Plan Review Details - Permit 06010854
Plan Review Stops For Permit 06010854
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-01 Cont ID  
Sent By alange Date 2006-05-01 Time 14:52 Rev Time 0.00
Received By alange Date 2006-05-01 Time 13:53 Sent To  
Notes
2006-05-01 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SHOW GUARD RAIL DETAILS COMPLYING
 WITH FBC 2004 1012.3 AND 1607.7 FOR
 BALCONYS.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 LINTELS, FLAT ROOF, ROOF TILE, STRAPS
 AND TIE-DOWNS, EXTERIOR DOORS, WINDOWS,
 IMPACT PROTECTION AND STORE FRONT
 SYSTEM.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC.
  
 9.SUBMIT A LIFE SAFTEY PLAN.
  
 10.BUILDING IS IN FLOOD ZONE "A".
 SUBMIT A SOILS REPORT INCLUDING
 RECOMMENDATIONS FOR FOOTINGS DESIGN.
  
 11. MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.FBC 106.3.3 WPB AMMENDMENTS
  
 -CONSTRUCTION TYPE PER TABLE 503.
 -OCCUPANCY GROUP
 -OCCUPANCY LOAD
 -SQUARE FOOTAGE FOR ALL AREAS FOR
 EXAMPLE, BUSINESS, PARKING GARAGE,
 STORAGE AREAS.
 -INTERIOR FINISHES
  
 12.SUBMIT INTERIOR FLOOR PLANS
 INCLUDING SEPERATION OF AREAS.
  
 13.EXISTING BUILDING ON PROPERTIES.
 WILL THEY BE DEMOLISHED UNDER A SEPERATE
 PERMIT?
  
 14.SUBMIT AN APPROVED UNITY OF TITLE
 FOR THE FOLLOWING PARCELS.
 74434315190070021 AND
 74434315190070010
  
 15.SUITE 101 SUBMIT DETAILS FOR
 ADMISSION AREA SHOWING COMPLIANCE WITH
 FBC 11-7.
  
 16.ACCESSABLE PARKING SPACES MISSING
 AND NOT SHOWN AT ALL LEVELS.SHOW CLEAR
 PATH OF TRAVEL FROM PARKING TO BUILDING
 ENTRANCE.
  
 17. A-7 WEST ELEVATION; DOES NOT REFLECT
 GROUND FLOOR PLAN. SOUTH STAIRS NOT
 SHOWN, EXIT NOT SHOWN.
  
 18.A-7 EAST ELEVATION; WHAT IS "L" NOT
 SHOWN ON 3RD FLOOR
  
 19.A-8.1 STAIR DETAIL, DOOR NOT SHOWN.
  
 20. ROOF FRAMING IS ON GROUND FLOOR
 FRAMING PAGE.
  
 21.SHOW HOW ELEVATORS WILL COMPLY FOR
 ACCESSABLILITY PER FBC 11-4.10
  
 22.SHOW CLEAR HEIGHT OF PARKING GARAGE
 FBC 406.2.2
  
 23. OPEN PARKING GARAGE SHALL BE OF TYPE
 I, II OR IV CONSTRUCTION.
  
 24.HANDICAP PARKING SPACES SHALL BE IN
 CLOSE PROXIMATY TO THE ELEVATOR.
  
 25.MONUMENTAL STAIRS SHALL HAVE AN
 INTERMEDIATE HANDRAIL.FBC 1009.11.2
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-27 Cont ID  
Sent By dpalmer Date 2006-02-27 Time 18:42 Rev Time 0.00
Received By dpalmer Date 2006-02-27 Time 17:19 Sent To  
Notes
2006-02-27 00:00:00*********UNSAT *********
  
 1)NOTE: PLEASE SEE TITLE BLOCK ON PLANS
 SHALL INDICATE THE ADDRESS AND LOCATION
 OF PROJECT.
 FAC 61G15-23.002,61G1-16.003
  
 2)NOTE: PLEASE BE SURE THE FOLLOWING
 CODES IN EFFECT ARE REFERENCED:
 2003 NFPA-101, 2002 NFPA-72, 2002
 NFPA-70.
 PLEASE SEE SOME CODES ETC ARE REFERENCED
 FROM THE 2001 FBC.
  
 3)NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS NEW MEDICAL OFFICE BLDG,
 HOWEVER NO INTERIOR PLANS WERE
 SUBMITTED. PLEASE SEE NOT EM/ EXT LTS
 PER FIRE REVIEW COMMENTS?
  
 4)NOTE: PLEASE PROVIDE PHOTOMETRICS FOR
 STAIR TOWERS AS NEW STAIRS IN 2003
 LS101, 7.8.1.3 REQUIRES 10FT CANDLES,
 UNDER NORMAL POWER AND 1FT CANDLE MIN
 UNDER EM. 7.9.2.2
 PLEASE ALSO SEE EM LTS FOR EGRESS PATH
 IN PARKING GARAGE COOULD NOT BE LOCATED.
 PLEASE ALSO PROVIDE A BATTERY BACK UP LT
 FIXTURE OF SOME SORT IN MAIN ELECTRICAL
 RM, ELEVATOR MACHINE RM AND LOCATION
 WHERE FACP IS BEING MOVED TO PER FIRE
 REVIEW COMMENTS.
 7.8,7.9,700.16, 700.12E ETC.
  
 5)NOTE: PLEASE SEE FBC 2004 CHAPTER 13,
 FOR COMMERCIAL BLDGS. PLEASE SEE
 13-413.1.ABC.1.1 &.2 FOR VOLTAGE DROP
 INFORMATIO TO BE PROVIDED.
 PLEASE SEE VERIFY COMPLIANCE FOR
 INTERIOR OF BLDG IF IN SCOPE OF WORK?
  
 6)NOTE: PLEASE SEE COMMENTS FROM OTHER
 TRADES FOR POWER FOR FAN POWER IN THE
 EVENT OF POWERE FAILURE, GATE CONTROLS
 FOR OPERATION OF THESE GATES AFTER POWER
 HAS BEEN LOST.
 PLEASE SEE ANY POSSIBEL COMMENTS FROM
 OTHER TRADES WHICH WILL AFFETC
 ELECTRICAL PLANS.
  
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETED SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IFTHERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-04-07 Cont ID  
Sent By mamini Date 2006-04-07 Time 14:41 Rev Time 1.00
Received By mamini Date 2006-04-07 Time 14:40 Sent To  
Notes
2006-04-07 00:00:00FAILED:
  
 1. PLEASE SUBMIT CALCULATION FOR STORM
 WATER, NOTE THAT, IT MUST BE DESIGN PER
 CITY' REQUIREMENTS AND CRITERIA.
 2. CIVIL PLANS MUST BE REVIEWED BY THE
 ENGINEERING SERVICES, FOR ALL THE
 CONNECTIONS TO THE CITY SERVICES,
 494-1085. MANNY GONZALEZ.
 3. A SEPARATE PERMIT AND REVIEW BY THE
 PB COUNTY FOR 12TH ST IMPROVEMENT AND BY
 THE FDOT FOR N. OLIVE AVE. WOULD BE
 REQUIRED.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-02-16 Cont ID  
Sent By mcarsill Date 2006-02-16 Time 11:03 Rev Time 0.00
Received By mcarsill Date 2006-02-16 Time 11:02 Sent To  
Notes
2006-02-16 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. EXIT STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 3. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 4. WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 5. BUILDING WILL BE REQUIRED TO BE FIRE
 SPRINKLERED IN ACCORDANCE WITH 553.895
 (2).
  
 6. THE ELECTRICAL DRAWINGS NEED TO BE
 EXAMINED. IT DOES NOT APPEAR ENOUGH EXIT
 SIGNS OR EMERGENCY LIGHTS EXIST OR ARE
 CALLED OUT ON THE DRAWINGS. EXIT SIGNS
 SHALL NOT EXCEED 100 FEET APART. ALL
 EXITS SHALL BE CLEARLY IDENTIFIED AND
 MARKED.
  
 7. PLEASE EXPLAIN 6" RISERS FOR
 MONUMENTAL STAIR.
  
 8. BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION. A MINUMUM OF AT LEAST 6" HIGH
 NUMBERS ARE REQUIRED.
  
 9. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM. THE FIRE ALARM
 SYSTEM SHALL BE MONITORED BY A LICENSED
 UL LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 10. PLEASE PROVIDE MORE DETAILS ON
 EXHAUST FAN 2. WHEN DOES IT RUN AND WHAT
 OCCURS WHEN LOSS OF POWER OCCURS TO THE
 BUILDING.
  
 11. NO EXIT SIGNS SHOWN ON PAGE E-2,
 GROUND LEVEL.
  
 12. ELECTRONIC SWITCHES, CHAIN AND LOCK
 REQUIRED ON FIRE LINE BACKFLOW DEVICE.
  
 13. PLEASE PROVIDE A LIFE SAFETY PLAN
 ILLUSTRATING EXIT ROUTES, TRAVEL
 DISTANCES, ANY DEAD-END CONDITIONS, ETC.
  
 14. COULD NOT LOCATE ANY EXISTING OR NEW
 FIRE HYDRANTS ON WATER AND SANITARY
 SEWER PLANS.
  
 15. NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
  
 16. THIS OFFICE WILL NOT ACCEPT THE FIRE
 ALARM CONTROL PANEL IN THE BASEMENT.
 PLEASE REVISE DRAWING.
  
 17. DOOR SCHEDULE DOES NOT ILLUSTRATE
 REQUIRED FIRE RATINGS. PLEASE REVISE
 PLANS.
  
 18. A MINIMUM OF AT LEAST A TWO HOUR
 HORIZONTAL FIRE SEPERATION IS REQUIRED
 BETWEEN THE PARKING AREA AND OTHER
 PORTIONS OF THE BUILDING.
  
 19. PLEASE DISPLAY FIRE EXTINGUISHER
 LOCATIONS.
  
 20. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR ALL WALLS AND
 CEILINGS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-01 Cont ID  
Sent By alange Date 2006-05-01 Time 14:52 Rev Time 0.00
Received By alange Date 2006-01-23 Time 15:15 Sent To  
Notes
2006-02-13 00:00:00TO "COMM" BD#63
2006-01-23 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-13 Cont ID  
Sent By pkrauss Date 2006-03-13 Time 11:05 Rev Time 0.00
Received By pkrauss Date 2006-03-03 Time 09:33 Sent To  
Notes
2006-03-13 00:00:00DENIED:
 1.PLAN INDICATES A BASEMENT LEVEL.
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 IN ACCORDANCE WITH 2004 FMC 404.1
 THROUGH 404.3.
  
 2.PLAN SHEET MP-1 INDICATES AC-1,
 PLEASE PROVIDE HANGING DETAIL.
  
 3.PLAN SHEET M-1 PLEASE PROVIDE
 INFORMATION ON VENTILATION TO THE
 STORAGE AREAS.
  
 4.PLAN SHEET MP-2 PLEASE CLARIFY THE
 RATING OF THE WALL WHERE EF-2
 TERMINATES.PROVIDE DISTANCE TO THE
 PROPERTY LINE. SHOW COMPLIANCE WITH 2004
 FMC 401.5, 401.5.2, & 501.2.
  
 5.PLEASE CLARIFY THE MECHANICAL CHASE
 WITH EXHAUST, FRESH AIR DUCT, & PIPING.
 SHOW COMPLIANCE WITH NFPA 90A-02
 5.3.4.5.PLEASE NOTE, ACCESS FOR
 SERVICE & INSPECTION OF THE HORIZONTAL
 FIRE DAMPER.
  
 6.PLEASE CLARIFY THE RATING OF THE
 CEILING/ROOF ASSEMBLY.
  
 7.PLEASE PROVIDE DETAIL FOR THE ROOF
 JACK, GOOSENECK & THE CONDENSING UNIT
 STANDS.STANDS AND CURBS SHALL COMPLY
 WITH 2004 FBC 1509.7.
  
 PLANS APPEAR TO BE FOR A "SHELL
 BUILDING" ONLY.ADDITIONAL EQUIPMENT
 AND DUCT LAYOUT WILL BE REQUIRED FOR THE
 INTERIOR BUILD-OUT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-24 Cont ID  
Sent By kstevens Date 2006-03-24 Time 17:01 Rev Time 0.00
Received By kstevens Date 2006-03-24 Time 17:01 Sent To  
Notes
2006-03-24 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY CODE WPB
  
 1. MINIMUM FACILITIES PER TABLES
 1004.1.2 AND 104.3 REQUIRE 5 WATER
 CLOSETS, AND 4 LAVS. ONLY ONE WATER
 CLOSET AND ONE LAV IS SHOWN.
 2. SUBMIT A DETAIL FOR THE ACCESSIBLE
 TOILET ROOMS. SHOW THE FOLLOWING:
 FOR THE W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 FOR THE LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
 FOR THE TOILET ROOMS:
 A. 11-4.22.3 5' TURNING AREA
 3. SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAIN REQUIRED TO BE ACCESSIBLE PER
 SECTION 11-4.1.3(10). DRINKING FOUNTAINS
 APPEAR TO BE HI/LOW, IF NOT SHOW
 COMPLIANCE WITH SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
 4. SHT A-5 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS.
 SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE SQUARE FOOTAGE
 AREA BEING DRAINED FOR EACH DRAIN ALONG
 WITH 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS BEING ADDED TO THE
 AREA OF THE ROOF.
 5. SCUPPER DRAINS SHALL BE SIZED IN
 ACCORDANCE WITH TABLE 1106.7, & SECTIONS
 1107.3 AND 1101.7. THE SIZING OF THE
 SCUPPERS CAN NOT BE DETERMINED WITHOUT
 REFERENCE TO THE DEFLECTION OF THE ROOF.
 PLEASE STATE ON THE PLANS THAT SCUPPER
 SIZES COMPLY WITH SECTIONS AND TABLE
 MENTIONED ABOVE.
 6. AHT A-8.2 BUILDING SECTION INDICATES
 THE SCUPPER TO BE 8" ABOVE THE ROOF. PER
 SECTION 1503.4.3, OVERFLOW SCUPPERS
 SHALL BE PLACED IN WALLS NOT LESS THEN
 2" OR MORE THAN 4" ABOVE THE FINISHED
 ROOF COVERING.
 7. SHT MP-1 DRAINAGE LINES INDICATE 4"
 RD, 2" CONDENSATE & 4" SANITARY ALL
 COMBINED IN ONE DRAINAGE LINE. THIS IS
 NOT APPROVED PER SECTIONS 125-90(5) AND
 90-203 OF THE CITY OF WEST PALM BEACH
 MUNICIPAL CODE. SEPARATE SANITARY, STORM
 AND CONDENSATE LINE ARE REQUIRED. SHOW
 THE PIPING FOR THESE SYSTEMS ON THE FLAT
 DRAWINGS TO REFLECT THE REQUIRED RISER
 DIAGRAMS. CONDENSATE SHALL DRAIN
 SEPARATELY OUT OF THE BUILDING, BUT CAN
 TIE INTO THE STORM LINES OUTSIDE THE
 BUILDING AND SHALL HAVE A RELIEF VENT,
 (GOOSE NECK), INSTALLED AS THE
 CONDENSATE EXITS THE BUILDING.
 8. SUBMIT A SANITARY RISER ISOMETRIC
 DIAGRAM. SHOW ALL PIPE SIZES, TRAPS,
 VENTS ETC. THE RISER DIAGRAM SHALL SHOW
 ALL PIPING FROM 5' OUTSIDE THE BUILDING,
 ALL BUILDING DRAIN PIPING, ALL FIXTURE
 PIPING, INCLUDING FUTURE STUBOUTS FOR
 DRAINAGE AND VENT, AND INDICATE DRAINAGE
 FIXTURE UNITS AS THEY ACCUMULATE IN THE
 SYSTEM. SECTION 106.3.5.1.3(4).
 9. SUBMIT A STORM ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VERTICAL
 RISERS, AND INDICATE THE SQUARE FOOTAGE
 AS IT ACCUMULATES IN THE SYSTEM. SECTION
 106.3.5.1.3(7).
 10. SUBMIT A WATER ISOMETRIC RISER
 DIAGRAM SHOW ALL PIPE SIZES, VALVES, AND
 WATER HAMMER ARRESTORS IF REQUIRED BY
 SECTION 604.9. WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING.
 RISER DIAGRAM SHALL SHOW ALL PIPING FROM
 THE ENTRANCE TO THE BUILDING TO THE LAST
 FIXTURE INCLUDING ALL FUTURE STUBOUTS
 WITH VALVES AND CAPS. SECTION
 106.3.5.1.3(10).
 11. PLANS SEEM INCOMPLETE AND MORE
 COMMENTS MAY BE FORTHCOMING DEPENDING ON
 THE COMMENT RESPONSES AND ADDED
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-04 Cont ID  
Sent By mflis Date 2006-04-04 Time 10:29 Rev Time 0.00
Received By mflis Date 2006-04-04 Time 10:03 Sent To  
Notes
2006-04-04 00:00:001. SHOW EDGE OF CURB, SITE TRIANGLES
 GROUND FLOOR PLAN
 2. PARKING MUST BE INDICATED BY CITY
 STANDARD DOUBLE STRIPING
 3. PROVIDE STANDARD CITY PARKING DETAILS
 4. 48 PARKING SPACES INDICATED -
 REQUIRES (2) ACCESSIBLE STALLS; ONLY ONE
 CURRENTLY INDICATED
 5. PROVIDE PROJECT FACT SHEET -
 INDICATING FLOOR AREA, PARKING, AND
 HANDICAP CALCULATIONS
 6. SHEET A-2 - INDICATE DIMENSION FROM
 WEST PROPERTY LINE TO BUILDING EDGE
 7. SHEET A-2 - 7'-5" PARKING STALL (FAR
 SOUTHWEST CORNER) NOT USUABLE. STRIPE TO
 BE TURN-AROUND AREA.
 8. SHEET A-3 - INDICATE DIMENSION FROM
 EAST PROPERTY LINE TO BUILDING; TO MEET
 APPROVED VARIANCE
 9. SHEET A-3 - PROVIDE DIMENSION STRING
 FOR PARKING; TO MEET APPROVED VARIANCE
 10. SHEET A-3 - COVERED PARKING DRIVE AT
 FAR SOUTH END OF PROPERTY INTRUDES INTO
 5'-0" SETBACK; REMOVE LAST PARKING SPACE
 AND ADJUST DRIVE TO MEET SETBACK REQ'S