Plan Review Stops For Permit 06011059 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2006-11-09 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2006-11-09 |
Time |
14:09 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2006-11-09 |
Time |
14:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-07-19 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2006-07-19 |
Time |
14:34 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2006-07-19 |
Time |
14:34 |
Sent To |
|
|
Notes |
2006-07-19 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 06011059 | | ADD: 951 OKEECHOBEE RD | | CONT: C. R. DUNN | | TEL: (561)585-2155 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 2ND REVIEW | | ACTION: DENIED | | 1 ) GENERATOR SLAB & ANCHOR REQUIREMENT | | PLEASE PROVIDE SIZE OF GENERATOR(WXL), | | PLUS PROVIDE PLANS WITH THE INFORMATION | | DEPICTING HOLD DOWN BRACKETS, TYPE OF | | FASTENER, AND THE MINIMUM EDGE DISTANCE | | THE DEVICE REQUIRES WITHOUT LOAD | | REDUCTION. | | SECOND, PROVIDE INFORMATION ON THE | | SLAB, THICKNESS, WIDTH AND LENGTH, IF | | WIREMESH, FIBER MESH OR IF STEEL REBAR | | WILL BEUSED. | | THE NEW SLAB AND HOLD DOWN DETAILS: | | 104.2.1* ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | PERSON RESPONSIBLE FOR THE DESIGN. | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-04-25 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2006-04-25 |
Time |
11:30 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2006-04-25 |
Time |
11:30 |
Sent To |
PC |
|
Notes |
2006-04-25 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 06011059 | | ADD: 951 OKEECHOBEE RD | | CONT: C. R. DUNN | | TEL: (561)585-2155 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | 1 ) GENERATOR SLAB & ANCHOR REQUIREMENT | | PLEASE PROVIDE SIZE OF GENERATOR(WXL), | | PLUS PROVIDE PLANS WITH THE INFORMATION | | DEPICTING HOLD DOWN BRACKETS, TYPE OF | | FASTENER, AND THE MINIMUM EDGE DISTANCE | | THE DEVICE REQUIRES WITHOUT LOAD | | REDUCTION. | | SECOND, PROVIDE INFORMATION ON THE | | SLAB, THICKNESS, WIDTH AND LENGTH, IF | | WIREMESH, FIBER MESH OR IF STEEL REBAR | | WILL BEUSED. | | THE NEW SLAB AND HOLD DOWN DETAILS: | | 104.2.1* ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | PERSON RESPONSIBLE FOR THE DESIGN. | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2006-10-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-10-25 |
Time |
11:09 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-10-25 |
Time |
07:49 |
Sent To |
|
|
Notes |
2006-10-25 11:11:43 | GENERATOR NUETRAL AND GROUNDING ATTACHMENT AT UNIT | | SHALL BE VERIFIED. | | IT HAS BECOME THE ATTENTION OF THIS OFFICE THAT THERE | | ARE MANUFACTURE WHICH BUILD AND SHIP UNITSWIRED FOR | | "SEPARATELY DERIVED" UNITS. THIS MUST BE VERIFIED AS | | SYSTEM IS BEING SHOWN AS NOT SD. | | REVISE IF NEEDED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-06-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-06-29 |
Time |
19:34 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-06-29 |
Time |
18:34 |
Sent To |
|
|
Notes |
2006-06-29 00:00:00 | ********** UNSAT 2ND REVIEW ************ | | | | ** PLEASE SEE THE FOLLOWING NOTES AS ALL | | INFORMATION NEEDED WAS NOT SUBMITTED. | | | | ** PLEASE SEE SOME OF THE SAME NOTES | | FROM PREVIOUS REVIEW STILL APPLY. | | PLEASE SEE NOTES BELOW ARE TAKEN | | DIRECTLY FROM PREVIOUS REVIEW. | | | | | | 1)NOTE: OK | | | | 2)NOTE: OK. | | | | 3)NOTE: NO, PLEASE SEE AN OLD SITE PLAN | | WAS SUBMITTED, HOWEVER LOCATION OF | | GENERATOR ETC WAS NOT SHOWN WITH THE NEW | | ELEVATION OF GEN ETC. | | "SLOSH" ELEVATION IS NOT REQUIRED , | | HOWEVER 6" ABOVE BFE WILL BE REQUIRED. | | | | ** PREVIOUS NOTES ** | | PLEASE KNOW, A SITE SURVEY AND | | ELEVATIONS WERE NOT SUBMITTED FOR | | LOCATION OF GENERATOR AND BFE. | | PLEASE SEE LOCATIONS OF GEN IN | | NFPA-110,7.2.3* WHICH REFERENCES THE | | "SLOSH" CHARTS. | | | | 4)NOTE: NO, PLEASE SEE NO SPECS ETC WERE | | SUBMITTED AND ARE REQUIRED AT THIS TIME. | | PLEASE KNOW, IF THE EQUIPMENT HAS NOT | | BEEN PURCHASED, PICK ONE , IT ONLY NEEDS | | TOMEET ALL LISTINGS BY A NRTL, AND TO | | CORRELATE WITH ALL THE CODE REQUIREMENTS | | FOR INSTALLATION ETC. **THE EQUIPMENT | | CAN BE REVISED AT A LATER DATE IF | | DIFFERENT EQUIPMENT IS CHOSEN. | | | | **PREVIOUS NOTE ** | | PLEASE SUBMIT ALL THE | | MANUFACTURE'S CUT/SPEC SHEETS FOR | | GENERATOR, ATS, AND ANY NEW FUEL | | TANK(S). PLEASE BE SURE ALL SPECS/SHEETS | | CONTAIN LISTINGS FROM A NRTL. | | 215.5 | | | | 5)NOTE: NO, PLEASE SEE MOST HAS BEEN | | CLEARED UP, HOWEVER PLEASE SEE RISER AND | | NOTES ON E-1, AS NOTES #4 AND #7, SEEM | | TO BE CROSSED.?? | | PLEASE SEE NO SIZES ARE PROVIDED FOR NEW | | MAIN, ATS ETC. | | | | ** PREVIOUS NOTE** | | PLEASE CORRELATE RISER ON E-1, | | WITH RISER ON E-2. | | PLEASE SEE NOTE #7 WHICH MENTIONS NEW | | CONDUITS FROM NEW MAIN, HOWEVER RISER | | SHOWS THIS AS EXIST TO REMAIN AND IS | | ALSO NOTED AS EXIST?? | | PLEASE SEE NOTE #3, WHICH SHOWS THIS | | NOTE FOR WHAT APPEARS TO BE A METER | | BEING REMOVED AND MAIN DISCONNECT? | | (MISPRINT?) | | PLEASE SEE RISER, AS SHOWN SEEMS TO BE | | MISPRINTED BACKWARDS ,?? | | | | 6)NOTE: OK, HOWEVER PLEASE LIST | | EQUIPMENT WHICH IS LOCATED IN MAIN | | ELECTRICAL RM AS EXISTING WHERE | | APPLICABLE. | | | | 7)NOTE: OK. | | | | 8)NOTE: NO, PLEASE SEE VALUE WAS NOT | | ADJUSTED. PLEASE KNOW, A VALUE WILL BE | | PLACED ON THE SCOPE OF WORK BY SUING THE | | "MARSHALL'S/ SWIFT" GUIDE IF NOT | | INCREASED. | | | | ** PREVIOUS NOTE ** | | PLEASE SEE 2004 FBC 108.3 CITY | | OF WEST PALM BEACH ADMINISTRATIVE CODE | | WHICH REQUIRES VALUE FOR SCOPE OF | | WORK/IMPROVEMENT TO INCLUDE ALL LABOR | | AND MATERIALS, EVEN IF EQUIPMENT IS | | OWNER SUPPLIED. | | PLEASE SEE VALUE IS TOO LOW FOR SCOPE OF | | WORK. | | | | 9)NOTE:NO, PLEASE SEE NO SLAB PLANS, | | DETAILS ETC WERE SUBMITTED AND ARE | | REQUIRED. | | | | ** PREVIOUS NOTE** | | PLEASE SEE BLDG REVIEW COMMENTS | | AS NO SLAB DETAIL WAS SUBMITTED. PLEASE | | SEE MIN REQUIREMENTS IN NFPA-110 AND | | ENGINEERING PRACTICES FOR A GENERATOR OF | | THIS SIZE AND WEIGHT. | | 7.2.1.1,7.4, 7.5* | | | | ** NEW NOTE ** | | | | 10) NOTE: PLEASE SEE FS 553.80(2)(B) | | WITH RESPECT TO REPEAT COMMENTS. | | | | | | ** PLEASE SEE POSSIBLE COMMENTS FROM | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | PLANS. | | | | ** PLEASE BE SURE TO REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW | | REVISED SHEETS INTO COMPLETE SETS FOR | | REVIEW AND STAMPING. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-02-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-02-28 |
Time |
19:22 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-02-28 |
Time |
18:39 |
Sent To |
|
|
Notes |
2006-02-28 00:00:00 | *********** UNSAT ************ | | | | ** PLEASE SEE THE FOLLOWING NOTES AS ALL | | INFORMATION NEEDED WAS NOT SUBMITTED. | | | | | | 1)NOTE: PLEASE KNOW, THE ADDRESS AND | | SITE BE ON TITLE BLOCK OF PLANS. PLEASE | | KNOW, THE ADDRESS IS 951 OKEECHOBEE RD, | | AND NOT "OLD" OKEECHOBEE AS ON PERMIT | | APPLICATION. | | | | 2)NOTE: PLEASE REFERENCE ALL CURRENTS | | CODES FOR INSTALLATION OF THIS PROJECT. | | PLEASE SEE 2003 NFPA-101, 2002 NFPA-110, | | NFPA-70 2002. | | | | 3)NOTE: PLEASE KNOW, A SITE SURVEY AND | | ELEVATIONS WERE NOT SUBMITTED FOR | | LOCATION OF GENERATOR AND BFE. | | PLEASE SEE LOCATIONS OF GEN IN | | NFPA-110,7.2.3* WHICH REFERENCES THE | | "SLOSH" CHARTS. | | | | 4)NOTE: PLEASE SUBMIT ALL THE | | MANUFACTURE'S CUT/SPEC SHEETS FOR | | GENERATOR, ATS, AND ANY NEW FUEL | | TANK(S). PLEASE BE SURE ALL SPECS/SHEETS | | CONTAIN LISTINGS FROM A NRTL. | | 215.5 | | | | 5)NOTE: PLEASE CORRELATE RISER ON E-1, | | WITH RISER ON E-2. | | PLEASE SEE NOTE #7 WHICH MENTIONS NEW | | CONDUITS FROM NEW MAIN, HOWEVER RISER | | SHOWS THIS AS EXIST TO REMAIN AND IS | | ALSO NOTED AS EXIST?? | | PLEASE SEE NOTE #3, WHICH SHOWS THIS | | NOTE FOR WHAT APPEARS TO BE A METER | | BEING REMOVED AND MAIN DISCONNECT? | | (MISPRINT?) | | PLEASE SEE RISER, AS SHOWN SEEMS TO BE | | MISPRINTED BACKWARDS ,?? | | | | 6)NOTE: PLEASE SEE EXISTING RISER SHOWS | | A EXISTING GEN DISC LCOATED INSIDE, | | NOTED TO BE REMOVED, YET NEW REVISED | | RISER SHOWS THIS DISCONNECT STILL | | LOCATED ON REVISED RISER? PLEASE | | CLARIFY, IF THE GEN DISC LOCATED INSIDE | | BLDG, IS BEING REMOVED. ALL ELECTRICAL | | EQUIPMENT NO LONGER IN USE SHOULD BE | | REMOVED. | | | | 7)NOTE: PLEASE PROVIDE OCP AT GENERATOR, | | PLEASE ALSO SEE 445.13. | | UNABLE TO VERIFY FEEDER SIZES, ETC . | | 215.5 | | | | | | 8)NOTE: PLEASE SEE 2004 FBC 108.3 CITY | | OF WEST PALM BEACH ADMINISTRATIVE CODE | | WHICH REQUIRES VALUE FOR SCOPE OF | | WORK/IMPROVEMENT TO INCLUDE ALL LABOR | | AND MATERIALS, EVEN IF EQUIPMENT IS | | OWNER SUPPLIED. | | PLEASE SEE VALUE IS TOO LOW FOR SCOPE OF | | WORK. | | | | 9)NOTE: PLEASE SEE BLDG REVIEW COMMENTS | | AS NO SLAB DETAIL WAS SUBMITTED. PLEASE | | SEE MIN REQUIREMENTS IN NFPA-110 AND | | ENGINEERING PRACTICES FOR A GENERATOR OF | | THIS SIZE AND WEIGHT. | | 7.2.1.1,7.4, 7.5* | | | | ** PLEASE SEE POSSIBLE COMMENTS FROM | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | PLANS. | | | | ** PLEASE BE SURE TO REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW | | REVISED SHEETS INTO COMPLETE SETS FOR | | REVIEW AND STAMPING. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2006-12-08 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-12-08 |
Time |
13:24 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-12-08 |
Time |
13:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2006-07-10 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2006-07-10 |
Time |
13:57 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2006-07-10 |
Time |
13:53 |
Sent To |
|
|
Notes |
2006-07-10 00:00:00 | 1. SURVEY PROVIDED WITH PERMIT | | APPLICATION IS DATED JUNE 6, 1986. THE | | SURVEY PROVIDED IS OVER TWENTY YEARS | | OLD. | | | | 2. NO PRODUCT APPROVALS OR SUBMITTAL | | DATE PROVIDED FOR THE GENERATOR, FEUL | | SUPPLY, LISTINGS, ETC. FOR THE | | APPLIANCE. | | | | 3. MORE DETAILS ARE NEEDED. | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | OFFICER | | 804-4709 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-03-24 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-03-24 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-03-24 |
Time |
15:20 |
Sent To |
|
|
Notes |
2006-03-24 00:00:00 | ******DENIED****** | | | | 1) PLEASE SUBMIT MANUFACTURER SPEC | | SHEETS FOR GENERATOR, FUEL TANK AND ALL | | ASSOCIATED EQUIPMENT. | | | | 2) PLEASE PROVIDE MORE INFORMATION | | REGARDING FUEL TANK SIZE, LOCATION ETC. | | EXISTING OR NEW? PROTECTION DEVICES MAY | | BE REQUIRED TO ELIMINATE MECHANICAL | | DAMAGE. | | | | 3) WORK SHALL COMPLY WITH APPLICABLE | | BUILDING CODES IN ADDITION TO NFPA 1 AND | | NFPA 110. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
Review Stop |
FUEL |
DIESEL GENERATOR |
Rev No |
2 |
Status |
N |
Date |
2006-10-31 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-10-31 |
Time |
09:30 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-10-31 |
Time |
09:28 |
Sent To |
|
|
Notes |
2006-10-31 09:30:43 | SUB-BASE FUEL TANK/SELF CONTAINED - NO FILL PIPING | | REQUIRED. |
|
|
Review Stop |
FUEL |
DIESEL GENERATOR |
Rev No |
1 |
Status |
F |
Date |
2006-07-28 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-07-28 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-07-28 |
Time |
14:10 |
Sent To |
|
|
Notes |
2006-07-28 00:00:00 | DENIED: | | 1.PLEASE INDICATE THE FUEL SOURCE FOR | | THE GENERATOR. | | | | 2.PLEASE PROVIDE MANUFACTURER | | SUBMITALL & INSTALLATION INSTRUCTIONS | | FOR THE GENERATOR. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
N |
Date |
2006-10-31 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-10-31 |
Time |
09:38 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-10-31 |
Time |
09:38 |
Sent To |
|
|
Notes |
2006-10-31 09:39:09 | DIESEL GENERATOR ONLY - GAS PERMIT NOT REQUIRED |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2006-07-28 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-07-28 |
Time |
14:19 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-07-28 |
Time |
14:18 |
Sent To |
|
|
Notes |
2006-07-28 00:00:00 | DENIED: | | INSUFFICIENT INFORMATION FOR REVIEW. | | PLEASE PROVIDE SUBMITTAL & INSTALLATION | | INSTRUCTIONS FOR THE GENERATOR. | | | | SHOULD THIS GENERATOR BE NATURAL GAS OR | | LP GAS GENERATOR, PLEASE PROVIDE THE | | INFORMATION INDICATED ON THE ATTACHED | | SHEET. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT KENNY STEVENS AT (561)805-6721 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-10-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-10-11 |
Time |
15:49 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-10-11 |
Time |
15:49 |
Sent To |
|
|
Notes |
2006-10-24 09:37:19 | TO "COMM" BD#24 | 2006-10-11 15:49:26 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-06-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-06-19 |
Time |
09:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-06-19 |
Time |
09:39 |
Sent To |
|
|
Notes |
2006-06-27 00:00:00 | TO "COMM" BD#23 | 2006-06-19 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-06-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-04-25 |
Time |
09:38 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-01-30 |
Time |
08:57 |
Sent To |
|
|
Notes |
2006-02-27 00:00:00 | TO "COMM" BD#25 | 2006-01-30 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2006-10-31 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-10-31 |
Time |
08:44 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-10-31 |
Time |
08:15 |
Sent To |
|
|
Notes |
2006-10-31 09:25:54 | PROVISO: | | | | EXHAUST FROM THE GENERATOR SHALL NOT BE LOCATED WITHIN | | 10 FT OF ANY DOOR, WINDOW, OR FRESH AIR INTAKE PER 2004 | | FMC 401.5.1. EXHAUST SHALL BE TERMINATE IN SUCH A | | MANNER AS NOT TO BE READILY DRAWN IN BY THE VENTILATING | | SYSTEM PER 2004 FMC 501.2. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected] | 2006-10-31 08:49:10 | | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2006-07-28 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-07-28 |
Time |
07:24 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-07-28 |
Time |
07:24 |
Sent To |
|
|
Notes |
2006-07-28 00:00:00 | DENIED: | | 2ND REQUEST: | | 1.PLEASE PROVIDE MANUFACTURER | | SUBMITTAL DATA FOR THE GENERATOR. | | | | 2.PLEASE INDICATE ON THE SITE PLAN THE | | FOLLOWING INFORMATION: | | | | A.LOCATION OF THE GENERATOR ON | | PLAN. | | B.DISTANCES TO BUILDINGS, PROPERTY | | LINES, AND FRESH AIR INTAKES | | (I.E. WINDOWS, DOORS, ETC.) | | | | 3.PLEASE INDICATE FUEL SOURCE - | | DIESEL, NATURAL GAS, LP GAS, ETC. | | | | 4.PLEASE PROVIDE ANCHORING DETAIL. | | | | 5.PLEASE PROVIDE A SLAB DETAIL. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-03-20 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2006-03-20 |
Time |
08:50 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2006-03-20 |
Time |
08:43 |
Sent To |
|
|
Notes |
2006-03-20 00:00:00 | PLANS DENIED | | PLEASE PROVIDE MANUFACTURERS | | INSTALLATION INSTRUCTIONS ON THE | | GANERATOR. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2006-10-31 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-10-31 |
Time |
09:39 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-10-31 |
Time |
09:39 |
Sent To |
|
|
Notes |
2006-10-31 09:40:03 | NO PLUMBING REQUIRED FOR DIESEL GENERATOR |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2006-07-28 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-07-28 |
Time |
14:22 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-07-28 |
Time |
14:22 |
Sent To |
|
|
Notes |
2006-07-28 00:00:00 | INSUFFICIENT INFORMATION FOR PROPER | | REVIEW. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2006-11-11 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2006-11-11 |
Time |
14:58 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2006-11-11 |
Time |
14:58 |
Sent To |
|
|
Notes |
2006-11-11 14:59:34 | PROVISO: THE PROPOSED GENERATOR MUST BE LANDSCAPE | | BUFFER FROM VIEW. THE PROPOSED GENERATOR SHALL NOT BE | | CLOSER THAN 14.34FT PROPERTY LINE. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2006-07-17 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2006-07-17 |
Time |
10:02 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2006-07-17 |
Time |
10:02 |
Sent To |
|
|
Notes |
2006-07-17 00:00:00 | DENIED, | | 1. THE SURVEY/SITEPLAN DOES NOT SHOW THE | | LOCATION OF THE PROPOSED GENERATOR AND | | THE SETBACK FROM THE PROPERTY LINE. | | 2. PLEASE SHOW THE LOCATION ON THE TWO | | COPY OF SURVEY/SITEPLAN WITH SETBACKS | | FROM PROPERTY LINE. | | | | NOTE: | | SEC 94-303 MECHANICAL/POOL | | EQUIPMENT/GENERATOR MAY NOT PROJECT MORE | | THAN FOUR FEET INTO A SETBACK. | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2006-04-06 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2006-04-06 |
Time |
17:03 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2006-04-06 |
Time |
17:03 |
Sent To |
|
|
Notes |
2006-04-06 00:00:00 | DENIED, | | 1. MUST PROVIDE TWO COPY OF SITEPLAN | | SHOWING THE LOCATION OF THE GENERATOR | | WITH SETBACKS. | | | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|