2006-02-01 00:00:00 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR A GAS PERMIT: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENTHS PER FBC-2004 |
| FUEL GAS CODE. (NOTE: YOUR DRAWING SHOWS |
| ONLY 35' OF U/G PE PIPE. HOW LONG ARE |
| THE RISERS?) |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| (NOTE: YOUR DRAWING ONLY SHOWS 3/4" PE |
| PIPE. WHAT SIZE, AND MATERIAL ARE THE |
| RISERS?) |
| 3. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34). (NOTE: HOUSE HAS EXISTING GAS, |
| EXISTING HOUSE AND TOTAL BTU LOADS NEED |
| TO BE NOTED ON DRAWING.) |
| |
| 4. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). (NOTE: THE |
| LONGEST LENGTH ON SYSTEM NEEDS TO NOTED |
| ON DRAWING IN ORDER TO CHECK SIZING WITH |
| TABLES.) |
| |
| END OF COMMENTS: |
| |