Plan Review Details - Permit 06011029
Plan Review Stops For Permit 06011029
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-08 Cont ID  
Sent By btrobaug Date 2006-03-08 Time 17:30 Rev Time 0.50
Received By btrobaug Date 2006-03-08 Time 17:11 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-01-30 Cont ID  
Sent By btrobaug Date 2006-01-30 Time 11:27 Rev Time 0.50
Received By btrobaug Date 2006-01-30 Time 07:51 Sent To PC
Notes
2006-01-30 00:00:00 
 PROVISO
 ~~~~~~~
  
 1} THE KITCHEN DETAIL IS NOT CLEAR
 ENOUGH TO VERIFY COMPLIANCE WITH
 210.52(C). RESUBMIT WITH KITCHEN DETAIL
 OR MORE CLARITY ON THE FLOOR PLAN,
 PERHAPS A LARGER SCALE DRAWING.
  
 2} INDICATE THE NEW PANEL LOCATION
 REFERRED TO IN THE NOTES.
  
 3} PLEASE PROVIDE A PANEL SCHEDULE SO
 THAT BRANH CIRCUIT COMPLIANCE CAN BE
 REVIEWED.
  
 PLEASE PROVIDE THE ABOVE INFORMATION
 PRIOR TO CALLING A ROUGH INSPECTION,
 ALLOW AT LEAST ONE WEEK FOR THE REVIEW
 PROCESS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-08 Cont ID  
Sent By adarroug Date 2006-03-08 Time 11:17 Rev Time 0.00
Received By adarroug Date 2006-03-08 Time 11:17 Sent To E
Notes
2006-03-08 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-30 Cont ID  
Sent By btrobaug Date 2006-01-30 Time 08:12 Rev Time 0.00
Received By btrobaug Date 2006-01-27 Time 15:13 Sent To E
Notes
2006-01-27 00:00:00TO "E" BOX