Plan Review Details - Permit 06010733
Plan Review Stops For Permit 06010733
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-07-24 Cont ID  
Sent By mperson Date 2006-07-24 Time 15:55 Rev Time 0.33
Received By mperson Date 2006-07-24 Time 15:55 Sent To PC
Notes
2006-07-24 00:00:00NOTE: DUPLICATE PERMIT AND STAMPED PLANS
  
 ******PROVISO******
 (A) PER FBC-2004 FUEL GAS, SECTION 409.4
 MP REGULATORS: A LISTED SHUTOFF VALVE
 SHALL BE INSTALLED IMMEDIATELY AHEAD OF
 EACH MP REGULATOR.
  
 (B) IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 (C) IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,750 CUBIC FEET REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-01-27 Cont ID  
Sent By mperson Date 2006-01-27 Time 15:36 Rev Time 1.25
Received By mperson Date 2006-01-27 Time 15:36 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-21 Cont ID  
Sent By adarroug Date 2006-07-21 Time 14:37 Rev Time 0.00
Received By adarroug Date 2006-07-21 Time 14:37 Sent To G
Notes
2006-07-21 00:00:00TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-27 Cont ID  
Sent By mperson Date 2006-01-27 Time 15:37 Rev Time 0.00
Received By mperson Date 2006-01-22 Time 12:13 Sent To PC
Notes
2006-01-22 00:00:00TO "G" BOX