Plan Review Details - Permit 06010615
Plan Review Stops For Permit 06010615
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-02-21 Cont ID  
Sent By amorse Date 2006-02-21 Time 16:09 Rev Time 0.00
Received By amorse Date 2006-02-21 Time 16:09 Sent To PC
Notes
2006-02-21 00:00:00 
 ***PROVISO***
  
 POOL BARRIER REQUIREMENTS PER 424.2.17
 OR R4101.17 SHALL BE IN PLACE AT POOL
 FINAL INSPECTION PER R4101.19

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-04 Cont ID  
Sent By jleahy Date 2006-03-04 Time 09:51 Rev Time 0.45
Received By jleahy Date 2006-03-04 Time 09:51 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-01-30 Cont ID  
Sent By jleahy Date 2006-01-30 Time 16:02 Rev Time 0.45
Received By jleahy Date 2006-01-30 Time 16:02 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-02-02 Cont ID  
Sent By mperson Date 2006-02-02 Time 11:16 Rev Time 0.00
Received By mperson Date 2006-02-02 Time 11:16 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-02 Cont ID  
Sent By adarroug Date 2006-03-02 Time 19:11 Rev Time 0.00
Received By adarroug Date 2006-03-02 Time 19:11 Sent To E
Notes
2006-03-02 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 08:55 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 08:55 Sent To E
Notes
2006-01-27 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-21 Cont ID  
Sent By amorse Date 2006-02-21 Time 16:09 Rev Time 0.00
Received By amorse Date 2006-01-18 Time 15:25 Sent To  
Notes
2006-01-18 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-03-07 Cont ID  
Sent By mperson Date 2006-03-07 Time 07:23 Rev Time 1.00
Received By mperson Date 2006-03-07 Time 07:23 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-02-02 Cont ID  
Sent By mperson Date 2006-02-02 Time 10:33 Rev Time 1.00
Received By mperson Date 2006-02-02 Time 10:33 Sent To B
Notes
2006-02-02 00:00:00DENIED
 REFERENCE:FBC-2004 424.2 SWIMMING POOLS
 AND FBC 2004 RES. R4101 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAIL, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW:
  
 1) COMPLY WITH FBC-2004 SEC.424.2 OR
 FBC-2004 RES. R4101 PRIVATE SWIMMING
 POOLS (ADD TO NOTES)
 2) FBC-2004424.2.6.6.5 OR FBC-2004
 RESIDENTIAL R4101.6.6.5
 WHERE PROVIDED THE VACUUM OR PRESSURE
 CLEANER FITTING SHALL BE LOCATED AT
 LEAST 6" AND NOT GREATER THAN 12" BELOW
 THE MINIMUM OPERATING WATER LEVEL OR AS
 AN ATTACHMENT TO THE SKIMMER. (ADD TO
 NOTES, DETAIL REQUIRED)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-26 Cont ID  
Sent By mmclean Date 2006-01-24 Time 17:43 Rev Time 0.00
Received By mmclean Date 2006-01-24 Time 17:43 Sent To I
Notes
***NONE***