Plan Review Details - Permit 06010844
Plan Review Stops For Permit 06010844
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-10 Cont ID  
Sent By mjacobs Date 2006-04-10 Time 17:43 Rev Time 0.00
Received By mjacobs Date 2006-04-10 Time 10:38 Sent To PC
Notes
2006-04-10 00:00:001) NEED PRODUCT APPROVAL FOR NEW INPACT
 GLASS DOOR.106.3.3* PRODUCT APPROVALS-
 2004 THOSE PRODUCTS THAT ARE RGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.TWO COPIES WITH
 THE STATE COVER SHEETS REQUIRED.
  
 2) ALL AWNINGS SHALL BE DESIGNED SO THAT
 FABRIC OR MEMBRANE COVER CAN BE QUICKLY
 AND EASILY REMOVED PER 3105.4.2.1
 TIGHTLY WRAPED OR WOVEN CORDS ARE NOT
 ACCEPTABLE. PLEASE SUBMIT A DETAIL
 DRAWING OF COBER ATTATCHMENT METHOD.
  
 3) 11-4.13.6 MANEUVERING CLEARANCES AT
 DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS
 THAT ARE NOT AUTOMATIC ORPOWER-ASSISTED
 SHALL BE AS SHOWN IN FIGURE 11-25 . THE
 FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE LEVEL AND CLEAR. SEE
 FIG.25 (A).
  
 4) 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS. SEE INFORMATION ON
 PARKING SPACE IN PACKAGE.
  
 5) THE ENERGY EFFICIENCY CODE FORMS ARE
 REFERENCING THE 2001 CODE. HOWEVEER ALL
 APPLICATIONS SUBMITTED AFTER OCTOBER 1ST
 SHALL REFER TO THE 2004 FBC.
 SEE 13-4000.0.A FOR MORE INFORMATION.
  
 6) THE BOARD AMENDED ITS SEALS RULE
 EFFECTIVE FEBRUARY 5TH, 2004, TO ALLOW
 ENBOSSING SEALS MADE OF MATERIALS OTHER
 THAN METAL AND AT THE SAME TIME CLEANED
 UP THE APPERANCE OF THE SEAL BY
 ELIMINATING OBSOLETE CONTENT AND
 CHANGING THE WORD "CERTIFICATE" TO
 "LICENSE". 61G15-23.001(1),F.A.C.
 SEE MORE INFORMATION IN PACKAGE.
  
 7) THE APPLICATION DOES NOT MENTION A
 FOUNTAIN. WILL THE FOUNTAIN BE DONE ON A
 SEPERATE PERMIT? IF SO SUBMIT PLANS WITH
 ALL REQUIRED INFORMATION AND DETAILS ON
 THE FOUNTAIN.
  
 8) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-16 Cont ID  
Sent By dpalmer Date 2006-02-16 Time 16:10 Rev Time 0.00
Received By dpalmer Date 2006-02-16 Time 16:10 Sent To  
Notes
2006-02-16 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.001 WHICH
 REQUIRED THE RAISED SEAL TO CHANGE FROM
 THE WORDING OF "CERTIFICATE" TO
 "LICENSE" BY 2/5/04, HOWEVER AN
 EXTENSION WAS GRANTED BY THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS TO
 DECEMBER 31,2005.
 PLEASE KNOW SEAL SHALL CONTAIN THE ABOVE
 WORDING ON RAISED SEAL AS REQUIRED.
 FS 471.025
 ANY STAMPED PLANS SHALL BECOME "VOID".
  
  
 2)NOTE: PLEASE SUBMIT ELECTRICAL WIRING
 DIAGRAM/DETAIL FOR ALL FOUNTAIN
 EQUIPMENT AND WIRING.
 PLEASE PROVIDE GROUNDING DETAIL PER 680.
 PLEASE SHOW HOW EQUIPMENTON PLANS
  
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE(S).
 PLEASE SEE 700.12E WHICH REQUIRES THE
 EXT/ EM LTS TO BE CIRCUITED TO THE LOCAL
 LIGHTING IN ANY ONE AREA.
  
 4)NOTE: PLEASE CORRELATE PLANS WITH
 RISER, AS LIGHTING PLANS SHOW A PANEL
 LOCATED OUTSIDE , WHERE-AS POWER PLANS
 SHOWS AND NEW MAIN DISCONNECT AS RISER
 SHOWS.
  
 5)NOTE: PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR SHALL BE SIZED PER
 250.66. PLEASE SEE A 1/0 MIN IS
 REQUIRED.
 PLEASE ALSO SEE MISSING CWP AS REQUIRED
 PER 250.50,250.52A
  
 6)NOTE: PLEASE INCLUDE SEC'S FROM METER
 TO MAINS.
 215.5,240.4,310.16
  
 7)NOTE: PLEASE REFERENCE THE FOLLOWING
 CODES ON PLANS.
 2002 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 PLEASE ALSO SEE BLDG REVIEW COMMENTS AS
 REFERENCE TO THE 2004 FBC COULD NOT BE
 LCOATED.
  
 8)NOTE: PLEASE SEE POSSIBLE MISSING
 CA/FIRM LICENSE # FOR ARCHITECTUAL FIRM.
 61G1-16.004, FS 481.219
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** PLEASW KNOW, ALL OLD/VOIDED SHEETS
 MUST BE REMOVED FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETED
 SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-02-16 Cont ID  
Sent By mcarsill Date 2006-02-16 Time 09:45 Rev Time 0.00
Received By mcarsill Date 2006-02-16 Time 09:23 Sent To  
Notes
2006-02-16 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION SHALL COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3. AWNINGS ARE TO BE FIRE RETARDANT.
  
 4. ELECTRIC STRIKES FOR DOORS SHALL NOT
 INTERFERE WITH ANY EXITING. SPECIAL
 LOCKING ARRANGEMENTS MUST BE MET IF
 PLANNED TO BE USED.
  
 5. BUILDING ADDRESS REQUIRED. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 6. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 7. PLEASE PROVIDE FLAMESPREAD DETAILS
 FOR MATERIAL USED TO SEPARATE AREAS.
  
 8. PLEASE ILLUSTRATE FIRE EXTINGUISHER
 LOCATIONS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-04-10 Time   Rev Time 0.00
Received By adarroug Date 2006-01-24 Time 10:27 Sent To  
Notes
2006-02-15 00:00:00TO "COMM" BD#4
2006-01-24 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-02 Cont ID  
Sent By pkrauss Date 2006-03-02 Time 15:24 Rev Time 0.00
Received By pkrauss Date 2006-03-02 Time 13:49 Sent To  
Notes
2006-03-02 00:00:00DENIED:
 1.RETURN AIR REQUIRED FROM THE CENTRAL
 RETURN BY A DOOR.PLAN SHEET M1THE
 KERASTASE ROOM DOES NOT INDICATE A
 RETURN.PLEASE SHOW COMPLIANCE WITH
 2004 FMC 601.4.
  
 2.PER 2004 FMC TABLE 403.3, PUBLIC
 RESTROOMS SHALL HAVE MECHANICAL EXHAUST
 WITH AIR MAKE-UP.RE-CIRCULATION OF
 THIS AREA IS PROHIBITED.
  
 3.CONDENSATE SHALL TERMINATE A MINIMUM
 OF 12" AWAY FROM THE BUILDING STRUCTURE,
 IN ACCORDANCE WITH 2004 FBC 1503.6.
  
 4.WITH REGARDS TO THE EXHAUST FROM THE
 MANICURE AREA.PER 2004 FMC 502.1.1
 INLET TO AN EXHAUST SYSTEM SHALL BE
 LOCATED IN THE AREA OF HEAVIEST
 CONCENTRATION OF CONTAMINANTS.
  
 5.PLANS DO NOT INDICATE DUCTWORK OR
 TERMINATION FOR THE DRYER EXHAUST.
 PLEASE SHOW COMPLIANCE WITH 2004 FMC
 504.
  
 6.NO COMBUSTIBLES ALLOWED IN THE AHU
 CLOSET WHICH APPEARS TO BE A PLEMUM.
 THIS APPLIES TO THE LOUVERED DOOR &
 FRAME ALSO.PER 2004 FMC MATERIALS
 EXPOSED WIHTIN PLENUMS SHALL HAVE A
 FLAME INDEX OF NOT MORE THAN 25 & A
 SMOKE DEVELOPED INDEX OF NOT MORE THAN
 50 WHEN TESTED IN ACCORDANCE WITH ASTM
 84.PLEASE VERIFY DOOR ASSEMBLY.
  
 7.DUCT SMOKE DETECTORS REQUIRED FOR
 ALL OF THE A/C SYSTEMS PER 2004 FMC
 606.2.2.PLEASE PROVIDE NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS
 PER 2004 FMC 606.4.1 EXCEPTION #2.
  
 8.PLEASE PROVIDE MANUFACTURE SUBMITTAL
 DATA FOR THE CONDENSING UNIT STAND
 INDICATED ON PLAN SHEET M2.INDICATE
 CLEARANCE FROM THE ROOF SURFACE TO THE
 BOTTOM OF THE SUPPORT RAIL.SHOW
 COMPLIANCE WITH 2004 FBC 1509.7.
  
 9.PROVIDE DETAIL FOR THE ATTACHMENT OR
 ANCHORING OF THE CONDENSING UNIT STAND
 IN ACCORDANCE WITH 2004 FMC 301.13 & FBC
 1603.1.4.
  
 10. PLEASE INDICATE ROOF ACCESS FOR THE
 SERVICE & MAINTENANCE OF THE ROOFTOP
 EQUIPMENT.2004 FMC 306.5.
  
 11. PLAN SHEET M4 DETAIL FOR THE AHU.
 OVERFLOW PROTECTION IS NOT INDICATED.
 SHOW COMPLIANCE WITH 2004 FMC 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-14 Cont ID  
Sent By kstevens Date 2006-03-14 Time 10:24 Rev Time 0.00
Received By kstevens Date 2006-03-13 Time 18:59 Sent To  
Notes
2006-03-14 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. A DATED
 SEAL IS REQUIRED, AND THE ARCHITECTS
 TITLE BLOCK SHALL BE UPDATED WITH THE
 CORRECT ADDRESS. (SEE ATTACHED SHEET
 FROM FLORIDA DBPR). FAC
 61G1-16.004(1)(5) AND FS 481.2055.
 2. SHT A1 SHOWS A FOUNTAIN. THIS IS NOT
 INDICATED ON THE APPLICATION "DESCRIBE
 PROJECT IN DETAIL". WILL THIS BE ON A
 SEPARATE PERMIT WITH SEPARATE PLANS? THE
 VALUE OF THE FOUNTAIN SHALL BE WITH THE
 SEPARATE PLANS/PERMIT.
 3. SHT A2 FOUNTAIN PUMP. SUBMIT MANUF.
 SPECIFICATIONS FOR FOUNTAIN PUMP. PUMP
 SHALL BE LISTED. SECTION 303.4
 4. SHT A2 PER TABLE 403.1 A DRINKING
 FOUNTAIN IS REQUIRED. SHOW THE LOCATION
 ON THE FLOOR PLAN, AND SHOW PIPING ON
 PLUMBING PLANS. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS, AND IF NOT A HI/LOW SHOW A
 DETAIL FOR SECTION 11-4.15..1.3(10)(A)
 REQUIREMENTS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 5. SHT A2 ENTRY PLAZA INDICATES SLOPE TO
 DRAIN. DRAIN NOT SHOWN. PLEASE CLARIFY.
 SECTION 106.1.1. INDICATE WHAT AND WHERE
 THE DRAIN WILL CONNECT TO. SUBMIT PIPING
 PLANS SHOWING ALL PIPE SIZES ETC.
 106.3.5.1.3.
 6. SHT A5 TOILET ROOM ELEVATIONS. SHOW
 THE FOLLOWING:
 FOR W/C'S:
 A. 11-4.16.5 FLUSH CONTROLS
 FOR LAVS:
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. 11-4.19.5 FAUCETS
 7. SHT A8 DETAIL "A" SINK SHALL BE
 ACCESSIBLE. DETAIL SHALL SHOW COMPLIANCE
 WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. FORWARD APPROACH TO SINK
 REQUIRED. A 5' TURNING AREA IS REQUIRED
 IN SINK AREA. SECTION 11-4.2.3.
 8. ALL PLUMBING, MECHANICAL, &
 ELECTRICAL SHEETS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE
 NUMBER AS WELL AS, THE NAME, ADDRESS,
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS ON EACH
 SHEET. FAC 61G15-23.002(2) & FS 471.025.
 9. SHT P2 SANT. RISER DIAGRAM, 3" IS
 REQUIRED UP TO THE WASH MACHINE TEE.
 SECTION 406.3. CLEANOUT SHALL BE MINIMUM
 4' ABOVE THE FLOOR FOR ACCESS. SECTION
 708.9.
 10. SHT P2 SANT. RISER DIAGRAM, HAIR
 WASH SINKS, (GROUP OF 4), ARE NOT
 VENTED. EITHER ISLAND VENTS OR AAV'S ARE
 REQUIRED. SECTION 901.2.1.
 11. SHT P2 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS ARE REQUIRED AT THE
 WASH MACHINE AND AT THE REF. ICE MAKER.
 SECTION 604.9. THESE SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
 12. SHT P2 PLUMBING SPECIFICATIONS #13
 INDICATES "K COPPER" FOR UNDERGROUND.
 RISERS DIAGRAM SHOWS FITTINGS. NO SOLDER
 JOINTS ARE APPROVED UNDER THE SLAB.
 PIPING SHOULD BE LOOPED FROM SINK TO
 SINK WITH THE MANIFOLD ABOVE THE SLAB.
 SECTION 604.10.3.
 13. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2.
 BACKFLOW SHALL BE LOCATED AS CLOSE TO
 THE WATER METER AS POSSIBLE ON PRIVATE
 PROPERTY.
 14. SHT P2 PLUMBING NOTES #1 INDICATES
 120 GALLON WATER HEATER, BUT SHT A2
 FLOOR PLAN SHOWS AN 80 GALLON WATER
 HEATER. PLEASE CORRELATE ARCHITECTURAL
 AND PLUMBING SHEETS. SECTION 106.1.1.
 15. MORE INFORMATION IS REQUIRED ON THE
 CONDENSATE SYSTEM. INDICATE HOW AHU'S
 ARE TO BE DRAINED. SUBMIT A CONDENSATE
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE
 SIZES, AND TERMINATION POINT. INDICATE
 MATERIAL TYPE. SECTION 106.3.5.1.3.
 16. SEPARATE PLANS REQUIRED FOR
 FOUNTAIN. SHOW ALL PIPE SIZES AND ALL
 PIPING FROM AND TO THE PUMP. INDICATE IF
 THERE IS A DRAIN FOR THE FOUNTAIN AND
 WHERE IT DRAINS TO. INDICATE IF THERE IS
 A FILTER FOR THE SYSTEM, AND IF THERE IS
 A WATER SUPPLY FOR THE FOUNTAIN. IF
 THERE IS A WATER SUPPLY, BACKFLOW
 PREVENTION IS REQUIRED. INDICATE METHOD
 OF BACKFLOW PREVENTION. SECTIONS
 106.1.1. AND 608.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status   Date 2006-04-13 Cont ID  
Sent By mmclean Date 2006-04-07 Time 11:26 Rev Time 0.00
Received By mmclean Date 2006-04-07 Time 11:26 Sent To  
Notes
2006-04-07 00:00:00OK FOR CHANGE OF USE.
  
 NOTE: PARKING MUST BE DOUBLED STRIPPED.
  
  