Plan Review Details - Permit 06010452
Plan Review Stops For Permit 06010452
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-10-25 Cont ID  
Sent By jwitmer Date 2006-10-25 Time 14:17 Rev Time 2.22
Received By jwitmer Date 2006-10-25 Time 14:17 Sent To  
Notes
2006-10-25 14:19:21BUILDING PROVISO:
 OVERHEAD GARAGE DOORS WILL REQUIRE A SEPERATE PERMIT.
 SPRAY BOOTH WILL REQUIRE A SEPERATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-08-23 Cont ID  
Sent By jwitmer Date 2006-08-23 Time 07:18 Rev Time 6.66
Received By jwitmer Date 2006-08-22 Time 13:38 Sent To  
Notes
2006-08-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06010452/ 06030925
  
 ADD:422 SUNSET/ 433 AVON RD
 CONT: BURKHARDT CONSTRUCTION
 TEL: (561)659-1400
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 601
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 2A)THE UNITY OF TITLE SUBMITTED IS NOT
 FOR THE LOTS BACK TO BACK, PHASE I AND
 PHASE II BUT FOR THE LOTS THAT ARE ON
 BOTH SIDES OF SUNSET. THIS IS A MATTER
 THAT ZONING, UTILITIES NOR THE LAW
 DEPARTMENT HAS APPROVED. THIS ISSUE HAS
 TO BE RESOLVED BEFORE A PERMIT WILL BE
 ISSUED.
 2B)ALSO SHEET A-1 PHASE-I REMOVE THE
 FENCE FROM ACROSS THE RITE OF WAY BEFORE
 A PERMIT WILL BE ISSUED.
 2C)PROVIDE A UNITY OF TITLE THAT HAS
 BEEN APPROVED FOR LOTS 116 AND 142
 COMBINING THESE LOTS INTO A SINGLE LOT.
  
 3) CONFLICT OR DISCREPANCY IN PLANS AND
 THE ARHITECTS RESPONSE. SHEET A-1
 PHASE-II ITEM# 17 INDICATES THAT THIS IS
 A NEW OVERHEAD FIRE RATED DOOR, WHEREAS
 COMMENT# 8 RESPONSE (06030925) INDICATES
 THIS IS AN EXISTING 3HR FIRE RATED
 DOORWAY. WHICH IS IT, SINCE THIS CROSSES
 PROPERTY LINES NO PERMIT WAS PULLED
 PROVIDE LITERATURE ON THE FIRE RATING
 SINCE WE STILL NEED A 2 HR SEPERATION
 FROM THE PAINT SHOP. TABLE 302.1.1.
  
 4) SHEET A-1 PHASE-II INDICATES A NEW
 HANDICAPPED RAMP AS A RESULT OF A
 MEETING BETWEEN THE OWNER, DESIGN TEAM,
 CONTRACTOR AND BUILDING DEPARTMENT.
 11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE. LOWER LANDING IS NOT
 INDICATED ON PLAN. WILL REQUIRE THE
 ELIMINATION OF ANOTHER PARKING SPOT.
  
 5) THE ARCHITECT HAS SUBMITTED A LETTER
 ON DISPROPORTIONATE COST BUT THIS LETTER
 STILL DOES NOT RELIEVE THE OWNER FROM
 VERTICAL ACCESSIBLIITY.
 11-4.1.6(1)(F) NOTHING IN THIS SECTION
 SHALL BE CONSTRUED TO RELIEVE THE OWNER
 OF ANY BUILDING, STRUCTURE OR FACILITY
 FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND
 BELOW OCCUPIABLE GRADE LEVEL, REGARDLESS
 OF WHETHER THE CODE REQUIRES AN ELEVATOR
 TO BE INSTALLED IN SUCH BUILDING,
 STRUCTURE.
 THE DESIGN TEAM HAS CREATED A RAMP
 TO ENTER THE WAREHOUSE PORTION BUT NO
 VERTICAL ACCESSIBLITY TO THE OFFICES.
  
 6A) A-1, PHASE I INDICATES ROOF TOP AIR
 HANDLERS, THE CURB IS TO BE TIED TO THE
 ROOF DECK BY 3"X3" ANGLES NO MENTION AS
 TO HOW THE ANGLES ARE FASTENED TO THE
 ALUMINIUM FRAME.2004 FBC BUILD 1503.1
  
 6B) THESE SAME 3"X3" ANGLES ARE TO BE
 BOLTED TO THE ROOF WHAT TYPE OF WEATHER
 PROOFING IS TO OCCUR AROUND THE BOLTS?
 2004 FBC BUILD 1503.1
  
 6C) M-1.2 PHASE I PLANS INDICATE THE
 HURRICANE SUPPORT DETAIL WITH A 5/8"
 EYEBOLT THROUGHT THE ROOF DECK BUT NO
 MENTION AS TO HOW TO MAKE THE CONNECTION
  
 WEATHER TIGHT? 2004 FBC BUILD 1503.1
  
 7) ONLY ONE COPY OF LISTED ITEMS BELOW
 REQUIRES (2) SUBMITTALS:
 7A) MSDS SHEETS
 7B) CARBON MONOXIDE MONITORING SYSTEM.
  
 8) WORK TO BE COMPLETED UNDER SEPERATE
 PERMIT:
 A) EXTERIOR MOTORIZED OVERHEAD DOORS
 B) PAINT BOOTH, MIXING ROOM & SUPRESSION
 SYSTEM.
 C) GENERATOR, PAD & LANDSCAPE WALL
 D) FUEL TANKS
 E) FENCING ACROSS SUNSET WITH CITY
 APPROVAL.
 F) KLAUS CAR STORAGE RACKS
  
 BUILDING PROVISOS:
 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSELY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-07-12 Cont ID  
Sent By mjacobs Date 2006-07-12 Time 07:07 Rev Time 0.00
Received By mjacobs Date 2006-06-12 Time 14:33 Sent To ENG
Notes
2006-06-12 00:00:00 
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ALL VOIDED PAGES. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPITION OF THE
 REVISION MADE, IDENTIFYING THE SHEETS OR
 SPECIFIC PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOU PERMIT.
 THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) WPB.AMEND. 106.1.3 THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY STANDARDS FOR PLANS
 AND SPECIFICATIONS,IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. "HAND WRITTEN INFORMATION IS
 NOT ACCEPTABLE ON ENGINEERED DRAWINGS".
 THE DRAWINGS AND INFORMATION BY THOMAS
 J.TWOMEY,P.E. WERE ALTERED. THIS IS NOT
 ACCEPTABLE.THE DRAWINGS SHALL BE
 ORIGINALLY SIGNED AND SEALED BY THE
 ENGINEER OF RECORD. SEE 61G15-23.001/
 61G15-23.002 FOR MORE INFORMATION.
  
 3) 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING. THE OWNER MUST SIGN
 THE NOC. PER FS.713.13(1)(G).
  
 4) WPB ADMIN CODE 106.3*3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. THE STATE
 COVER SHEETS ARE REQUIRED FOR THOSE
 PRODUCTS WHICH ARE APPROVED BY THE
 STATE. NOTE: THE PRODUCT APPROVAL FOR
 THE PGT FIXED WINDOW HAS BEEN REVISED
 AND UPDATED. SUBMIT THE UPDATED PRODUCT
 APPROVAL FOR THIS PRODUCT. SEE
 WWW.FLORIDABUILDING.ORG. #FL243-R3 FOR
 MORE INFORMATION.
  
 5)FBC 704.8 ALLOWABLE AREA OF OPENINGS.
 THE MAXIMUM AREA OF UNPROTECTED OR
 PROTECTED OPENINGS PERMITTED IN AN
 EXTERIOR WALL IN ANY STORY SHALL NOT
 EXCEED THE VALUES SET FORTH IN TABLE
 704.8 . WHERE BOTH UNPROTECTED AND
 PROTECTED OPENINGS ARE LOCATED IN THE
 EXTERIOR WALL IN ANY STORY, THE TOTAL
 AREA OF THE OPENINGS SHALL COMPLY WITH
 THE FOLLOWING FORMULA: SEE (FBC TABLE
 602) FOR ADDITIONAL INFORMATION. IF THE
 WINDOWSWILL BE REMOVE THEY WILL HAVE
 TO MEET THE REQUIREMENTS OF THESE TWO
 SECTIONS OF THE CURRENT FBC.
  
 6) ARE THERE TWO BUILDINGS OR ONE AT
 THIS ADDRESS? IF IT'S TWO BUILDINGS
 SUBMIT THE UNITY OF TITLE COMBINING THE
 TWO STRUCTURES.
  
 7) SHOW THE CORRECT SQUARE FOOTAGE OF
 THIS BUILDING. THE DRAWINGS INDICATE THE
 SQUARE FOOTAGE AS 22,922 HOWEVER, THE
 DIMENTIONS OF THIS BUILDING DOES NOT
 NATCH THAT FIGURE.
  
 8) SHEET D-1 SHOWS A FENCE WITH A GATE
 IN THE MIDDLE OF SUNSET ROAD. IF THE
 OWNER HAS PERMISSION FOR THE
 INSTALLATION OF THES FENCE PROVIDE THE
 INFORMATION FROM THE ENGINEERING DEPT.
 WHICH ALLOW THIS FENCE TO BE
 CONSTRUCTED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
 .
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-07 Cont ID  
Sent By mjacobs Date 2006-04-07 Time 11:20 Rev Time 0.00
Received By mjacobs Date 2006-04-06 Time 13:55 Sent To  
Notes
2006-04-06 00:00:001) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) IF GLASS BLOCK WON'T BE USED IN THE
 BUILDING,REMOVE THE NOTE #12 ON SHEET
 A-1. ALSO IF THERE IS ANY OTHER
 INFORMATION WHICH DOES NOT AFFECT THIS
 PROJECT PLEASE HAVE IT REMOVED FORM THE
 DRAWINGS AND NOTES.
  
 3) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. THE STATE COVER
 SHEET IS REQUIRED FOR THOSE PRODUCTS
 WHICH ARE APPROVED BY THE STATE. THE
 ONES SUBMITTED DON'T HAVE THE COVER
 SHEETS.
  
 3) NOTE: NOA #02-0702.04 FOR THE SINGLE
 HUNG WINDOW HAS EXPIRED.
  
 4) THE SEALS ON SHEETS D-1 AND A-1 ARE
 ILLEGIBLE. ALL INFORMATION ON
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. SEE FBC.106.1.1
  
 5) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE DESIGN OCCUPANT LOAD, SEE 1004.
 D) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 E) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-31 Cont ID  
Sent By mjacobs Date 2006-01-31 Time 10:14 Rev Time 0.00
Received By jwitmer Date 2006-08-22 Time 13:38 Sent To PC
Notes
2006-01-30 00:00:001) PRODUCT APPROVALS ARE REQUIRED FOR
 ALL EXTERIOR WINDOWS AND DOORS, ALSO
 THE GLASS BLOCK.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2)SHOWW A DETAIL DRAWWING WHERE THE
 STUCCO WILL BE FINISH OVER THE 1" FOAM.
 SHOW HOW THE FOAM IS ATTATCHED AND WHAT
 IT IS ATTATCHED TO. ALSO WHERE IS
 EXHAUST FAN IS REMOVED, SHOW THE FRAMING
 DETAIL OF HOW THE HOLE WILL BE SEALED.
  
 3) ARE ALL THE WINDOWS FIXED WINDOWS?
 SUBMIT A WINDOW/DOOR SCHEDULE SHOWING
 THE SIZE AND TYPWOF EACH DOOR AND
 WINDOW.
  
 4) IF ANY ROOFING WORK IS REQUIRED,
 SUBMIT THE PRODUCT APPROVALS FOR THE
 ROOFING PRODUCT WHICH WILL BE USED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEK:(561)805-6726
  
  
  
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2007-02-04 Cont ID  
Sent By dpalmer Date 2007-02-04 Time 10:40 Rev Time 0.00
Received By dpalmer Date 2007-02-04 Time 10:02 Sent To  
Notes
2007-02-04 10:40:47** VALUE WAS INCREASED TO $525K,. $411K WAS INCREASED
 ON THIS PERMIT AND $114K WAS ALREADY ON 06030925.
  
  
  
 REDLINED, ALL EXISTING OFFICE AREAS IS BEING BROUGHT UP
 TO THE 2004 FBC CHAPTER 13 FOR LIGHTING AND CONTROLS.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2006-12-08 Cont ID  
Sent By dpalmer Date 2006-12-08 Time 19:06 Rev Time 0.00
Received By dpalmer Date 2006-12-08 Time 18:11 Sent To  
Notes
2006-12-08 19:08:10***UNSAT ***
  
  
 1) NOTE:PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE
 OF WORK ON THIS PROJECT NEEDS TO BE UPDATED. PLEASE
 KNOW EVEN WITH THE PREVIOUS APPLIED VALUE UNDER 433
 AVON WHICH WAS $114K AND THE VALUE ON THIS PERMIT AT
 $85K, THE VALUE FOR ALL WORK IN ACTUAL SCOPE IS
 EXTREMELY LOW. PLEASE KNOW THE ELECTRICAL ALONE IN THIS
 BUILDING IS HIGHER THAN THE APPLIED VALUE FOR THIS
 PERMIT. PLEASE KNOW THE VALUE SHALL INCLUDE ALL LABOR
 AND MATERIALS.
 PLEASE KNOW IF A VALUE IS NOT ADJUSTED FOR ALL WORK AND
 MATERIALS AS SHOWN, ONE WILL BE APPLIED BASED ON THE
 TABLES FROM THE FBC OR MARSHALL'S AND SWIFT GUIDE.
 FBC 108.3
  
 2) NOTE: PLEASE SEE PANEL P5 IS BEING SHOWN AT 600A'S
 WITH A 225A FEED. PLEASE VERIFY.
 FBC 106.1.2
  
 3) NOTE: PLEASE KNOW AS THE SCOPE INVOLVED EXCEEDS THAT
 OF 30%, PLEASE SEE FBC CHAPTER 13 WILL APPLY TO THE
 EXISTING OFFICES. THIS WAS GONE OVER IN PREVIOUS
 MEETINGS WITH THE ENGINEER AND DESIGN TEAM AND THIS
 INFORMATION WAS TO BE UPDATED AND APPLIED TO PLANS.
 PLEASE SEE LIGHTING CONTROLS, LIGHTING DENSITIES, ETC.
 PLEASE SEE OTHER ROOM(S) ON PLANS WHICH DO NOT SEEM TO
 INDICATE A SEPARATE SPACE CONTROL.
 PLEASE SEE NEW OUTSIDE LIGHTS REQUIRED TO BE PART OF
 THE EXTERIOR LIGHTING POWER ALLOWANCES.
 FBC 13-415.1.ABC.1.1, .1.2 AND .1.3
 13-415.2.
  
 4) NOTE: PLEASE VERIFY SUB SECTIONS FOR PANELS, 4, AND
 2 NOT ON RISER.
  
 5) NOTE: PLEASE PROVIDE A COMPLETE LOAD SUMMARY FOR THE
 GENERATOR AS WELL AS THE LOADS ON EACH OF THE EDP AND
 THE EDPA.
 220, 702.5
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-10-22 Cont ID  
Sent By dpalmer Date 2006-10-22 Time 08:41 Rev Time 0.00
Received By dpalmer Date 2006-10-21 Time 18:44 Sent To  
Notes
2006-10-22 08:41:07****** NOTESREDLINED *********
  
  
  
 1) PLEASE SEE AS ONLY TWO SETS OF SPEC BOOKS WERE
 SUBMITTED AND THREE SETS OF PLANS WERE SUBMITTED, THE
 THIRD SET OF MANUFACTURES SPECS/CUT SHEETS FOR EACH OF
 THE ATS'S WERE ATTACHED TO THE SET 3OF 3. ON RISER
 SHEET.
 THE OTHER TWO SETS WERE PLACED IN SPEC BOOKS .
  
 2) PLEASE SEE PLANS CALL FOR SPRAY BOOTH TO BE UNDER
 SEPARATE PERMIT(S) AND ARE NOT INCLUDED IN EITHER PHASE
 ONE OR PHASE TWO ON PLANS. PLEASE KNOW THAT THE
 MANUFACTURES SPEC WERE REMOVED FROM THE TWO SPEC BOOKS
 SUBMITTED AND PLACED WITH THE OTHER THREE SETS OF SPECS
 SUBMITTED SEPARATELY (LOOSE).
 THESE ARE LABELEDNIC AND WILL BE RETURNED TO
 CONTRACTOR FOR FUTURE USE.
  
 3) NOTE: PLEASE SEE PHASE I RISERCALLS FOR SPACE FOR
 "FUTURE" METER, THIS IS REDLINED AS NO 2ND METER IS
 PERMITTED UNLESS PROPER REQUIRED TENANT SEPARATION IS
 CONSTRUCTED.
  
 4) PLEASE BE AWAREBOTH PERMITS FOR GEN-ELEC AND FUEL
 PERMITS 06061596(ELEC) AND 06061597(FUEL) HAVE HAD
 ADDRESSES CHANGED TO CORRELATE WITH THE ADDRESS OF 422
 SUNSET AND GEN-COM PERMIT NUMBER 06061595.
  
  
 ELECTRICAL PLANS STAMPED ALONG WITH SPECS FOR ATS'S.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-10-22 08:01:50REVIEW IN PROGRESS
2006-10-21 18:44:46ELEC REVIEW IN PROGRESS

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-08-10 Cont ID  
Sent By dpalmer Date 2006-08-10 Time 21:13 Rev Time 0.00
Received By dpalmer Date 2006-08-10 Time 20:42 Sent To  
Notes
2006-08-10 00:00:00*** UNSAT ***
  
 ** PLEASE SEE COMMENTS BELOW, SOME ARE
 EXISTING AND SOME ARE NEW BASED ON PLANS
 SUBMITTED.
  
 1) NOTE: PLEASE SEE PHASE 1, SHOWS METER
 FUTURE AND YET AND METER CAN IS BEING
 INSTALLED. PLEASE SEE PHASE II WHICH
 SHOWS THE METER BEING INSTALLED AS
 EXISTING.
 PLEASE KNOW WITHOUT TENANT SEPARATION
 THIS METERCAN IS NOT PERMITTED. SEC'S
 FROM GUTTER SHALL GO DIRECTLY INTO THE
 MAIN2 OF 2.
 THIS IS A SINGLE OCCUPANCY , ANY FUTURE
 METER CAN WILL BE DONE AT THE TIME OF
 SUCH SEPARATION OF TENANTS TAKES PLACE.
 THIS WAS THE UDNERSTANDING OF THE LAST
 MEETING BY THE DESIGN TEAM.
 PLEASE ALSO SEE PHASE ONE FOR RISER
 SHOWS CONDUIT AND FEEDERS TO NOTHING
 AFTER THE MAIN DISCONNECT.
  
 2) NOTE: PLEASE SEE PLANS INDICATE A
 PHASE 1 FOR E-1.1, YET TITLE BLOCK CALLS
 FOR PHASE II. PLEASE SEE THIS SHEET DOES
 NOT CORRELATE WITH PHASING OF THE
 PROJECT.
 PLEASE SEE SPRAY BOOTH IS BEING SHOWN AS
 FUTURE ON PHASE TWO SHEETS, YET SHOWS AS
 BEING INSTALLED ON OTHER SHEETS AND ON
 PAHSE TWO PANEL SCHEDULES.
 PLEASE KNOW ALL INFORMATION AS REQUESTED
 FOR LOCATIONS ETC WAS NOT SHOWN FOR
 SPRAY BOOTH.
 PLEASE SEE NOTE FROM PREVIOUS REVIEW
 BELOW;
 "PLEASE SEE NEC 511 AND 516. ALL AREAS
 AND CLASS LOCATION SHALL BE INDICATED
 AND LAYED OUT PER NEC 500, 500.5, 501,
 CLASS 1 DIV 1, CLASS 1 DIV 2?
 NFPA-88B, 1997
 PLEASE SEE THIS SHOWN WITH A "WAREHOUSE"
 OCCUPANCY WHICH DOES NOT SEEM TO
 CORRELATE WITH NEW REVISED PLANS AND
 PROPOSED WORK.
  
 3) NOTE: PLEASE SEE SEAL BY THE ENGINEER
 IS NOT CLEAR AND VISABLE WITH ALL
 INFORMATION ON SAID SEAL. THIS OFFICE
 HAS ATTEMPTED TO SHADE THESE SHEETS TO
 SHOW ALL INFORMATION, HOWEVER THIS HAS
 NOT BEEN AFFECTIVE.
 PLEASE SEE FAC 61G15-23.001
 "RAISED SEAL MUST BE CLEAR AND VISABLE"
  
 4) NOTE: MISSING DISCONNECT'S FOR CU'S.
 440.11
  
 5) NOTE: PLEASE SEE MISSING GFI FOR CU'S
 210.63, 210.8.
  
 6) NOTE: PLEASE SEE WIRE AND CONDUIT
 SCHEDULE AS #2 SHOWS AN "EQUIPMENT
 GROUNDING CONDUCTOR" BEFORE THE FIRST
 MEANS OF DISCONNECT. PLEASE SEE 250.6,
 250.24 B AS THE "EQUIPMENT GROUNDING
 CONDUCTOR" IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
 PLEASE SEE SEC'S TO MAIN 1 OF 1.
  
  
  
  
  
  
 6) NOTE: ** IMPORTANT" AS REQUESTED BY
 THE BUIDLING REVIEWER ON PREVIOUS NOTES:
 ONCE ALL REVIEWS ARE COMPLETE, BEFORE
 RESUBMITTING PLANS, PLEASE COMPLETELY
 REMOVE ALL OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. ONE COPY
 OF THE OLD/VOIDED REMOVED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP TO ALLEAVIATE ANY DELAYS
 INTHE PROCESS.
  
 ** PLEASE KNOW, ONE SET OF EACH OF THE
 PREVIOUS SUBMITTED ELECTRICAL PLANS
 ALONG WITH THE NEW REVISED ELECTRICAL
 PLANS ARE BEING RETAINED BY THIS OFFICE
 AS EACH SET CONTAINS COMPLETELY
 DIFFERENT INFORMATION FOR USE/OCCUPANCY
 ETC.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELETRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, OR COMMENTS
 PLEASE CALL.
 A CALLED WAS PLACED TO THE ELECTRICAL
 ENGINEER'S OFFICE AND A MESSAGE WAS LEFT
 AS OF THIS REVIEW TO GO OVER PLANS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-07-07 Cont ID  
Sent By dpalmer Date 2006-07-07 Time 21:06 Rev Time 0.00
Received By dpalmer Date 2006-07-07 Time 19:20 Sent To B
Notes
2006-07-07 00:00:00********* UNSAT 4TH REVIEW ************
  
 PLEASE SEE NOTES BELOW AS MANY ARE NEW
 DUE TO COMPLETELY NEW RISERAND MANY
 CHANGES ON PLANS.
 PLEASE SEE OTHER NOTES PER THIS REVIEW.
 * REPRESENTS FBC ADMINISTRATIVE SECTION
 106.1.2 AS ADOPTED BY THE CITY OF WEST
 PALM BEACH
  
 1) NOTE: IMPORTANT, ONCE ALL REVIEW(S)
 ARE DONE AND BEFORE PLANS ARE
 RESUBMITTED, PLEASE COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT THE NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE ALSO REMOVE ALL STAPLED PRODUCT
 APPROVALS WHICH ARE NOW ATTACHED TO
 PLANS. THESE SHOULD BE IN TWO SETS
 SEPARATELY FROM PLANS AND NOT ATTACHED.
 THIS COMMENT IS FOR OTHER TRADE(S)
 SHEETS WHICH WERE LEFT IN SETS.
 PLEASE ONLY SUBMIT ONE COPY OF THE
 OLD/VOIDED REMOVED SHEETS FOR REFERENCE.
  
 2) NOTE: PLEASE BE SURE PLANS REFLECT
 THE CURRENT CODES IN EFFECT. PLEASE SEE
 ELECTRICAL PLANS REFLECT THE 2001 FBC.
 PLEASE ADJUST AND REFERENC THE FOLLOWING
 WHICH ARE CURRENTLY UNDER.
 2002 NFPA-70 (DONE), 2002 NFPA-72, 2003
 NFPA-101, 2004 FBC.
  
 3) NOTE: PLEASE SEE NOTES BELOW WITH
 RESPECT TO SERVICE(S) BEING PROPOSED.
 PLEASE KNOW, IN THE MEAN TIME ANY ATS
 BEING INSTALLED IN ANY SERVICE REQUIRES
 THE MANUFACTURES SPECS/CUT SHEETS TO BE
 SUBMITTED. PLEASE BE SURE THESE SHEETS
 INDICATE A LISTING BY ANRTL.
 106.1.2 FBC ADMIN SECT, 110.3
  
 4) NOTE: PLEASE CORRELATE PLANS WITH
 RISER DIAGRAM. PLEASE SEE SOME SERVICE
 EQUIPMENT WHICH IS BEING SHOWN ON RISER,
 HOWEVER THESE ARE NOT ON PLANS, POWER OR
 LIGHTING SHEETS? (EDP ETC.)
 106.1.2*
  
 5) NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PLANS WITH SUBMITTED PANEL SCHEDULES.
 PLEASE SEE MANY ITEMS ARE BEING SHOWN
 CIRCUITED TO THE PREVIOUS PANEL
 SCHEDULES.
 PLEASE SEE PANEL SCHEDULES WHICH SHOW
 SPARE, YET CIRCUITS ARE ON PLANS.
 PLEASE SEE A/C RTU'S BEING SHOWN TO MDP,
 HOWEVER MDP DO NOT SHOW THESE ANYMORE.
 PLEASE SEE ME LTS ETC.
 106.1.2*
  
 6) NOTE: PLEASE KNOW, EM LIGHTING SHALL
 BE CIRCUITED PER 700.12E.
 PLEASE KNOW, AS THE CIRCUIT FOR THE EM
 LTS IS NOW SHOWN AS A BLANK ON PANEL
 SCHEDULE. PLEASE KNOW UNLESS THE
 GENERATOR WAS PERMITTED UNDER THIS
 PERMIT WHICH IT IS NOT, EM LTSWILL BE
 REQUIRED WITH BATTERY BACK UP AT A MIN
 AT THIS TIME AND UNDER THIS PERMIT.
 PLEASE SEE 700.12E, 700.16, LS 101 7.8,
 7.9.
  
 7) NOTE: PLEASE SEE"EDP"IS BEING
 SHOWN AS 800A MLO AND WITH A LOAD OF
 300+ A'S YET, THE OCP DEVICE SHOWN ON
 MDP IS ONLY SHOWN AS 125A'S? PLEASE SEE
 THIS EXCEEDS THE RATING OF THE
 OVERCURRENT DEVICE.
 240.4,310.16,240, ETC.
  
 8) NOTE: PLEASE SEE MDP IS NOTED AND
 CIRCUITS ON MDP ETC ARE NOTED WITH A #1
 IN A CIRCLE WHICH MENTIONS TO SEE RISER
 FOR FEEDERS, CONDUITS ETC. PLEASE SEE
 RISER DOES NOT INDICATE ANY FEEDERS ETC
 FROM MDP TO ATS AND FROM ATS TO EDP.
 PLEASE REVISE AND ADJUST.
 240.4,310.16, 215.5 ETC
  
 9) NOTE: PLEASE KNOW, A DISCONNECTING
 MEANS WILL BE REQUIRED GROUPED FOR
 FEEDERS COMING FROM FUTURE GENERATOR.
 THIS MAY BE SOMETHING PLACED INTO THE
 DESIGN AT THIS TIME OR AT A LATER DATE.
 PLEASE ALSO SEE NOTES FOR SERVICE.
 225.31-225.39, 110.27
  
 10) NOTE: PLEASE INCLUDE SECT #2 OF P1
 ON RISER DIAGRAM.
 PLEASE ALSO INDICATE IF THE PANEL "P1"
 CONTAINS OCP FEEDING SECT #2 OR DOES
 "P1" CONTAIN "FEED-THRU"LUGS.
 PLEASE SHOW.
 106.1.2*
  
 11) NOTE: PLEASE SEE ENERGY CALCULATIONS
 DO NOT REFLECT LIGHTING INSTALLED AND
 LIGHTING ALLOWANCE IN CALCS. IT IS NOTED
 ON PLANS AND LETTER FROM ENGINEER THAT
 THE "LPD" ARE UNDER MAX LIMITS, YET THE
 TOTAL WATTAGE ETC SHOULD BE IN
 CALCULATIONS.
 FBC 13-415.1.AB.1,13-415.2.ABC.1
  
 12) NOTE: PLEASE CLARIFY NEWOR
 EXISTING ROOF TOP GFI(S) FOR A/C
 EQUIPMENT.
 210.63,210.8
  
 13) NOTE: PLEASE CLARIFY THE NUMBER OF
 AHU'S IN THIS SPACE, AS "M" SHEET
 MENITONS AHU'S #1, #2, #3 AND #4??
 ??
  
 14) NOTE: PLEASE SEE NOTICE OF
 COMMENCMENT ATTACHED TO PACKAGE HAS
 EXPIRED PER FS 713.13(2).
 THIS WILL BE REQUIRED OT BE RE-RECORDED
 AND SUBMITTED BEFORE PICKING UP PERMIT.
  
 PLEASE SEE THE FOLLOWING AS COMMENTED
 WITH RESPECT TO THE SERVICE.
  
 ** CALLED ENGINEER ON 7/7/06 AT 4:45 PM
 AND LEFT MESSAGE TO CONTACT ME WITH
 RESPECT TO THE SERVICE, SEPARATION ETC.
  
 AS PER CONSULTATION WITH MR. ROBERT AND
 OTHERS. THE FOLLOWING TWO OPTIONS MAY BE
 DONE.
  
 1) IF OPENING BETWEEN THIS SPACE AND THE
 ADJOINING FUTURE SPACE IS GOING TO
 REMAIN, EVEN WITH THE RATED OVER-HEAD
 DOOR, THEN THE ELECTRICAL SERVICE WILL
 HAVE TO BE REVISED TO INCLUDE ONLY ONE
 SERVICE RISER, ONE METER.
  
 2)IF THE WALL IS CLOSED UP TO PROVIDE
 THE PROPER TENANT SEPARATION AS REQUIRED
 FOR OCCUPANCY TYPES, THEN ONE SERVICE
 WITH TWO METERS AND TWO MAINS WOULD BE
 PERMITTED.
  
 PLEASE KNOW ANY EMERGENCY BACK UP SYSTEM
 MAY STILL BE INSTALLED AFTER EACH MAIN
 ETC.
  
 ** THIS IS CONSIDERED ONE "BUILDING"
 UNDER THE DEFINITIONS OF THE FBC.
 ONLY IF SEPARATED BY A "FIRE WALL" WOULD
 THESE BE CONSIDERED TWO SEPARATE
 BUILDINGS. PLEASE SEE "FIRE WALL" UNDER
 DEFINITIONS.
 IF CONSTRUCTION OF CLOSING IN THE WALL ,
 AND CONTRUCTION OF THE EXISTING WALL,
 CEILING ETC BETWEEN THE TWO MEET THE
 "FIRE WALL" REQUIRMENTS, THEN TWO
 SEPARATE SERVICES WILL BE PERMITTED WITH
 TWO SEPARATE OPT STAND-BY GENERATOR
 SYSTEMS.
  
 ** PLEASE KNOW, A MEETING SHOULD BE HELD
 TO GO COMMENTS, DESIGN ETC BEFORE
 RESUBMITTING PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
 PLANS WERE ROUTED TO MR ROBERT BROWN
 AFTER THE ELECTRICAL REVIEW.
2006-07-02 00:00:00SEE DEWEY PALMER WHEN PLANS COME BACK
 IN.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-06-16 Cont ID  
Sent By jleahy Date 2006-06-16 Time 09:26 Rev Time 1.30
Received By jleahy Date 2006-06-16 Time 07:36 Sent To  
Notes
2006-06-16 00:00:00ON THE LAST PLAN REVIEW CHAPTER 13 OF
 THE FBC WAS REFERENCED BY THIS OFFICE.
  
 NO COMPLIANCE WITH THIS SECTION IS
 SHOWN.
  
 PLEASE SEE THE FOLLOWING SECTIONS:
  
 13-415.1.ABC.1.1 AUTOMATIC LIGHTING
 SHUTOFF
  
 13-415.1.ABC.1.2 SPACE CONTROL
  
 13-415.1.ABC.1.3 ADDITIONAL CONTROLS
  
 13-415.1.ABC.3TANDEM WIRING
  
 13-415.1.ABC.1CALCULATION
  
 13-415.1.CMETHOD C
  
 13-415.2.ABC.1PERFORMANCE CALCULATION
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-03 Cont ID  
Sent By jleahy Date 2006-04-03 Time 15:57 Rev Time 1.00
Received By jleahy Date 2006-04-03 Time 15:57 Sent To  
Notes
2006-04-03 00:00:00NEED TO EXPLAIN WHAT TYPE OF BUSINESS IS
 GOING TO RUN OUT OF THIS BAY?
  
 FROM THE DRAWINGS IT LOOKS LIKE
 AUTOMOTIVE REPAIR!!IF SO PLEASE
 APPLY THE REQUIREMENTS FROM ARTICLE 511
 FROM THE NEC.
  
 BUILDING TO MEET THE REQUIREMENTS OF
 CHAPTER 13 OF THE FL BLDG. CODE FOR
 LIGHTING ,A/C AND EQUIPMENT.
  
 MAINS TO BE GROUPED PLEASE SHOW LOCATION
 230.72
  
 FOUR OF THE LIGHTING FIXTURE ARE THROUGH
 A WALL ??? SEE PAGE E1.1
  
 NEED LOAD CALCULATIONS PER THE NEC
 215.5, 220.
  
 NOTE 20 NEEDS TO BE CHANGED.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-01-20 Cont ID  
Sent By jleahy Date 2006-01-20 Time 07:25 Rev Time 0.30
Received By jleahy Date 2006-01-20 Time 07:25 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2006-09-21 Cont ID  
Sent By rchokshi Date 2006-09-21 Time 14:04 Rev Time 0.00
Received By rchokshi Date 2006-09-21 Time 11:49 Sent To  
Notes
2006-09-21 00:00:00EVERYTHING IS O.K. PASSED
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-07-13 Cont ID  
Sent By rchokshi Date 2006-07-13 Time 13:44 Rev Time 0.00
Received By rchokshi Date 2006-07-13 Time 13:19 Sent To PC
Notes
2006-07-13 00:00:00FAILED
 1. SHEET D-1 SHOWS DOOR ON PUBLIC STREET
 SUNSET ROAD, DOOR ON PUBLIC STREET MAY
 NOT BE ALLOWED BY CITY.
 2. NEED TO SHOW WATER/SEWER LINES ON
 PLAN/ELEVATION,DETAIL ETC.
 3. PLEASE SHOW SIDE WALK, HANDYCAP
 ACCESS RAMP, ETC
 4. NEED FLOOR ELEVATION,FLOODING
 REQUIREMENT,SFWMD APPROVAL
 5.PLAN NEED TO BE APPROVED FROM UTILITY
  
 PLEASE CALL IF YOU NEED HELP, RASIK
 CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2007-02-23 Cont ID  
Sent By mawillia Date 2007-02-23 Time 19:53 Rev Time 0.00
Received By mawillia Date 2007-02-23 Time 19:53 Sent To  
Notes
2007-02-23 20:01:05*****APPROVED*****
  
  
 REVISION #6 DATED 12/27/06;SHEET E-1.1 WAS STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2007-01-08 Cont ID  
Sent By mawillia Date 2007-01-08 Time 14:10 Rev Time 0.00
Received By mawillia Date 2007-01-08 Time 14:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2006-11-01 Cont ID  
Sent By mwennerg Date 2006-11-01 Time 14:48 Rev Time 0.00
Received By mwennerg Date 2006-11-01 Time 14:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-09-01 Cont ID  
Sent By mwennerg Date 2006-09-01 Time 11:16 Rev Time 0.00
Received By mwennerg Date 2006-09-01 Time 11:16 Sent To  
Notes
2006-09-01 00:00:00***PROVISO***
  
 1) NEW SHEETS DON'T APPEAR TO SHOW FIRE
 EXTINGUISHERS. PLEASE SHOW THE LOCATIONS
 WHEN RESUBMITTING THE PLANS FOR OTHER
 COMMENTS.
  
 2) SINCE THIS WORK WILL BE IN PHASES,
 ALL EXIT DOORS THAT SERVE AS SUCH SHALL
 HAVE ILLUMINATED EXIT SIGNS IN PLACE.
 THIS IS NOT CLEARLY SHOWN ON PLANS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-06-22 Cont ID  
Sent By mwennerg Date 2006-06-22 Time 13:34 Rev Time 0.00
Received By mwennerg Date 2006-06-22 Time 13:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-04-11 Cont ID  
Sent By mwennerg Date 2006-04-11 Time 11:14 Rev Time 0.00
Received By mwennerg Date 2006-04-11 Time 11:14 Sent To  
Notes
2006-04-11 00:00:00******DENIED******
  
 1) PLEASE INDICATE OCCUPANCY TYPE ON THE
 PLANS. WILL THERE BE PAINT SPRAYING OF
 VEHICLES?
  
 2) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION.
  
 3) PLEASE ILLUSTRATE REQUIRED ADDRESS ON
 BUILDING ELEVATIONS. MIMIMUM 6" ON
 CONTRASTING BACKGROUND.
  
 4) IS BUILDING PROTECTED BY AUTOMATIC
 FIRE SPRINKLER SYSTEM. SEPARATE SHOP
 DRAWINGS AND PERMIT REQUIRED FOR
 REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-01-24 Cont ID  
Sent By nmccray Date 2006-01-24 Time 10:53 Rev Time 0.00
Received By nmccray Date 2006-01-24 Time 10:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-03-03 Cont ID  
Sent By adarroug Date 2007-03-03 Time 17:40 Rev Time 0.00
Received By adarroug Date 2007-03-03 Time 17:40 Sent To P
Notes
2007-03-03 17:40:29TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-01-20 Cont ID  
Sent By adarroug Date 2007-01-20 Time 12:35 Rev Time 0.00
Received By adarroug Date 2007-01-20 Time 12:35 Sent To  
Notes
2007-01-31 15:56:35TO "COMM" BD#61
2007-01-20 12:36:14WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status   Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 19:57 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 19:57 Sent To E
Notes
2006-11-29 19:58:10SENT TO ELECTRICAL BOX

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-11-29 Cont ID  
Sent By spalmer Date 2006-11-29 Time 18:34 Rev Time 0.00
Received By spalmer Date 2006-11-29 Time 18:34 Sent To  
Notes
2006-12-08 15:20:04TO "COMM" BD#22
2006-11-29 18:34:52WAITING FOR "COMM" BOARD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-04 Cont ID  
Sent By adarroug Date 2006-10-04 Time 14:46 Rev Time 0.00
Received By adarroug Date 2006-10-04 Time 14:46 Sent To  
Notes
2006-10-17 13:50:04TO "COMM" BD#43
2006-10-04 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 13:51 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 13:51 Sent To  
Notes
2006-08-09 00:00:00TO "COMM" BD#53
2006-07-31 00:00:00WAITING FOR "COMM" BD--NEW MECH AND
 PLUMB SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-06 Cont ID  
Sent By adarroug Date 2006-07-06 Time 14:17 Rev Time 0.00
Received By adarroug Date 2006-07-06 Time 14:17 Sent To E
Notes
2006-07-06 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-23 Cont ID  
Sent By adarroug Date 2006-05-23 Time 14:09 Rev Time 0.00
Received By adarroug Date 2006-05-23 Time 14:09 Sent To  
Notes
2006-06-12 00:00:00TO "COMM" BD#49
2006-05-23 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-07 Cont ID  
Sent By adarroug Date 2006-03-07 Time 16:31 Rev Time 0.00
Received By adarroug Date 2006-03-07 Time 16:31 Sent To  
Notes
2006-04-03 00:00:00TO "COMM" BD#57
2006-03-07 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-01-31 Time   Rev Time 0.00
Received By adarroug Date 2006-01-17 Time 16:05 Sent To  
Notes
2006-01-17 00:00:00TO "COMM" BD#11

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-10-27 Cont ID  
Sent By pkrauss Date 2006-10-27 Time 15:07 Rev Time 0.00
Received By pkrauss Date 2006-10-27 Time 15:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-09-21 Cont ID  
Sent By pkrauss Date 2006-09-18 Time 13:13 Rev Time 0.00
Received By pkrauss Date 2006-09-18 Time 13:00 Sent To  
Notes
2006-09-18 00:00:00PROVISO:
 SUBMITTAL FOR THE TEXTILE DUCT &
 DIFFUSERS ARE NOT LISTED WITH UL.
 ANOTHER PRODUCT MAY HAVE TO BE SUBMITTED
 THAT MEET THE CLASS 0 (SURFACE BURNING
 CHARACTERISTICS OF ZERO) OR CLASS 1
 (FLAME SPREAD INDEX <25 AND SMOKE
 DEVELOPED INDEX <50).THIS ISSUE MUST
 BE RESOLVED PRIOR TO INSTALLATION OF ANY
 DUCT.
  
 NON-METALIC DUCT SHALL COMPLY WITH
 2004 FMC 603.4, DUCTS SHALL BE
 CONSTRUCTED WITH CLASS 0 OR CLASS 1 DUCT
 MATERIAL IN ACCORDANCE WITH UL 181.
  
 PLEASE NOTE, FABRIC DUCT SUBMITTED
 (PRIHODA) HAS NO UL LISTING. THE TEST
 REPORT PAGE 3 UNDER "LIMITATIONS" THERE
 IS A WARNING WHICH STATES THE FOLLOWING;
 "THIS DOCUMENT DOES NOT REPRESENT TYPE
 APPROVAL OR CERTIFICATION OF THE
 PRODUCT."
  
  
 ADDITIONAL PERMIT REQUIRED FOR THE SPRAY
 PAINT BOOTH.PLANS AND MANUFACTURER
 SUBMITTAL DATA ON FILE WITH BUILDING
 PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-14 Cont ID  
Sent By pkrauss Date 2006-06-14 Time 07:41 Rev Time 0.00
Received By pkrauss Date 2006-06-14 Time 07:11 Sent To  
Notes
2006-06-14 00:00:00PROVISO:
  
 NO WORK TO BE PERFORMED ON ANY VEHICLE.
 THIS IS FOR STORAGE ONLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-04-17 Cont ID  
Sent By pkrauss Date 2006-04-17 Time 07:34 Rev Time 0.00
Received By pkrauss Date 2006-04-17 Time 07:33 Sent To  
Notes
2006-04-17 00:00:00DENIED:
 MECHANICAL PLANS WERE NOT SUBMITTED WITH
 THE INITIAL REVIEW.
  
 1.PLEASE INDICATE WHAT TYPE OF
 BUSINESS THIS WILL BE.PLANS INDICATE
 CARS INSIDE BUSINESS.PLEASE PROVIDE
 CLARIFICATION, PARKING GARAGE, REAPIR
 GARAGE, BODY WORK OR PAINTING?
  
 2.PLEASE NOTE, EXHAUST SHALL TERMINATE
 AS NOT TO CREATE A NUISANCE & SHALL NOT
 BE DIRECTED ONTO WALKWAYS. EXHAUST &
 INTAKE OPENINGS SHALL BE LOCATED A
 MINIMUM 10 FEET FROM LOT LINES OR
 BUILDINGS ON THE SAME LOT.
  
 3.FRESH AIR INTAKE SHALL BE LOCATED A
 MINIMUM OF 10 FEET FROM ANY HZARDOUS OR
 NOXIOUS CONTAMINANT, SUCH AS PARKING
 LOTS, STREETS, ALLEYS OR LOADING DOCKS.
  
 4.PLAN SHEET M-1.1 EF-3 INDICATES
 REELS FROM THE CEILING JOIST.IS THIS A
 SYSTEM THAT IS DESIGNED TO CONNECT
 DIRECTLY TO THE EXHAUST MUFFLER OF THE
 VEHICLE?PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA.
  
 5.PLAN SHEET M-1.2 INDICATES THE CO
 SENSORS LOW LEVEL ALARM AT 35 PPM.PER
 2004 FMC 404.1, MECHANICAL VENTILATION
 IS NOT REQUIRED TO TO RUN CONTINUOUSLY
 WHERE THE SYSTEM IS ARRANGED TO OPERATE
 AUTOMATICALLY UPON DETECTION OF A
 CONCENTRATION OF CARBON MONOXIDE OF 25
 PPM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 8 Status P Date 2007-03-08 Cont ID  
Sent By jleech Date 2007-03-08 Time 07:42 Rev Time 0.00
Received By jleech Date 2007-03-08 Time 07:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 7 Status F Date 2007-02-21 Cont ID  
Sent By jleech Date 2007-02-21 Time 09:04 Rev Time 0.00
Received By jleech Date 2007-02-21 Time 09:04 Sent To  
Notes
2007-02-21 09:22:54DENIED;
 THE LAST APPROVED P-1 ON FILE WAS UP TO REVISION # 4
 9/26/06. THE NEWP-1 IS UP TO REVISION # 8. ONE SET OF
 PLANS HAS YELLOW HI-LITES AROUND ALL CHANGES NOT ON
 APPROVED PLANS. PLEASE SHOW CHANGES 5, 6, 7, AND 8 ON
 NEXT REVISION.
 1. THE SERVICE SINK VENT CAN BE THE WET VENT FOR THE
 FLOOR DRAINS. THE DRY VENT CAN BE REMOVED FROM THE
 SANITARY RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 6 Status F Date 2007-01-13 Cont ID  
Sent By kstevens Date 2007-01-13 Time 17:14 Rev Time 0.00
Received By kstevens Date 2007-01-13 Time 17:14 Sent To  
Notes
2007-01-13 17:30:42DENIED
 REFERENCE: CITY MUNICIPAL CODE
 UTILITY DEPT STANDARDS
  
 1. SHT P-1.1 900 GAL SAND/OIL INTERCEPTOR DETAIL.
 UTILITY STANDARDS INDICATE 3" WALLS AND 4" BOTTOM
 REQUIRED ON ALL INTERCEPTORS. (SEE ATTACHED SHEET).
 CITY CODE SECTION 90-124(7)(F) STATES "EACH INTERCEPTOR
 SHALL BE CONSTRUCTED OF STEEL REINFORCED CONCRETE.
 PLANS CALL FOR "FIBRILLATED POLYPROPLYLENE FIBER".
 DETAIL ALSO INDICATES 2.5" WALLS AND 3" BOTTOM. THIS
 DOES NOT MEET MUNICIPAL CODE OR UTILITY STANDARDS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-11-01 Cont ID  
Sent By jleech Date 2006-11-01 Time 09:37 Rev Time 0.00
Received By jleech Date 2006-11-01 Time 09:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-09-22 Cont ID  
Sent By jleech Date 2006-09-22 Time 08:04 Rev Time 0.00
Received By jleech Date 2006-09-22 Time 08:04 Sent To  
Notes
2006-09-22 00:00:00DENIED;
 1ADA DETAIL FOR PHASE 11 ON PAGE A-2
 ONLY SHOWS A DETAIL OF LAVATORY. DETAIL
 OF WHOLE BATHROOM IS REQUIRED, SHOW THE
 TOILET, SHOWER, AND LAVATORY IN DETAIL.
 REQUIREMENTS FOR COMPLIANCE CAN BE
 FOUND, FBC-2004 CHAPTER 11; TOILET SEC.
 11-4.16.1 THRU 11-4.16.6; LAVATORY
 11-4.19.1 THRU 11-4.19.6; SHOWER DETAIL
 SECTION 11-4.21.1 THRU 11-4.21.8.
 2.HOT WATER REQUIRED TO SERVICE SINK.
 (SHOW ON PLANS)LOCATION SIZE AND FUIL
 SORCE OF WATER HEATER.
 3.SANITARY RISER DIAGRAM;
 A)TRENCH DRAIN AND FLOOR DRAIN SHALL
 NOT BE DOUBLE TRAPPED. SEC.1002.1
 B)WHAT IS THE 4" VERTICAL DRAIN AND
 BACK WATER VALVE FOR? NEED MORE
 INFOREMATION.
 C)WHY IS A FLOOR DRAIN NEEDED IN THE
 FUTURE PAINT BOOTH? (SECOND
 REQUEST)
 4. SAND INTERCEPTER; (SECOND REQUEST)
 PLANS MUST BE REVIEW AND APROVED BY THE
 UTILITY DEPARTMENT FOR SIZE AND
 LOCATION.
 THE CONTACT PERSON IS;
 LYNN MASSON
 PHONE822-2271
 FAX 822-2279
 E-MAIL [email protected]
 5.PLUMBING FIXTURE REQUIREMENT TABLE FOR
 PHASE 11 IS NOT CORRECT. WORK WILL BE
 DONE IN IN THIS PART OF THE BUILDING.
 PLEASE CHANGE CLASIFICATION TO BUSINESS,
 OR CHANGE BOTH PHASES TO BUSINESS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-06-29 Cont ID  
Sent By jleech Date 2006-06-29 Time 08:53 Rev Time 0.00
Received By jleech Date 2006-06-29 Time 08:53 Sent To  
Notes
2006-06-29 00:00:00FIXTURE CHANGE OUT ONLY.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-04-04 Cont ID  
Sent By jleech Date 2006-04-04 Time 13:29 Rev Time 0.00
Received By jleech Date 2006-04-04 Time 13:29 Sent To  
Notes
2006-04-04 00:00:00DENIED;
 NO PLUMBING WORK SHOWN ON DRAWINGS.
 NO TYPE OF BUSINESS LISTED ON DRAWINGS.
 IF AUTOMOTIVE REPAIRS ARE TO BE DONE
 SAFTY EQUIPMENT @EYE WASH, SHOWER MAY BE
 REQUIRED. OIL OR SAND INTERSEPTOR MAY BE
 REQUIRED. SHOW COMPLIANCE TO FBC-2004
 PLUMBING TABLE 403.1 AND CHAPTER 11 OF
 THE BUILDING CODE ACCESSIBILITY CODE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-25 Cont ID  
Sent By jleech Date 2006-01-25 Time 07:19 Rev Time 0.50
Received By jleech Date 2006-01-25 Time 07:19 Sent To  
Notes
2006-01-25 00:00:00DENIED;
 NO PLUMBING SHOWN ON DRAWINGS. PLEASE
 SHOW PLUMBING WORK SCOTT MAXWELL
 PLUMBING WILL DO.
 SHOW COMPLIANCE TO FBC-2004 PLUMBING
 TABLE 403.1 (MINIMUM PLUMBING FIXTURES,
 AND FBC-2004 CHAPTER 11 .
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695