Plan Review Details - Permit 06011059
Plan Review Stops For Permit 06011059
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-11-09 Cont ID  
Sent By jwitmer Date 2006-11-09 Time 14:09 Rev Time 0.55
Received By jwitmer Date 2006-11-09 Time 14:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-19 Cont ID  
Sent By jwitmer Date 2006-07-19 Time 14:34 Rev Time 0.55
Received By jwitmer Date 2006-07-19 Time 14:34 Sent To  
Notes
2006-07-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06011059
 ADD: 951 OKEECHOBEE RD
 CONT: C. R. DUNN
 TEL: (561)585-2155
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 1 ) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-25 Cont ID  
Sent By jwitmer Date 2006-04-25 Time 11:30 Rev Time 0.55
Received By jwitmer Date 2006-04-25 Time 11:30 Sent To PC
Notes
2006-04-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06011059
 ADD: 951 OKEECHOBEE RD
 CONT: C. R. DUNN
 TEL: (561)585-2155
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1 ) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-25 Cont ID  
Sent By dpalmer Date 2006-10-25 Time 11:09 Rev Time 0.00
Received By dpalmer Date 2006-10-25 Time 07:49 Sent To  
Notes
2006-10-25 11:11:43GENERATOR NUETRAL AND GROUNDING ATTACHMENT AT UNIT
 SHALL BE VERIFIED.
 IT HAS BECOME THE ATTENTION OF THIS OFFICE THAT THERE
 ARE MANUFACTURE WHICH BUILD AND SHIP UNITSWIRED FOR
 "SEPARATELY DERIVED" UNITS. THIS MUST BE VERIFIED AS
 SYSTEM IS BEING SHOWN AS NOT SD.
 REVISE IF NEEDED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-29 Cont ID  
Sent By dpalmer Date 2006-06-29 Time 19:34 Rev Time 0.00
Received By dpalmer Date 2006-06-29 Time 18:34 Sent To  
Notes
2006-06-29 00:00:00********** UNSAT 2ND REVIEW ************
  
 ** PLEASE SEE THE FOLLOWING NOTES AS ALL
 INFORMATION NEEDED WAS NOT SUBMITTED.
  
 ** PLEASE SEE SOME OF THE SAME NOTES
 FROM PREVIOUS REVIEW STILL APPLY.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
  
 1)NOTE: OK
  
 2)NOTE: OK.
  
 3)NOTE: NO, PLEASE SEE AN OLD SITE PLAN
 WAS SUBMITTED, HOWEVER LOCATION OF
 GENERATOR ETC WAS NOT SHOWN WITH THE NEW
 ELEVATION OF GEN ETC.
 "SLOSH" ELEVATION IS NOT REQUIRED ,
 HOWEVER 6" ABOVE BFE WILL BE REQUIRED.
  
 ** PREVIOUS NOTES **
 PLEASE KNOW, A SITE SURVEY AND
 ELEVATIONS WERE NOT SUBMITTED FOR
 LOCATION OF GENERATOR AND BFE.
 PLEASE SEE LOCATIONS OF GEN IN
 NFPA-110,7.2.3* WHICH REFERENCES THE
 "SLOSH" CHARTS.
  
 4)NOTE: NO, PLEASE SEE NO SPECS ETC WERE
 SUBMITTED AND ARE REQUIRED AT THIS TIME.
 PLEASE KNOW, IF THE EQUIPMENT HAS NOT
 BEEN PURCHASED, PICK ONE , IT ONLY NEEDS
 TOMEET ALL LISTINGS BY A NRTL, AND TO
 CORRELATE WITH ALL THE CODE REQUIREMENTS
 FOR INSTALLATION ETC. **THE EQUIPMENT
 CAN BE REVISED AT A LATER DATE IF
 DIFFERENT EQUIPMENT IS CHOSEN.
  
 **PREVIOUS NOTE **
 PLEASE SUBMIT ALL THE
 MANUFACTURE'S CUT/SPEC SHEETS FOR
 GENERATOR, ATS, AND ANY NEW FUEL
 TANK(S). PLEASE BE SURE ALL SPECS/SHEETS
 CONTAIN LISTINGS FROM A NRTL.
 215.5
  
 5)NOTE: NO, PLEASE SEE MOST HAS BEEN
 CLEARED UP, HOWEVER PLEASE SEE RISER AND
 NOTES ON E-1, AS NOTES #4 AND #7, SEEM
 TO BE CROSSED.??
 PLEASE SEE NO SIZES ARE PROVIDED FOR NEW
 MAIN, ATS ETC.
  
 ** PREVIOUS NOTE**
 PLEASE CORRELATE RISER ON E-1,
 WITH RISER ON E-2.
 PLEASE SEE NOTE #7 WHICH MENTIONS NEW
 CONDUITS FROM NEW MAIN, HOWEVER RISER
 SHOWS THIS AS EXIST TO REMAIN AND IS
 ALSO NOTED AS EXIST??
 PLEASE SEE NOTE #3, WHICH SHOWS THIS
 NOTE FOR WHAT APPEARS TO BE A METER
 BEING REMOVED AND MAIN DISCONNECT?
 (MISPRINT?)
 PLEASE SEE RISER, AS SHOWN SEEMS TO BE
 MISPRINTED BACKWARDS ,??
  
 6)NOTE: OK, HOWEVER PLEASE LIST
 EQUIPMENT WHICH IS LOCATED IN MAIN
 ELECTRICAL RM AS EXISTING WHERE
 APPLICABLE.
  
 7)NOTE: OK.
  
 8)NOTE: NO, PLEASE SEE VALUE WAS NOT
 ADJUSTED. PLEASE KNOW, A VALUE WILL BE
 PLACED ON THE SCOPE OF WORK BY SUING THE
 "MARSHALL'S/ SWIFT" GUIDE IF NOT
 INCREASED.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 2004 FBC 108.3 CITY
 OF WEST PALM BEACH ADMINISTRATIVE CODE
 WHICH REQUIRES VALUE FOR SCOPE OF
 WORK/IMPROVEMENT TO INCLUDE ALL LABOR
 AND MATERIALS, EVEN IF EQUIPMENT IS
 OWNER SUPPLIED.
 PLEASE SEE VALUE IS TOO LOW FOR SCOPE OF
 WORK.
  
 9)NOTE:NO, PLEASE SEE NO SLAB PLANS,
 DETAILS ETC WERE SUBMITTED AND ARE
 REQUIRED.
  
 ** PREVIOUS NOTE**
 PLEASE SEE BLDG REVIEW COMMENTS
 AS NO SLAB DETAIL WAS SUBMITTED. PLEASE
 SEE MIN REQUIREMENTS IN NFPA-110 AND
 ENGINEERING PRACTICES FOR A GENERATOR OF
 THIS SIZE AND WEIGHT.
 7.2.1.1,7.4, 7.5*
  
 ** NEW NOTE **
  
 10) NOTE: PLEASE SEE FS 553.80(2)(B)
 WITH RESPECT TO REPEAT COMMENTS.
  
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-28 Cont ID  
Sent By dpalmer Date 2006-02-28 Time 19:22 Rev Time 0.00
Received By dpalmer Date 2006-02-28 Time 18:39 Sent To  
Notes
2006-02-28 00:00:00*********** UNSAT ************
  
 ** PLEASE SEE THE FOLLOWING NOTES AS ALL
 INFORMATION NEEDED WAS NOT SUBMITTED.
  
  
 1)NOTE: PLEASE KNOW, THE ADDRESS AND
 SITE BE ON TITLE BLOCK OF PLANS. PLEASE
 KNOW, THE ADDRESS IS 951 OKEECHOBEE RD,
 AND NOT "OLD" OKEECHOBEE AS ON PERMIT
 APPLICATION.
  
 2)NOTE: PLEASE REFERENCE ALL CURRENTS
 CODES FOR INSTALLATION OF THIS PROJECT.
 PLEASE SEE 2003 NFPA-101, 2002 NFPA-110,
 NFPA-70 2002.
  
 3)NOTE: PLEASE KNOW, A SITE SURVEY AND
 ELEVATIONS WERE NOT SUBMITTED FOR
 LOCATION OF GENERATOR AND BFE.
 PLEASE SEE LOCATIONS OF GEN IN
 NFPA-110,7.2.3* WHICH REFERENCES THE
 "SLOSH" CHARTS.
  
 4)NOTE: PLEASE SUBMIT ALL THE
 MANUFACTURE'S CUT/SPEC SHEETS FOR
 GENERATOR, ATS, AND ANY NEW FUEL
 TANK(S). PLEASE BE SURE ALL SPECS/SHEETS
 CONTAIN LISTINGS FROM A NRTL.
 215.5
  
 5)NOTE: PLEASE CORRELATE RISER ON E-1,
 WITH RISER ON E-2.
 PLEASE SEE NOTE #7 WHICH MENTIONS NEW
 CONDUITS FROM NEW MAIN, HOWEVER RISER
 SHOWS THIS AS EXIST TO REMAIN AND IS
 ALSO NOTED AS EXIST??
 PLEASE SEE NOTE #3, WHICH SHOWS THIS
 NOTE FOR WHAT APPEARS TO BE A METER
 BEING REMOVED AND MAIN DISCONNECT?
 (MISPRINT?)
 PLEASE SEE RISER, AS SHOWN SEEMS TO BE
 MISPRINTED BACKWARDS ,??
  
 6)NOTE: PLEASE SEE EXISTING RISER SHOWS
 A EXISTING GEN DISC LCOATED INSIDE,
 NOTED TO BE REMOVED, YET NEW REVISED
 RISER SHOWS THIS DISCONNECT STILL
 LOCATED ON REVISED RISER? PLEASE
 CLARIFY, IF THE GEN DISC LOCATED INSIDE
 BLDG, IS BEING REMOVED. ALL ELECTRICAL
 EQUIPMENT NO LONGER IN USE SHOULD BE
 REMOVED.
  
 7)NOTE: PLEASE PROVIDE OCP AT GENERATOR,
 PLEASE ALSO SEE 445.13.
 UNABLE TO VERIFY FEEDER SIZES, ETC .
 215.5
  
  
 8)NOTE: PLEASE SEE 2004 FBC 108.3 CITY
 OF WEST PALM BEACH ADMINISTRATIVE CODE
 WHICH REQUIRES VALUE FOR SCOPE OF
 WORK/IMPROVEMENT TO INCLUDE ALL LABOR
 AND MATERIALS, EVEN IF EQUIPMENT IS
 OWNER SUPPLIED.
 PLEASE SEE VALUE IS TOO LOW FOR SCOPE OF
 WORK.
  
 9)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 AS NO SLAB DETAIL WAS SUBMITTED. PLEASE
 SEE MIN REQUIREMENTS IN NFPA-110 AND
 ENGINEERING PRACTICES FOR A GENERATOR OF
 THIS SIZE AND WEIGHT.
 7.2.1.1,7.4, 7.5*
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-12-08 Cont ID  
Sent By mawillia Date 2006-12-08 Time 13:24 Rev Time 0.00
Received By mawillia Date 2006-12-08 Time 13:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-07-10 Cont ID  
Sent By mcarsill Date 2006-07-10 Time 13:57 Rev Time 0.00
Received By mcarsill Date 2006-07-10 Time 13:53 Sent To  
Notes
2006-07-10 00:00:001. SURVEY PROVIDED WITH PERMIT
 APPLICATION IS DATED JUNE 6, 1986. THE
 SURVEY PROVIDED IS OVER TWENTY YEARS
 OLD.
  
 2. NO PRODUCT APPROVALS OR SUBMITTAL
 DATE PROVIDED FOR THE GENERATOR, FEUL
 SUPPLY, LISTINGS, ETC. FOR THE
 APPLIANCE.
  
 3. MORE DETAILS ARE NEEDED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-03-24 Cont ID  
Sent By mwennerg Date 2006-03-24 Time 15:20 Rev Time 0.00
Received By mwennerg Date 2006-03-24 Time 15:20 Sent To  
Notes
2006-03-24 00:00:00******DENIED******
  
 1) PLEASE SUBMIT MANUFACTURER SPEC
 SHEETS FOR GENERATOR, FUEL TANK AND ALL
 ASSOCIATED EQUIPMENT.
  
 2) PLEASE PROVIDE MORE INFORMATION
 REGARDING FUEL TANK SIZE, LOCATION ETC.
 EXISTING OR NEW? PROTECTION DEVICES MAY
 BE REQUIRED TO ELIMINATE MECHANICAL
 DAMAGE.
  
 3) WORK SHALL COMPLY WITH APPLICABLE
 BUILDING CODES IN ADDITION TO NFPA 1 AND
 NFPA 110.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status N Date 2006-10-31 Cont ID  
Sent By pkrauss Date 2006-10-31 Time 09:30 Rev Time 0.00
Received By pkrauss Date 2006-10-31 Time 09:28 Sent To  
Notes
2006-10-31 09:30:43SUB-BASE FUEL TANK/SELF CONTAINED - NO FILL PIPING
 REQUIRED.

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2006-07-28 Cont ID  
Sent By pkrauss Date 2006-07-28 Time 14:10 Rev Time 0.00
Received By pkrauss Date 2006-07-28 Time 14:10 Sent To  
Notes
2006-07-28 00:00:00DENIED:
 1.PLEASE INDICATE THE FUEL SOURCE FOR
 THE GENERATOR.
  
 2.PLEASE PROVIDE MANUFACTURER
 SUBMITALL & INSTALLATION INSTRUCTIONS
 FOR THE GENERATOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2006-10-31 Cont ID  
Sent By pkrauss Date 2006-10-31 Time 09:38 Rev Time 0.00
Received By pkrauss Date 2006-10-31 Time 09:38 Sent To  
Notes
2006-10-31 09:39:09DIESEL GENERATOR ONLY - GAS PERMIT NOT REQUIRED

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-07-28 Cont ID  
Sent By pkrauss Date 2006-07-28 Time 14:19 Rev Time 0.00
Received By pkrauss Date 2006-07-28 Time 14:18 Sent To  
Notes
2006-07-28 00:00:00DENIED:
 INSUFFICIENT INFORMATION FOR REVIEW.
 PLEASE PROVIDE SUBMITTAL & INSTALLATION
 INSTRUCTIONS FOR THE GENERATOR.
  
 SHOULD THIS GENERATOR BE NATURAL GAS OR
 LP GAS GENERATOR, PLEASE PROVIDE THE
 INFORMATION INDICATED ON THE ATTACHED
 SHEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT KENNY STEVENS AT (561)805-6721

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-11 Cont ID  
Sent By adarroug Date 2006-10-11 Time 15:49 Rev Time 0.00
Received By adarroug Date 2006-10-11 Time 15:49 Sent To  
Notes
2006-10-24 09:37:19TO "COMM" BD#24
2006-10-11 15:49:26WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 09:39 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 09:39 Sent To  
Notes
2006-06-27 00:00:00TO "COMM" BD#23
2006-06-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-04-25 Time 09:38 Rev Time 0.00
Received By adarroug Date 2006-01-30 Time 08:57 Sent To  
Notes
2006-02-27 00:00:00TO "COMM" BD#25
2006-01-30 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-10-31 Cont ID  
Sent By pkrauss Date 2006-10-31 Time 08:44 Rev Time 0.00
Received By pkrauss Date 2006-10-31 Time 08:15 Sent To  
Notes
2006-10-31 09:25:54PROVISO:
  
 EXHAUST FROM THE GENERATOR SHALL NOT BE LOCATED WITHIN
 10 FT OF ANY DOOR, WINDOW, OR FRESH AIR INTAKE PER 2004
 FMC 401.5.1. EXHAUST SHALL BE TERMINATE IN SUCH A
 MANNER AS NOT TO BE READILY DRAWN IN BY THE VENTILATING
 SYSTEM PER 2004 FMC 501.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected]
2006-10-31 08:49:10 
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-28 Cont ID  
Sent By pkrauss Date 2006-07-28 Time 07:24 Rev Time 0.00
Received By pkrauss Date 2006-07-28 Time 07:24 Sent To  
Notes
2006-07-28 00:00:00DENIED:
 2ND REQUEST:
 1.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE GENERATOR.
  
 2.PLEASE INDICATE ON THE SITE PLAN THE
 FOLLOWING INFORMATION:
  
 A.LOCATION OF THE GENERATOR ON
 PLAN.
 B.DISTANCES TO BUILDINGS, PROPERTY
 LINES, AND FRESH AIR INTAKES
 (I.E. WINDOWS, DOORS, ETC.)
  
 3.PLEASE INDICATE FUEL SOURCE -
 DIESEL, NATURAL GAS, LP GAS, ETC.
  
 4.PLEASE PROVIDE ANCHORING DETAIL.
  
 5.PLEASE PROVIDE A SLAB DETAIL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-20 Cont ID  
Sent By hmoser Date 2006-03-20 Time 08:50 Rev Time 0.00
Received By hmoser Date 2006-03-20 Time 08:43 Sent To  
Notes
2006-03-20 00:00:00PLANS DENIED
 PLEASE PROVIDE MANUFACTURERS
 INSTALLATION INSTRUCTIONS ON THE
 GANERATOR.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status N Date 2006-10-31 Cont ID  
Sent By pkrauss Date 2006-10-31 Time 09:39 Rev Time 0.00
Received By pkrauss Date 2006-10-31 Time 09:39 Sent To  
Notes
2006-10-31 09:40:03NO PLUMBING REQUIRED FOR DIESEL GENERATOR

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-07-28 Cont ID  
Sent By pkrauss Date 2006-07-28 Time 14:22 Rev Time 0.00
Received By pkrauss Date 2006-07-28 Time 14:22 Sent To  
Notes
2006-07-28 00:00:00INSUFFICIENT INFORMATION FOR PROPER
 REVIEW.

Review Stop Z ZONING
Rev No 3 Status P Date 2006-11-11 Cont ID  
Sent By mmclean Date 2006-11-11 Time 14:58 Rev Time 0.00
Received By mmclean Date 2006-11-11 Time 14:58 Sent To  
Notes
2006-11-11 14:59:34PROVISO: THE PROPOSED GENERATOR MUST BE LANDSCAPE
 BUFFER FROM VIEW. THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 14.34FT PROPERTY LINE.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-17 Cont ID  
Sent By mmclean Date 2006-07-17 Time 10:02 Rev Time 0.00
Received By mmclean Date 2006-07-17 Time 10:02 Sent To  
Notes
2006-07-17 00:00:00DENIED,
 1. THE SURVEY/SITEPLAN DOES NOT SHOW THE
 LOCATION OF THE PROPOSED GENERATOR AND
 THE SETBACK FROM THE PROPERTY LINE.
 2. PLEASE SHOW THE LOCATION ON THE TWO
 COPY OF SURVEY/SITEPLAN WITH SETBACKS
 FROM PROPERTY LINE.
  
 NOTE:
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-06 Cont ID  
Sent By mmclean Date 2006-04-06 Time 17:03 Rev Time 0.00
Received By mmclean Date 2006-04-06 Time 17:03 Sent To  
Notes
2006-04-06 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF SITEPLAN
 SHOWING THE LOCATION OF THE GENERATOR
 WITH SETBACKS.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720