUPANT LOAD
 K ) FLOOD ZONE
 L ) FLOOD ELEVATION
 M) WHAT USAGE CLASSIFICATION TO BE USED
 FOR ON THE 2ND FLOOR?
  
 6) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7)1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 8) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) MULLIONS IF NOT PART OF WINDOW
 REPORT
 C) GLASS DOORS
 D)STORM SHUTTERS
 E) ROOFING ASSEMBLIES.
  
 9) PRODUCT APPROVALS SUBMITED ARE FOR
 BOTH LARGE AND REPORTS FOR
 SMALL MISSLE IMPACT GLAZING. GLAZED
 OPENINGS ZERO -30 FT REQUIRE LARGE
 MISSLE IMPACT GLAZING, OR SHUTTERS.
 SINCE THIS IS CONDOS AND A LARGE PROJECT
 IF SHUTTERS ARE TO BE USED APPROVAL FROM
 THE BUILDING OFFIICAL WILL BE REQUIRED.
 SEE THE BUILDING OFFICIALS
 INTERPRETATION OF CODE. SEE QUESTION 13
 & 14 OF INTERPRETATION OF STANDARDS.
 ****************************
 (13) RECOGNIZING SUCH CONCERNS AS
 ABSENTEE OWNERS, OR CASES WHERE LONGER
 TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING
 RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING
 IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
 (13) ANSWER: IN MATTERS CONCERNING
 PUBLIC SAFETY, HEALTH, AND THE GENERAL
 WELFARE NOT SPECIFICALLY ADDRESSED IN
 THE CODE SECTION 104.1* FLORIDA BUILDING
 CODE, 2004 EDITION, PROVIDES THE ABILITY
 FOR THE BUILDING OFFICIAL TO IMPLEMENT
 REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF
 EXISTING & NEW BUILDINGS.
 IN ORDER TO ASSURE THE SECURING OF
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION
 PLANS MUST BE SUBMITTED BY THE PROPERTY
 OWNERS OR MANAGING AGENTS FOR REVIEW BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ANY SUCH PLAN SHALL INCLUDE, AT A
 MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS (SAID PARTIES MUST BE LOCATED
 WITHIN PALM BEACH COUNTY), TOTAL NUMBER
 OF OPENINGS TO BE PROTECTED AND TOTAL
 TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN TWELVE (12) HOURS OR
 LESS OF THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH.
 PROVISIONS IN THE BUILDING CODES
 (AND THIS STANDARD) ARE NOT INTENDED TO
 PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE
 BUILDING OFFICIAL TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE
 PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON
 A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATE.
  
 (14)ARE REMOVABLE STORM PANELS
 APPROPRIATE FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES?
 (14) ANSWERS: NO, EXCEPT ON THE
 GROUND FLOOR. ON COMMERCIAL AND
 MULTI-UNIT RESIDENTIAL STRUCTURES, ABOVE
 THE FIRST LEVEL, IMPACT RESISTANT
 GLAZING OR PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL BE INSTALLED.
 PERMANENTLY AFFIXED PROTECTIVE DEVICES
 SHALL REQUIRE THE WRITTEN APPROVAL OF
 THE BUILDING OFFICIAL.
 **************************
 10) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 ASCE7-95 WRONG WIND DESIGN, 2004 FBC
 USES ASCE7 -02.
  
 11)S-1
 11A) UPDATE BUILDING CODE TO 2004 FBC
 BUILDING, 2004 EXISTING BUILDING CODE.
  
 11B) UPDATE ACI-95 TO ACI- 315-02
  
 11C) STRUCTURAL NOTES (H) REFERS TO SFBC
 2404.2 CORRECT TO 1802.2.1 QUESTIONABLE
 SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE
 SOIL IS IN DOUBT, OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH
 1802.6 .
 PROVIDE SOILS REPORT, ORIGINAL 2 SETS.
  
 12) EXISTING BUILDING CODE 2004, 902.2
 AREA LIMITATION. NO ADDITION SHALL
 INCREASE THE AREA OF AN EXISTING
 BUILDING BEYOND THAT PERMITTED UNDER THE
 APPLICABLE PROVISIONS OF CHAPTER 5.
  
 13) 13-101.1.2 ADDITIONS.
 ADDITIONS TO EXISTING COMMERCIAL
 BUILDINGS ARE CONSIDERED NEW BUILDING
 CONSTRUCTION AND SHALL COMPLY WITH
 SUBCHAPTER 13-4 OF THIS CODE AS ALLOWED
 IN SECTION 101.1.1 .
 ADDITIONS TO EXISTING NONRESIDENTIAL
 BUILDINGS THAT ARE UNABLE TO COMPLY WITH
 CODE REQUIREMENTS FOR THE ADDITION ALONE
 MAY COMPLY WITH THE CODE BY BRINGING THE
 ENTIRE BUILDING INTO COMPLIANCE WITH THE
 REQUIREMENTS FOR NEW BUILDINGS.
  
 13-101.1.3 RENOVATIONS.
 RENOVATED COMMERCIAL BUILDINGS SHALL,
 WHEN APPLICABLE (SEE SECTION 202 ),
 COMPLY WITH THE PRESCRIPTIVE
 REQUIREMENTS CONTAINED IN FORM 400 C OR
 WITH METHOD B OF SUBCHAPTER 13-4 FOR
 INSULATION, HVAC SYSTEMS, LIGHTING,
 WATER HEATING SYSTEMS AND EXTERIOR
 ENVELOPE COMPONENTS BEING RETROFITTED OR
 REPLACED.
  
 14) LS-1 NO EXIT LIGHTS OR EMERGENCY
 LIGHTING PROVIDED.
  
 15) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-09-25 Cont ID  
Sent By dpalmer Date 2007-09-25 Time 15:08 Rev Time 0.00
Received By dpalmer Date 2007-09-25 Time 15:08 Sent To B
Notes
2007-09-25 15:09:13N EW SHEETS, STAMPED ELECTRICAL PLANS.
 ROUTED BY LUIS MARTINEZ, SENT BACK TO LUIS MARTINEZ.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-06-23 Cont ID  
Sent By dpalmer Date 2007-06-23 Time 16:08 Rev Time 0.00
Received By dpalmer Date 2007-06-23 Time 15:55 Sent To  
Notes
2007-07-23 13:39:59UPDATED STATUS, AS OF 7/18, CALCS ARE FOR SHELL
 ESTIMATION.(METHOD B)
2007-06-23 16:08:45 
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-02-03 Cont ID  
Sent By dpalmer Date 2007-02-03 Time 17:52 Rev Time 0.00
Received By dpalmer Date 2007-02-03 Time 17:52 Sent To  
Notes
2007-02-03 17:55:16** UNSAT 3RD REVIEW ***
  
 1) NOTE: PLEASE SEE THE SAME NOTE FROM THE PREVIOUS
 REVIEW STANDS AS THE SAME EXACT SHEETS WERE RESUBMITTED
 FOR REVIEW WITHOUT CORRECTIONS MADE.
 PLEASE SEE LS 101 7.8, 7.9 AND NEC 700.12S.
 FBC 106.1.2 , 106.3.5.1.2
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS. THIS IS ONLY GIVEN AS A NOTICE AT THIS
 TIME.
  
 3) NOTE:** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS. PLEASE DO NOT ATTACH ALL
 OLD/VOIDED SHEETS TO THE SAME NEW COMPLETE SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-22 Cont ID  
Sent By dpalmer Date 2006-09-22 Time 18:46 Rev Time 0.00
Received By dpalmer Date 2006-09-22 Time 17:55 Sent To  
Notes
2006-09-22 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE EM LTS AND EXIT LTS
 ARE BEING SHOWN, HOWEVER NOT CIRCUITED
 TO ANYTHING. PLEASE SEE ONE MIN LT
 FIXTURE SHALL BE REQUIRED FROM EACH END
 OF THE TENANT/SHELL SPACE ALONG WTIH THE
 CIRCUITING OF THE EM.EXT LTS TO THE
 LOCAL LIGHT(S).
 700.12E.
 PLEASE INDICATE WHERE THESE FEEDS ARE
 COMING FROM.
  
 DEWEY PALMER.
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-06 Cont ID  
Sent By dpalmer Date 2006-03-06 Time 20:21 Rev Time 0.00
Received By dpalmer Date 2006-03-06 Time 20:10 Sent To  
Notes
2006-03-06 00:00:00********UNSAT ***********
  
 1)NOTE: PLEASE SEEBLDG REVIEW NOTES
 FOR "S" SHEETS. PLEASE SEE THE SEAL FOR
 ENGINEERCONTAINS THE WORDING OF
 "CERTIFICATE". PLEASE KNOW, FAC
 61G1-16.001 WHICH REQUIRED THE WORDING
 IN ALL SEALS TO BE CHANGED TO "LICENSE"
 PLEASE KNOW THIS RULING BY THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS WAS
 PASSED ON FEB 5, 2004. AN EXTENSION WAS
 GRANTED TO THE DATE OF 12/31/05,
 WHERE-AS OF JAN 1ST, 2006 SEALS WERE NO
 LONDER ACCEPTABLE WITH THE WORDING OF
 "CERTIFICATE".
 PLEASE OBTAIN NEW SEAL.
  
 2)NOTE: PLEASEBE SURE ALL CURRENT
 CODES FOR THE FOLLOWING ARE REFERENCED
 ON ELECTRICAL PLANS.
 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72.
 PLEASE SEE SHEETSWHICH REFLECT THE
 2001 FBC.
 PLEASEKNOW, THE STATE OF FLORIDA
 ADOPTED THE 2004 FBC ON OCT 1ST, 2005
  
 3A)NOTE: PLEASE SEE MISSING CERTIFICATE
 OF AUTHORIZATION NUMBER ON "S" SHEETS,
 THIS WILL ALSO BE IN BLDG REVIEW NOTES.
 FS 471.023, FAC 61G15-23.002.
  
 3B) PLEASE SEE IN TWO SETS SHEET "S-1"
 IS SIGNED BY THE ARCHITECT AND ENGINEER
 ON THE SAME SEAL. (THIS SEEMS TO HAVE
 DONE IN ERROR) PLEASE CORRECT.
  
 4)NOTE: PLEASE KNOW, AN ELECTRICAL
 PERMIT /APPLICATION IS REQUIRED FOR
 ELECTRICAL DEMO WORK.
  
 5)NOTE: PLEASE NOTE: THESE PLANS DO NOT
 SEEM TO CORRELATE WITH TENANT FIT UP
 PLANS. PLEASE SEEE THE MAIN ELECTRICAL
 ROOM IS NOT SHOWN, WHICH SEEMS TO BE IN
 PART OF THIS LAYOUT??
  
 6)NOTE: PLEASE SEE FBC CHAPTER 13, FOR
 THE NEW REWUIREMENTS FOR COMMERCIAL
 BLDGS.
 PLEASE PROVIDE ALL PRESCRITIVE
 CALCULATIONS FOPR ENCLOSING NEW AREA.
  
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
  
 ** PLEASE COMPLETETLY REMOVED ANY
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2007-10-23 Cont ID  
Sent By rchokshi Date 2007-10-23 Time 10:23 Rev Time 0.00
Received By rchokshi Date 2007-10-23 Time 10:23 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2007-09-25 Cont ID  
Sent By rchokshi Date 2007-09-25 Time 09:12 Rev Time 0.00
Received By rchokshi Date 2007-09-25 Time 08:51 Sent To  
Notes
2007-09-25 09:12:32WE READ A LETTER FROM JIM WESSON DATED8/21/07.WE
 HAVE NOT RECEIVED THE FOLLOWING INFOYET TO COMPLETE
 THE FILE.
  
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWINGSTHE LOCATION OF DUMPSTER &
 ITS ENCLOSURE & ITS DETAILSPER CITY OF WPB, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. PLEASE PROVIDE THE CALCULATIONS TO DETERMINE THE
 FIRST FLOOR ELEVATION, USING FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, MUST MEET THESE MINIMUM REQUIREMENTS.
 PLEASE SHOW CROWN OF THE ROAD ELEVATION, PARKING LOT
 ELEVATION ON DRAWING.
 4. PLEASE SHOW SITE AREA, PERVIOUS AREA, IMPERVIOUS
 AREA, GREEN AREA, LAKE AREA IF ANY ON THE DRAWING.
 MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST MATCH
 WITH AREAS USED IN STORM WATER QUALITY CALCULATIONS.
 5. PLEASE SHOW ON YOUR DRAWINGS ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM
 WATER PIPES.PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, HOW DID YOU DETERMINE NO OF
 STORM TECHS?? OR LENGTHS OF THE STORMTECHS? PLEASE
 EXPLAINPLEASE SHOW DRY DETENTION/WET DETENTION AREAS
 WITH 100% FULL OF STORM WATER ELEVATION? YOU NEED TO
 SHOW ALL OF THESE IN WATER QUALITY CALCULATIONS.
 6. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST AROUND
 YOUR SITE.
 7. PLEASERESUBMIT A COPY OF SFWMD PERMIT,, A COPY OF
 GEO-TECH REPORTAND A LATESTEST COPY OF STORM STORM
 WATER QUALITY CALCULATIONS THAT YOU PROVIDED AT 45TH
 STREET.
 8. POLLUTION PREVENTION PLANS ARE NOT SEALED AND
 SIGNED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2007-07-20 Cont ID  
Sent By rchokshi Date 2007-07-20 Time 09:21 Rev Time 0.00
Received By rchokshi Date 2007-07-20 Time 08:58 Sent To  
Notes
2007-07-20 09:21:04 
  
 WE ASKED EXPLANATION FOR COMMENTS FOR REV 2, DATED
 2/2/07. THE PERSON WHO RESPONDED COMMENTS FOR REV 2,
 DID NOT MENTIONED HIS/HER NAME ON THE COMMENTS SHEET.
 HE/SHE SAID "NO CHANGES" FROM PREVIOUS REVISION " THIS
 IS A SHELL ONLY"
 IF THIS PERMIT FOR A SHELL ONLY THENYOU STILL NEED TO
 SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
  
  
 BUT WE NEED THE FOLLOWING INFORMATIONFOR THIS PROJECT
 SITE IN ONE OF THE PERMITS YOU APPLIED(WHAT PERMIT # I
 CAN FIND THE FOLLOWING INFO):
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWINGSTHE LOCATION OF DUMPSTER &
 ITS ENCLOSURE & ITS DETAILSPER CITY OF WPB, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, MUST MEET THESE MINIMUM REQUIREMENTS.
 PLEASE SHOW IN YOUR STORM WATER CALS.
 4. MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST
 MATCH WITH AREAS USED IN STORM WATER QUALITY
 CALCULATIONS.
 5. PLEASE SHOW ON YOUR DRAWINGS ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM
 WATER PIPES.PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, DO YOU HAVE EXFILTRATION
 TRENCHES. PLEASE SHOW DRY DETENTION/WET DETENTION AREAS
 WITH 100% FILL OF STORM WATER ELEVATION?
 6. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST AROUND
 YOUR SITE.
 7. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, A COPY OF
 GEO-TECH REPORT AND A LATESTEST COPY OF STORM STORM
 WATER QUALITY CALCULATIONS THAT YOU PROVIDED AT 45TH
 STREET.
 8. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED 10.
 PLEASE PROVIDE LATEST COPY OF SET OF CIVIL DRAWINGS
 THAT WERE APPROVED AT 45TH STREET IN JUNE 2007.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-02-02 Cont ID  
Sent By rchokshi Date 2007-02-02 Time 13:24 Rev Time 0.00
Received By rchokshi Date 2007-02-02 Time 13:11 Sent To  
Notes
2007-02-02 13:23:53PLEASE EXPLAIN WHAT CHANGES YOU MADE FROM LAST TIME WE
 APPROVED ENGINEERING ON 3-31-06??
  
 1. DIDYOU MAKE ANY CHANGES INSIDEWALK WIDTH , ITS
 SLOPE, DRIVEWAY, PARKING, HANDICAP PARKING, PAINT, ALL
 MUST FOLLOW CITY STANDARDS,PER CITY CODES ETC., MUST
 MEET PER ADA,,ETC.,
 2. DID YOU MAKE ANY CHANGES IN DRAWINGS FORDUMPSTER &
 ITS ENCLOSURE DETAILS? LOCATION ON DWG, LOCATION MUST
 BE ACCESSIBLE FOR PICKUP TRUCK.
 3. ANY CHANGES IN FIRST FLOOR ELEVATION, CENTER LINE OF
 ROAD , SIDEWALK ELEVATION MUST MEET FL BLDG CODE,
 PLEASE SHOW ON THE DRAWINGS.
 4. ANY CHANGES IN SFWMD PERMIT, OR GEO TECH REPORT??
 5.ANY CHANGES IN STORM WATER CALCULATIONS, WHAT
 CRITERIA YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER
 ENTIRE SITE OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE
 GREEN, LAKES, ETC,IMPERVIOUS AREA CAL.,
 6. ANY CHANGES IN THE SITE AREA, YOU ARE DEVELOPING FOR
 THIS PROJECT ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS
 CAL.
 7.ANY CHANGES IN CONNECTING THE STORM WATER PIPES IN
 YOUR SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER
 PIPES AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 8. ANY CHANGES IN POLLUTION PREVENTION DETAILS,CLOTHES
 USED FOR SILT ETC., PLANS SHOWING SILT FENCE AROUND THE
 SITE
 9.ANY CHANGES INWATER & SEWER PLANS?MUST BE
 APPROVED FROM 45TH STREET (MANNY G.), UTILITY DEPT
 BEFORE WE APPROVED
 10..ANY CHANGES IN CATCH BASINS NEAREST,AROUND YOUR
 SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL IN A LETTER AND IN
 THE DRAWINGS AS REVISIONS,TO EXPEDITE YOUR PERMITTING
 PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2006-03-31 Cont ID  
Sent By mamini Date 2006-03-31 Time 16:29 Rev Time 1.00
Received By mamini Date 2006-03-31 Time 16:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-09-26 Cont ID  
Sent By mwennerg Date 2007-09-26 Time 15:09 Rev Time 0.00
Received By mwennerg Date 2007-09-26 Time 15:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-07-24 Cont ID  
Sent By mawillia Date 2007-07-24 Time 11:10 Rev Time 0.00
Received By mawillia Date 2007-07-24 Time 10:17 Sent To  
Notes
2007-07-24 11:10:28*****DENIED*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
  
 1.THE NUMERICAL ADDRESS, INCLUDING THE SUITE NUMBER,
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 3.SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR THE
 FIRE SPRINKLER REMODEL.
  
 4.PLEASE SHOW THE LOCATION OF REQUIRED 2A:10BC RATED
 FIRE EXTINGUISHER(S) THAT SHALL NOT EXCEED THE 75'
 TRAVEL DISTANCE.
  
 5.IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101, 2003 EDITION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-02-23 Cont ID  
Sent By mwennerg Date 2007-02-23 Time 14:46 Rev Time 0.00
Received By mwennerg Date 2007-02-23 Time 14:45 Sent To  
Notes
2007-02-23 14:54:57***DENIED***
  
 FIRST FIRE REVIEW CONDUCTED AS EXTERIOR DEMO ONLY.
 PLEASE SEE NEW COMMENTS:
  
 1) APPLICATION AND DRAWINGS SHALL REFLECT THE SAME
 ADDRESS SUITE.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 SPRINKLER REMODEL.
  
 4) PLEASE SHOW LOCATION OF REQUIRED 2A-10B,C RATED FIRE
 EXTINGUISHERS THAT SHALL NOT EXCEED 75' TRAVEL
 DISTANCE.
  
 5) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101, 2003 EDITION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW(561) 805-6722
 FIRE PREVENTION(561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-03-24 Cont ID  
Sent By mwennerg Date 2006-03-24 Time 13:51 Rev Time 0.00
Received By mwennerg Date 2006-03-24 Time 13:51 Sent To  
Notes
2006-03-24 00:00:00EXTERIOR DEMO AND ENCLOSURE OF DRIVE
 THROUGH ONLY.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-01-15 Cont ID  
Sent By adarroug Date 2008-01-15 Time 09:33 Rev Time 0.00
Received By adarroug Date 2008-01-15 Time 09:33 Sent To B
Notes
2008-01-15 09:33:44TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-10-10 Cont ID  
Sent By adarroug Date 2007-10-10 Time 08:47 Rev Time 0.00
Received By adarroug Date 2007-10-10 Time 08:47 Sent To  
Notes
2007-10-10 08:47:37WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-04 Cont ID  
Sent By adarroug Date 2007-09-04 Time 14:59 Rev Time 0.00
Received By adarroug Date 2007-09-04 Time 14:59 Sent To  
Notes
2007-09-04 15:00:14WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-18 Cont ID  
Sent By adarroug Date 2007-05-31 Time 09:02 Rev Time 0.00
Received By adarroug Date 2007-05-31 Time 09:02 Sent To  
Notes
2007-06-18 09:03:59TO "COMM" BD#56

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-20 Cont ID  
Sent By adarroug Date 2007-01-20 Time 14:53 Rev Time 0.00
Received By adarroug Date 2007-01-20 Time 14:53 Sent To  
Notes
2007-01-31 15:28:46TO "COMM" BD#6
2007-01-20 14:55:30WAITING FOR "COMM" BD--NEW SHEETS(STAMPED SET VOIDED)

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-11 Cont ID  
Sent By adarroug Date 2006-09-11 Time 09:20 Rev Time 0.00
Received By adarroug Date 2006-09-11 Time 09:20 Sent To  
Notes
2006-09-20 00:00:00TO "COMM" BD#25
2006-09-11 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-04 Cont ID  
Sent By kstevens Date 2006-05-04 Time 17:50 Rev Time 0.00
Received By kstevens Date 2006-01-31 Time 14:10 Sent To  
Notes
2006-03-06 00:00:00TO "COMM" BD#41
2006-01-31 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2007-02-21 Cont ID  
Sent By tgordon Date 2007-02-21 Time 15:47 Rev Time 0.20
Received By tgordon Date 2007-02-21 Time 15:46 Sent To  
Notes
2007-02-21 15:50:35NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-03-22 Cont ID  
Sent By hmoser Date 2006-03-22 Time 14:56 Rev Time 0.00
Received By hmoser Date 2006-03-22 Time 14:56 Sent To  
Notes
2006-03-22 00:00:00MECHANICAL PLANS NOT REQUIRED FOR DEMO.
 PLAN REVIEW BY HAROLD MOSER

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-07-14 Cont ID  
Sent By kstevens Date 2007-07-14 Time 06:46 Rev Time 0.00
Received By kstevens Date 2007-07-14 Time 06:46 Sent To  
Notes
2007-07-14 06:47:58APPROVAL FOR SHELL ONLY, ROOF DRAINAGE ONLY REVIEWED
 --NO PLUMBING INSIDE STRUCTURE SHOWN.

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-02-16 Cont ID  
Sent By kstevens Date 2007-02-16 Time 09:07 Rev Time 0.00
Received By kstevens Date 2007-02-16 Time 09:07 Sent To  
Notes
2007-02-16 09:08:57DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 THIRD REVIEW. FROM PREVIOUS REVIEWS:
  
 FROM PREVIOUS REVIEW: COMMENT NUMBER TO
 REMAIN THE SAME.
  
 9. SHT A-2 SUBMIT CALCULATIONS FOR THE
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTION 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE SF AREA OF THE
 ROOF, WITH 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS ADDED TO THE SF
 OF THE ROOF AS WELL AS THE AREA OF ALL
 ROOFS THAT DRAIN ONTO THE ROOF FROM
 ABOVE, (IF ANY).
 ***RESPONSE NOTED, BUT CALCULATIONS
 INDICATE A TOTAL OF 2,545SF. SHT A-1
 INDICATES NEW RETAIL 2,640SF. ALSO NO
 INFORMATION FOR THE VERTICAL WALLS
 ADJACENT TO THE ROOF FROM THE OTHER
 SPACES IN THE BUILDING. NORTH ELEVATION
 ON SHT A-2 INDICATES THE TOP OF THE
 PARAPET TO BE 29'0", AND THE TOP OF THE
 PARAPET TO THE SOUTH IS 16'0". NO
 CONTRIBUTION FROM THE VERTICAL WALLS WAS
 INDICATED IN THE CALCULATIONS. ALSO
 PLEASE INDICATE THE ELEVATION FOR THE
 ROOF AT BOTH THE HIGH END AND THE LOW
 END TO VERIFY CALCULATIONS.
 ******NO RESPONSE, NOT ADDRESSED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-7631
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-10-05 Cont ID  
Sent By kstevens Date 2006-10-05 Time 07:38 Rev Time 0.00
Received By kstevens Date 2006-10-04 Time 18:24 Sent To  
Notes
2006-10-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 FROM PREVIOUS REVIEW: COMMENT NUMBER TO
 REMAIN THE SAME.
  
 9. SHT A-2 SUBMIT CALCULATIONS FOR THE
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTION 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE SF AREA OF THE
 ROOF, WITH 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS ADDED TO THE SF
 OF THE ROOF AS WELL AS THE AREA OF ALL
 ROOFS THAT DRAIN ONTO THE ROOF FROM
 ABOVE, (IF ANY).
 ***RESPONSE NOTED, BUT CALCULATIONS
 INDICATE A TOTAL OF 2,545SF. SHT A-1
 INDICATES NEW RETAIL 2,640SF. ALSO NO
 INFORMATION FOR THE VERTICAL WALLS
 ADJACENT TO THE ROOF FROM THE OTHER
 SPACES IN THE BUILDING. NORTH ELEVATION
 ON SHT A-2 INDICATES THE TOP OF THE
 PARAPET TO BE 29'0", AND THE TOP OF THE
 PARAPET TO THE SOUTH IS 16'0". NO
 CONTRIBUTION FROM THE VERTICAL WALLS WAS
 INDICATED IN THE CALCULATIONS. ALSO
 PLEASE INDICATE THE ELEVATION FOR THE
 ROOF AT BOTH THE HIGH END AND THE LOW
 END TO VERIFY CALCULATIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-7631
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-04 Cont ID  
Sent By kstevens Date 2006-05-04 Time 16:45 Rev Time 0.00
Received By kstevens Date 2006-05-04 Time 13:29 Sent To  
Notes
2006-05-04 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-1 SHOW THE LOCATION OF THE
 TOILET ROOM ON THE FLOOR PLAN. SECTION
 106.1.1.
  
 2. SHT A-1 MINIMUM WIDTH FOR A HDCP
 TOILET ROOM IS 5'3" FINISHED. PLANS SHOW
 5'2-1/2".SECTION 11-4.19.3, FIG. 28,
 AND SECTION 405.3.1.
  
 3. SHT A-1 A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTIONS. ALSO SHOW
 COMPLIANCE WITH SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
  
 4. SHT A-1 DETAIL 1/A-1 SHOW THE CLEAR
 FLOOR SPACE FOR THE W/C PER SECTION
 11-4.16.2.
  
 5. SHT A-1 DETAIL A/A-1 SHOW THE FLUSH
 CONTROL PER SECTION 11-4.16.5.
  
 6. SHT A-1 DETAIL A/A-1 INDICATE FAUCET
 TYPE PER SECTION 11-4.19.5.
  
 7. SUBMIT A SANITARY RISER ISOMETRIC
 DIAGRAM. SHOW ALL PIPE SIZES, TRAPS, AND
 VENTS. SECTION 106.3.5.1.3.
  
 8. SUBMIT A WATER RISER ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES,
 AND INDICATE AN RPZV BACKFLOW REQUIRED
 ON THE WATER SERVICE TO SPACE. SECTIONS 106.3.5.1.3 AND
 608.13.2.
  
 9. SHT A-2 SUBMIT CALCULATIONS FOR THE
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTION 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE SF AREA OF THE
 ROOF, WITH 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS ADDED TO THE SF
 OF THE ROOF AS WELL AS THE AREA OF ALL
 ROOFS THAT DRAIN ONTO THE ROOF FROM
 ABOVE, (IF ANY).
  
 10. SHOW THE LOCATION OF ALL SECONDARY
 ROOF DRAINS REQUIRED IN SECTION 1107.1 &
 1107.2. SEPARATE SYSTEMS REQUIRED. IF
 THE SECONDARY ROOF DRAINS ARE EMERGENCY
 OVERFLOW SCUPPERS, THEN THEY WILL BE
 SIZED PER SECTIONS 1101.7, 1107.3 AND
 TABLE 1106.7. THE SIZING OF THE OVERFLOW
 SCUPPERS CAN NOT BE DETERMINED WITHOUT
 REFERENCE TO THE DEFLECTION OF THE ROOF.
 PLEASE STATE ON THE PLANS THAT THE
 OVERFLOW SCUPPER SIZES COMPLY WITH
 SECTIONS 1101.7, 1107.3 AND TABLE
 1106.7.
  
 11. SUBMIT DETAILS FOR THE DOWNSPOUTS,
 COLLECTION HEAD, DRAIN SCUPPERS, &
 EMERGENCY OVERFLOW SCUPPERS. SHOW THE
 LENGTH, WIDTH, HEIGHT, OF EACH, AND SHOW
 THE DISTANCE FROM THE ROOF TO THE FLOW
 LEVEL OF THE EMERGENCY SCUPPER PER
 SECTION 1503.4.3. INDICATE THE
 TERMINATION POINT OF THE DOWNSPOUTS AND
 SHOW COMPLIANCE WITHE SECTION 1503.6
 1503.6 PROTECTION AGAINST DECAY AND
 TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS
 SHALL DISCHARGE AT LEAST 1 FOOT (305 MM)
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL
 EXTENSIONS, OR SPLASH BLOCKS. GUTTERS
 WITH DOWNSPOUTS ARE REQUIRED ON ALL
 BUILDINGS WITH EAVES OF LESS THAN 6
 INCHES (152 MM) HORIZONTAL PROJECTION
 EXCEPT FOR GABLE END RAKES OR ON A ROOF
 ABOVE ANOTHER ROOF.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 WHEN RESUBMITTING FOR REVIEW, PLEASE
 SUBMIT ONE SET OF ORIGINAL SHEETS FOR
 COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 7 Status P Date 2007-11-29 Cont ID  
Sent By jroach Date 2007-11-29 Time 17:54 Rev Time 0.00
Received By jroach Date 2007-11-29 Time 17:54 Sent To  
Notes
2007-11-29 17:55:08***PROVISO***
  
 A) THE PARKING SHALL BE STRIPED ACCORDING TO THE CITY'S
 ZONING AND LAND DEVELOPMENT REGULATIONS (SEE ATTACHED
 DETAIL); AND
  
 B) ALTHOUGH THE SCOPE OF WORK ON THE SITE PLAN DOES NOT
 COVER THE ENTIRE PROPERTY, ALL OF THE LANDSCAPING SHOWN
 ON SHEETS LP-1 THROUGH LP-4 SHALL BE INSTALLED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 6 Status P Date 2007-10-23 Cont ID  
Sent By jroach Date 2007-10-23 Time 17:16 Rev Time 0.00
Received By jroach Date 2007-10-23 Time 17:16 Sent To  
Notes
2007-10-23 17:17:43***PROVISO***
  
 A) THE PARKING SHALL BE STRIPED ACCORDING TO THE CITY'S
 ZONING AND LAND DEVELOPMENT REGULATIONS (SEE ATTACHED
 DETAIL); AND
  
 B) ALTHOUGH THE SCOPE OF WORK ON THE SITE PLAN DOES NOT
 COVER THE ENTIRE PROPERTY, ALL OF THE LANDSCAPING SHOWN
 ON SHEETS LP-1 THROUGH LP-4 SHALL BE INSTALLED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 5 Status F Date 2007-09-20 Cont ID  
Sent By jroach Date 2007-09-20 Time 17:13 Rev Time 0.00
Received By jroach Date 2007-09-20 Time 17:13 Sent To  
Notes
2007-09-20 17:19:26THE LANDSCAPE PLANS THAT WERE TURNED IN WITH THE
 RESUBMITTAL ARE NOT SIGNED & SEALED.SECTION 94-442(A)
 OF THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS
 REQUIRES THAT LANDSCAPE PLANS BE SIGNED & SEALED BY A
 REGISTERED LANDSCAPE ARCHITECT.EITHER RESUBMIT THE
 PREVIOUSLY-STAMPED LANDSCAPE PLANS, OR IF CHANGES WERE
 MADE, THE NEW LANDSCAPE PLANS SHALL BE SIGNED &
 SEALED.
  
 THE PROVISIOS INDICATED ON JUNE 18, 2007 REMAIN:
  
 A) THE PARKING SHALL BE STRIPED ACCORDING TO THE CITY'S
 ZONING AND LAND DEVELOPMENT REGULATIONS (SEE ATTACHED
 DETAIL); AND
  
 B) ALTHOUGH THE SCOPE OF WORK ON THE SITE PLAN DOES NOT
 COVER THE ENTIRE PROPERTY, ALL OF THE LANDSCAPING SHOWN
 ON SHEETS LP-1 THROUGH LP-4 SHALL BE INSTALLED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 4 Status P Date 2007-06-18 Cont ID  
Sent By jroach Date 2007-06-18 Time 19:43 Rev Time 0.00
Received By jroach Date 2007-06-18 Time 19:43 Sent To  
Notes
2007-06-18 19:44:43***PROVISO***
  
 1) PARKING SHALL BE STRIPED ACCORDING TO ATTACHED
 DETAIL.
  
 2) ALTHOUGH SCOPE OF WORK ON SITE PLAN DOES NOT COVER
 THE ENTIRE SITE, ALL OF THE LANDSCAPING SHOWN ON SHEETS
 LP-1 THROUGH LP-4 SHALL BE INSTALLED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-02-11 Cont ID  
Sent By jroach Date 2007-02-11 Time 13:54 Rev Time 0.00
Received By jroach Date 2007-02-11 Time 13:54 Sent To  
Notes
2007-02-11 13:54:58***PASSED WITH PROVISOS***
  
 1) PARKING SPACES SHALL BE STRIPED ACCORDING TO
 ATTACHED DETAIL.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-09-22 Cont ID  
Sent By jroach Date 2006-09-22 Time 20:32 Rev Time 0.00
Received By jroach Date 2006-09-22 Time 20:32 Sent To  
Notes
2006-09-22 00:00:009/22/06 ***FAILED***
  
 TWO (2) ADDITIONAL SETS OF SIGNED/SEALED
 LANDSCAPE PLANS SHALL BE PROVIDED.ONLY
 ONE (1) SET WAS INCLUDED IN THE PERMIT
 PACKAGE.UPON PROVIDING THESE PLANS,
 PERMIT WILL BE PASSED BY THE PLANNING
 AND ZONING DEPARTMENT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-10 Cont ID  
Sent By jroach Date 2006-04-10 Time 19:28 Rev Time 0.00
Received By jroach Date 2006-04-10 Time 19:28 Sent To  
Notes
2006-04-10 00:00:004/10/06 ***FAILED***
  
 1) APPROVAL OF FORMAL SITE PLAN REVIEW
 CASE NO. 785E EXPIRED ON JANUARY 25,
 2006."SIGNIFICANT CONSTRUCTION
 ACTIVITY, AS EVIDENCED BY THE POURING
 AND COMPLETION OF FOOTINGS" WAS TO OCCUR
 PRIOR TO EXPIRATION FOR THE SITE PLAN TO
 BE VESTED.NEW SITE PLAN APPROVAL SHALL
 BE OBTAINED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435
 REGARDING THIS ISSUE.