Plan Review Details - Permit 06010310
Plan Review Stops For Permit 06010310
Review Stop AD ADDRESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-02 Cont ID  
Sent By jwitmer Date 2006-05-02 Time 10:00 Rev Time 33.33
Received By jwitmer Date 2006-04-26 Time 14:15 Sent To  
Notes
2006-04-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06010310
 ADD: 720 S. DIXIE HWY.
 CONT: THE WEITZ CO
 TEL: (561)719-0317
  
 ----- THE HARRICK-----
  
 ARCH FIRM:OLIVER GLIDEN SPINA & PARTNERS
  
 KEITH M SPINA
 ENGFIRM: ONMJ O'DONNELL, NACCARAATO,
 MIGNOGNA& JOHNSON STRUCTURAL
  
 ENGINEERS
 PHILLIP J. RIZZO
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUM- BER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICA TION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CON- TAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 6) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 7) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
  
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
  
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
  
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
  
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
  
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
  
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) NUMBER OF UNITS
 H) NUMBER OF FLOORS
 I) NUMBER OF BEDROOMS
 J) NUMBER OF ROOMS
 K) NUMBER OF BEDROOMS
 L) SQ. FT. LIV SPACE/ FL
 M) SQ. FT. FOOTPRINT
 N) SQ. FT. UNDER ROOF (TOTAL)
 O) OCCUPANT LOAD
 P) FLOOD ZONE
  
 8) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 9) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 10) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 601
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 11) PLANS DO NOT HAVE AN INDEX PAGE
 MAKING IT DIFICULT TO LOCATE ITEMS FOR
 PLAN REVIEW.
  
 12) SHEET A2.1.1 INDICATES A FIRE
 CONTROL ROOM, IF THIS IS THE SAME AS A
 FIRE COMMAND CENTER THERE ARE MINIMUM
 ROOM DIMENSIONS, SHOW COMPLIANCE:
 911.1 FEATURES.
 WHERE REQUIRED BY OTHER SECTIONS OF THIS
 CODE, A FIRE COMMAND CENTER FOR FIRE
 DEPARTMENT OPERATIONS SHALL BE PROVIDED.
 THE LOCATION AND ACCESSIBILITY OF THE
 FIRE COMMAND CENTER SHALL BE SEPARATED
 FROM THE REMAINDER OF THE BUILDING BY
 NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE-RATED FIRE BARRIER. THE
 ROOM SHALL BE A MINIMUM OF 96 SQUARE
 FEET (9 M 2 ) WITH A MINIMUM DIMENSION
 OF 8 FEET (2438 MM). A LAYOUT OF THE
 FIRE COMMAND CENTER AND ALL FEATURES
 REQUIRED BY THE SECTION TO BE CONTAINED
 THEREIN SHALL BE SUBMITTED FOR APPROVAL
 PRIOR TO INSTALLATION. THE FIRE COMMAND
 CENTER SHALL COMPLY WITH NFPA 72 AND
 SHALL CONTAIN THE FOLLOWING FEATURES.
 1.THE EMERGENCY VOICE/ALARM
 COMMUNICATION SYSTEM UNIT.
 2.THE FIRE DEPARTMENT
 COMMUNICATIONS UNIT.
 3.FIRE DETECTION AND ALARM SYSTEM
 ANNUNCIATOR UNIT.
 4.ANNUNCIATOR UNIT VISUALLY
 INDICATING THE LOCATION OF THE ELEVATORS
 AND WHETHER THEY ARE OPERATIONAL.
 5.STATUS INDICATORS AND CONTROLS
 FOR AIR-HANDLING SYSTEMS.
 6.THE FIRE-FIGHTER?S CONTROL PANEL
 REQUIRED BY SECTION 909.16 FOR SMOKE
 CONTROL SYSTEMS INSTALLED IN THE
 BUILDING.
 7.CONTROLS FOR UNLOCKING STAIRWAY
 DOORS SIMULTANEOUSLY.
 8.SPRINKLER VALVE AND WATER-FLOW
 DETECTOR DISPLAY PANELS.
 9.EMERGENCY AND STANDBY POWER
 STATUS INDICATORS.
 10.A TELEPHONE FOR FIRE DEPARTMENT
 USE WITH CONTROLLED ACCESS TO THE PUBLIC
 TELEPHONE SYSTEM.
 11.FIRE PUMP STATUS INDICATORS.
 12.SCHEMATIC BUILDING PLANS
 INDICATING THE TYPICAL FLOOR PLAN AND
 DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS,
 FIRE-FIGHTING EQUIPMENT AND FIRE
 DEPARTMENT ACCESS.
 13.WORKTABLE.
 14.GENERATOR SUPERVISION DEVICES,
 MANUAL START AND TRANSFER FEATURES.
 15.PUBLIC ADDRESS SYSTEM, WHERE
 SPECIFICALLY REQUIRED BY OTHER SECTIONS
 OF THIS CODE.
  
 13A) A2.1.1 SHOW COMPLIANCE AT THE ENTRY
 DROP OFF ZONE/ VALET PARKING/ LOADING
 ZONE.
 11-4.6.6 PASSENGER LOADING ZONES.
 PASSENGER LOADING ZONES SHALL PROVIDE AN
 ACCESS AISLE AT LEAST 60 INCHES (1525
 MM) WIDE AND 20 FEET (6096 MM) LONG
 ADJACENT AND PARALLEL TO THE VEHICLE
 PULL-UP SPACE (SEE FIGURE 11-10 ). IF
 THERE ARE CURBS BETWEEN THE ACCESS AISLE
 AND THE VEHICLE PULL-UP SPACE, THEN A
 CURB RAMP COMPLYING WITH SECTION 11-4.7
 SHALL BE PROVIDED. VEHICLE STANDING
 SPACES AND ACCESS AISLES SHALL BE LEVEL
 WITH SURFACE SLOPES NOT EXCEEDING 1:50
 (2 PERCENT) IN ALL DIRECTIONS.
 FL S S 553.5041(1)
  
 13B) A2.1.1 SHOW COMPLIANCE WITH "VAN
 ACCESSIBLE PARKING" 11-4.6.4.
  
 14) A2.1.1, EXIT CORRIDOR# 112 INDICATES
 A RAMP WITH 12" RISE NO HANDRAILS,
 1010.8 HANDRAILS.
 HANDRAILS SHALL BE PROVIDED ALONG BOTH
 SIDES OF A RAMP RUN WITH A RISE GREATER
 THAN 6 INCHES (152 MM) AND SHALL CONFORM
 TO THE REQUIREMENTS IN SECTIONS 1009.11
 . IF HANDRAILS ARE NOT CONTINUOUS, THEY
 SHALL EXTEND AT LEAST 18 INCHES (305 MM)
 BEYOND THE TOP AND BOTTOM OF THE RAMP
 SEGMENT AND SHALL BE PARALLEL WITH THE
 FLOOR OR GROUND SURFACE. ENDS OF
 HANDRAILS SHALL BE EITHER ROUNDED OR
 RETURNED SMOOTHLY TO FLOOR, WALL OR
 POST. HANDRAILS SHALL NOT ROTATE WITHIN
 THEIR FITTINGS. TOP OF THE HANDRAIL
 GRIPPING SURFACE SHALL BE NOT LESS THAN
 34 INCHES (864 MM) NOR MORE THAN 38
 INCHES (965 MM) ABOVE THE RAMP SURFACE.
 11-4.8.5 HANDRAILS.
 IF A RAMP RUN HAS A RISE GREATER THAN 6
 INCHES (150 MM) OR A HORIZONTAL
 PROJECTION GREATER THAN 72 INCHES (1830
 MM), THEN IT SHALL HAVE HANDRAILS ON
 BOTH SIDES. HANDRAILS ARE NOT REQUIRED
 ON CURB RAMPS OR ADJACENT TO SEATING IN
 ASSEMBLY AREAS. HANDRAILS SHALL COMPLY
 WITH SECTION 11-4.26 AND SHALL HAVE THE
 FOLLOWING FEATURES:
 (1)HANDRAILS SHALL BE PROVIDED
 ALONG BOTH SIDES OF RAMP SEGMENTS. THE
 INSIDE HANDRAIL ON SWITCHBACK OR DOGLEG
 RAMPS SHALL ALWAYS BE CONTINUOUS.
 (2)HANDRAILS ON RAMPS WHICH ARE NOT
 CONTINUOUS SHALL EXTEND NOT LESS THAN 18
 INCHES (457 MM) BEYOND THE SLOPED
 SEGMENT AT BOTH THE TOP AND BOTTOM, AND
 SHALL BE PARALLEL TO THE FLOOR OR GROUND
 SURFACE.
 (3)THE CLEAR SPACE BETWEEN THE
 HANDRAIL AND THE WALL SHALL BE 1? INCHES
 (38 MM).
 (4)GRIPPING SURFACES SHALL BE
 CONTINUOUS.
 (5)TOP OF HANDRAIL GRIPPING
 SURFACES SHALL BE MOUNTED BETWEEN 34
 INCHES AND 38 INCHES (865 MM AND 965 MM)
 ABOVE RAMP SURFACES.
 (6)ENDS OF HANDRAILS SHALL BE
 EITHER ROUNDED OR RETURNED SMOOTHLY TO
 FLOOR, WALL, OR POST.
 (7)HANDRAILS SHALL NOT ROTATE
 WITHIN THEIR FITTINGS.
  
 15) COMMON TO ALL FLOORS, THE PLANS DO
 NOT INDICATE FIRE RESISTANCE RATING TO
 ANY WALLS, TENANT SEPERATION, CORRIDOR
 WALLS, ETC.707.2/TABLE 1016.1.
  
 16) A2.2.1 PLANS ARE MISSING DOORS AT
 231B.
  
 17) A2.2.1. ELEVATOR LOBBY PLANS
 INDICATE 45 MIN DOORS WITH THE EXCEPTION
 OF 201A AND 231B. 707.14.1.
  
 18) PLEASE PROVIDE SINK DETAILS FOR
 STAFF BREAK ROOM.
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 19) A2.2.1 RESTROOM DETAIL INDICATES A
 SECTION )/ A6.00 FOR ENLARGED PLAN AND
 DIMENSIONS. NO SUCH SHEET.
  
 20) A2.2.1 DETAIL 1/ A5.5 THIS DETAIL IS
 A 2ND FLOOR BALCONY GAURD RAIL DETAIL
 BUT DETAIL IS FOR THE 14TH -21ST FLOORS.
 PLEASE CORECT.
  
 21)A2.3.1 ROOM 302 (EXIT ACCESS
 CORRIDOR) THIS IS NOT A EXIT ACCESS
 CORRIDOR BUT A EXIT PASSAGE.DEFINITION:
 EXIT PASSAGEWAY. AN EXIT COMPONENT THAT
 IS SEPARATED FROM ALL OTHER INTERIOR
 SPACES OF A BUILDING OR STRUCTURE BY
 FIRE-RESISTANCE-RATED CONSTRUCTION AND
 OPENING PROTECTIVES, AND PROVIDES FOR A
 PROTECTED PATH OF EGRESS TRAVEL IN A
 HORIZONTAL DIRECTION TO THE EXIT
 DISCHARGE OR THE PUBLIC WAY. EXTENTION
 OF EXIT.SEE SECTION A0.0.
  
 22)A2.3.1 NORTH WALL INDICATES LOUVERS
 ON THE NORTH WALL, PLANS DO NOT PROVIDE
 THE DIMENSION FROM THE BUILING LINE TO
 THE NORTH NOR EAST PROPERTY LINE. TABLE
 503, TABL4 601, TABLE 602 & TABLE 704.8.
  
 23) THE FREIGHT ELEVATOR FOR VEHICLES
 FLOORS 1-4.
 3002.1 HOISTWAY ENCLOSURE PROTECTION.
 ELEVATOR , DUMBWAITER AND OTHER HOISTWAY
 ENCLOSURES SHALL HAVE A FIRE-RESISTANCE
 RATING NOT LESS THAN THAT SPECIFIED IN
 CHAPTER 6 AND SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH CHAPTER 7 . 707.2 SHAFT
 ENCLOSURE REQUIRED.
  
 OPENINGS THROUGH A FLOOR/CEILING
 ASSEMBLY SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE COMPLYING WITH THIS SECTION
  
 3002.1.1 OPENING PROTECTIVES.
 OPENINGS IN HOISTWAY ENCLOSURES SHALL BE
 PROTECTED AS REQUIRED IN CHAPTER 7 .
  
 24) PROVIDE INFORMATION ON VEHICLE
 STORAGE SYSTEM.
  
 25) THIRD & FOURTH FLOOR PARKING GARAGE.
  
 25A)110.4.2* STORAGE & FACTORY-
 INDUSTRIAL OCCUPANCIES.
 IT SHALL BE THE RESPONSIBILITY OF THE
 OWNER, AGENT, PROPIETOR OR OCCUPANT OF
 GROUP S AND GROUP F OCCUPANCIES, OR ANY
 OCCUPANCY WHERE EXCESSIVE FLOOR LOADING
 IS LIKELY TO OCCUR, TO EMPLOY A
 COMPETENT ARCHI- TECT OR ENGINEER IN
 COMPUTING THE SAFE FLOOR LOAD CAPACITY.
 ALL SUCH COMPUTA- TIONS SHALL BE
 ACCOMPANIED BY AN AFFA- DAVIT FROM THE
 ARCHITECT OR ENGINEER STATING THE SAFE
 ALLOWABLE FLOOR LOADS ON EACH FLOOR IN
 POUNDS PER SQ FT.THE COMPUTATIONS &
 AFFADAVIT SHALL BE FILED AS A PERMANENT
 RECORD OF THE BLDG DEPT.
  
 25B) 110.4.3* SIGNS REQUIRED. IN EVERY
 BUILDING OR PART OF A BUILDING USED FOR
 STORAGE, INDUSTRIAL OR HAZARDOUS PUR-
 POSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN,
 SHALL BE MARKED ON PLATES OF APPROVED DE
 SIGN WHICH SHALL BE SUPPLIED & SECURELY
 AFFIXED BY THE OWNER OF THE BUILDING IN
 A CONSPICUOUS PLACE IN EACH STORY TO
 WHICH THEY RELATE. SUCH PLATES SHALL NOT
 BE REMOVEDOR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL
 REPLACE THEM.
  
 25C)1607.9.1.1 HEAVY LIVE LOADS.
 LIVE LOADS THAT EXCEED 100 PSF (4.79
 KN/M 2 ) SHALL NOT BE REDUCED EXCEPT THE
 LIVE LOADS FOR MEMBERS SUPPORTING TWO OR
 MORE FLOORS ARE PERMITTED TO BE REDUCED
 BY A MAXIMUM OF 20 PERCENT, BUT THE LIVE
 LOAD SHALL NOT BE LESS THAN L AS
 CALCULATED IN SECTION 1607.9.1 .
  
 25D) 1607.9.1.2 PASSENGER VEHICLE
 GARAGES. THE LIVE LOADS SHALL NOT BE
 REDUCED IN PASSENGER VEHICLE GARAGES
 EXCEPT THE LIVE LOADS FOR MEMBERS
 SUPPORTING TWO OR MORE FLOORS ARE
 PERMITTED TO BE REDUCED BY A MAXIMUM OF
 20 PERCENT, BUT THE LIVE LOAD SHALL NOT
 BE LESS THAN L AS CALCULATED IN SECTION
 1607.9.1 .
  
 26) MECH M2.3/ M2.4 BOTH INDICATE
 MECHANICAL EQUIPMENT IN THE EXIT
 PASSAGEWAY THAT DO NOT HAVE ANY BEARING
 ON THE STAIR PRESSURIZATION FOR THE EXIT
 1020.5 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH
 AN EXIT PASSAGEWAY ARE PROHIBITED EXCEPT
 FOR REQUIRED EXIT DOORS, EQUIPMENT AND
 DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE
 DEPARTMENT COMMUNICATION AND ELECTRICAL
 RACEWAY SERVING THE EXIT PASSAGEWAY AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M 2 ). SUCH
 PENETRATIONS SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 712 . THERE
 SHALL BE NO PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT
 PASSAGEWAYS.
  
 27) MECH M2.3/ M2.4 BOTH STAIRWELLS
 INDICATE THE USE OF LOUVER GRAVITY
 DAMPERS, PROVIDE ADDITIONAL INFORMATION
 WHERE THEY HAVE A 1 1/2 HR FIRE RATING.
  
 28) SHEET A2.5.1 DETAIL OF ELEVATOR
 LOBBY 0/ A6.0.0 MISSING DETAIL
  
 29) A2.5.1 ELEVATOR LOBBY DOORS T04A &
 T04B, BOTH DOORS AND ELEVATOR LOBBY
 DOORS 5TH FLOOR AND ABOVEARE MISSING
 THE FIRE RATING OF 3/4 HR SEE 707.14.1./
 TABLE 1016.1.
  
 30) SHEET A2.5.1 EAST WEST CUT SECTION,
 DETAIL1/ A4.2 NO SUCH SECTION.
  
 31) SHEET A2.1.1- A2.10.1 ALL INDICATE
 PARTITION LEGEND, PROVIDE THE EQUIVALENT
 THICKNESS AND ASSOCIATED FIRE RESISTANCE
 RATING FOR BOTH CONCRETE MASONARY WALLS
 AND CAST IN PLACE CONCRETE.
 721.3.2 CONCRETE MASONRY WALLS.
 THE FIRE-RESISTANCE RATING OF WALLS AND
 PARTITIONS CONSTRUCTED OF CONCRETE
 MASONRY UNITS SHALL BE DETERMINED FROM
 TABLE 721.3.2 . THE RATING SHALL BE
 BASED ON THE EQUIVALENT THICKNESS OF THE
 MASONRY AND TYPE OF AGGREGATE USED.
 REPORT FROM THE BLOCK MANUFACTURER FOR
 RATING OF BLOCK.NOT U. L. LISTING.
 721.2.1.1 CAST-IN-PLACE OR PRECAST
 WALLS.
 THE MINIMUM EQUIVALENT THICKNESSES OF
 CAST-IN-PLACE OR PRECAST CONCRETE WALLS
 FOR FIRE-RESISTANCE RATINGS OF 1 HOUR TO
 4 HOURS ARE SHOWN IN TABLE 721.2.1.1 .
 FOR SOLID WALLS WITH FLAT VERTICAL
 SURFACES, THE EQUIVALENT THICKNESS IS
 THE SAME AS THE ACTUAL THICKNESS. THE
 VALUES IN TABLE 721.2.1.1 APPLY TO
 PLAIN, REINFORCED OR PRESTRESSED
 CONCRETE WALLS.
  
 32) A2.5.1 DETAIL 1/A5.4INDICATES A CUT
 SECTION THROUGH A BALCONY BUT NO DETAILS
 GIVEN FOR BALCONY RAILING. GLASS IN
 HANDRAILS AND GUARDS.2407.1 MATERIALS.
 GLASS USED AS STRUCTURAL BALUSTRADE
 PANELS IN RAILINGS SHALL BE CONSTRUCTED
 OF EITHER SINGLE FULLY TEMPERED GLASS,
 LAMINATED FULLY TEMPERED GLASS OR
 LAMINATED HEAT-STRENGTHENED GLASS.
 GLAZING IN RAILING IN-FILL PANELS SHALL
 BE OF AN APPROVED SAFETY GLAZING
 MATERIAL THAT CONFORMS TO THE PROVISIONS
 OF SECTION 2406.1.1 . FOR ALL GLAZING
 TYPES, THE MINIMUM NOMINAL THICKNESS
 SHALL BE ? INCH (6.4 MM). FULLY TEMPERED
 GLASS AND LAMINATED GLASS SHALL COMPLY
 WITH CATEGORY II OF CPSC 16 CFR 1201,
 LISTED IN CHAPTER 35 .
  
 2407.1.1 LOADS.
 THE PANELS AND THEIR SUPPORT SYSTEM
 SHALL BE DESIGNED TO WITHSTAND THE LOADS
 SPECIFIED IN SECTION 1607.7 . A SAFETY
 FACTOR OF FOUR SHALL BE USED.
  
 2407.1.2 SUPPORT.
 EACH HANDRAIL OR GUARD SECTION SHALL BE
 SUPPORTED BY A MINIMUM OF THREE GLASS
 BALUSTERS OR SHALL BE OTHERWISE
 SUPPORTED TO REMAIN IN PLACE SHOULD ONE
 BALUSTER PANEL FAIL. GLASS BALUSTERS
 SHALL NOT BE INSTALLED WITHOUT AN
 ATTACHED HANDRAIL OR GUARD .
  
 33)A2.5.1 LAUNDRY CHUTE REQUIRES A 2HR
 RATED WALL PROVIDE THE EQUIVALENT
 THICKNESS AND TYPE OF BLOCK TO BE USED,
 FROM BLOCK MANUFACTURER.
  
  
 34) SERVICE ELEVATOR MISSING ELEVATOR
 LOBBY,707.14.1 ELEVATOR LOBBY.
 ELEVATORS OPENING INTO A
 FIRE-RESISTANCE-RATED CORRIDOR AS
 REQUIRED BY SECTION 1016.1 SHALL BE
 PROVIDED WITH AN ELEVATOR LOBBY AT EACH
 FLOOR CONTAINING SUCH A CORRIDOR. THE
 LOBBY SHALL SEPARATE THE ELEVATORS FROM
 THE CORRIDOR BY FIRE PARTITIONS AND THE
 REQUIRED OPENING PROTECTION. ELEVATOR
 LOBBIES SHALL HAVE AT LEAST ONE MEANS OF
 EGRESS COMPLYING WITH CHAPTER 10 AND
 OTHER PROVISIONS WITHIN THIS CODE.
  
 35) A2.9.1 COOLING TOWERS ONCE DOOR IS
 OPENED TO THIS AREA THERE IS NO 36"
 MEANS OF EGRESS AROUND THE COOLING
 TOWERS.
  
 36) 1509.7 MECHANICAL UNITS.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE
 MOUNTED ON CURBS RAISED A MINIMUM OF 8
 INCHES (203 MM) ABOVE THE ROOF SURFACE,
 OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARANCE
 HEIGHT IN ACCORDANCE WITH TABLE 1509.7 .
  
  
 37) A2.9.1 PLAN INDICATES FOR ENLARGED
 STAIR PLAN AND DIMENSIONS SEE A0.0.0.
  
 38) A2.9.1 MECHANICAL ROOM/ COOLING
 TOWERS PLANS DO NOT INDICATE THERE IS TO
 BE A GENERATOR LOCATED IN THIS AREA ,SEE
 M2.22. PROVIDE DETAILS FOR GENERATOR,
 FOR COMPLIANCE WITH:
 403.10.1 SPECIAL REQUIREMENTS FOR
 STANDBY POWER SYSTEMS.
 IF THE STANDBY SYSTEM IS A GENERATOR SET
 INSIDE A BUILDING, THE SYSTEM SHALL BE
 LOCATED IN A SEPARATE ROOM ENCLOSED WITH
 2-HOUR FIRE-RESISTANCE-RATED FIRE
 BARRIER ASSEMBLIES. SYSTEM SUPERVISION
 WITH MANUAL START AND TRANSFER FEATURES
 SHALL BE PROVIDED AT THE FIRE COMMAND
 CENTER. SURROUNDING WALL 2HR WITH
 1 1/2HR OPENING PROTECTIVES, DOOR M04A.
  
 39) A2.10.1 AT SECTION 1/ A5.1JUST TO
 THE RIGHT OF THIS SECTION THE HEIGHT OF
 THE PLANTER WALL 3'-2" AND THE HEIGHT OF
 THE GLASS RAIL AS 3'-2". SEE DETAIL
 1/A5.1 THE GLASS RAILING SITS ATOP OF
 THE PLANTER WALL AN ADDITIONAL 3'-71/2".
  
 40) A2.10.1 THE ELEVATOR DOORS AND
 WINDOWS ON EITHER SIDE OF THE ELEVATOR
 LOBBY ARE MISSING THE 1 1/2 HR RATING.
 707.14.1 ELEVATOR LOBBY.
 ELEVATORS OPENING INTO A
 FIRE-RESISTANCE-RATED CORRIDOR AS
 REQUIRED BY SECTION 1016.1 SHALL BE
 PROVIDED WITH AN ELEVATOR LOBBY AT EACH
 FLOOR CONTAINING SUCH A CORRIDOR. THE
 LOBBY SHALL SEPARATE THE ELEVATORS FROM
 THE CORRIDOR BY FIRE PARTITIONS AND THE
 REQUIRED OPENING PROTECTION. ELEVATOR
 LOBBIES SHALL HAVE AT LEAST ONE MEANS OF
 EGRESS COMPLYING WITH CHAPTER 10 AND
 OTHER PROVISIONS WITHIN THIS CODE.
  
 41) A2.10.1 THE MENS AND WOMENS
 HANDICAPPED TOILET STALL DOORS ARE NOT
 DIMENSIONED PLEASE SEE FIGURE 30, THE
 STALL DOOR TO BE 32" CLEAR.
  
 42) NOTE: 424.1 PUBLIC SWIMMING POOLS
 AND BATHING PLACES.
 PUBLIC SWIMMING POOLS AND BATHING PLACES
 SHALL COMPLY WITH THE DESIGN AND
 CONSTRUCTION STANDARDS OF THIS SECTION.
 NOTE: OTHER ADMINISTRATIVE AND
 PROGRAMMATIC PROVISIONS MAY APPLY. SEE
 DEPARTMENT OF HEALTH (DOH) RULE 64E-9,
 FLORIDA ADMINISTRATIVE CODE AND CHAPTER
 514, FLORIDA STATUTES.FAC 514 PUBLIC
 SWIMMING AND BATHING FACILITIES.
  
 43) A2.10.1 BAR D11 NO CUT SECTION
 INDICATING COMPLIANCE WITH, FAIR HOUSING
 REACH RANGES, ACCESSIBLE OUTE BEHIND
 BAR.
  
 44)A2.11.1 PLANS DO NOT INDICATE
 ELEVATOR VENTS OR NOTES WHERE TO FIND
 VENTS.
 3004.2 LOCATION OF VENTS.
 VENTS SHALL BE LOCATED BELOW THE FLOOR
 OR FLOORS AT THE TOP OF THE HOISTWAY,
 AND SHALL OPEN EITHER DIRECTLY TO THE
 OUTER AIR OR THROUGH NONCOMBUSTIBLE
 DUCTS TO THE OUTER AIR. NONCOMBUSTIBLE
 DUCTS SHALL BE PERMITTED TO PASS THROUGH
 THE ELEVATOR MACHINE ROOM PROVIDED THAT
 PORTIONS OF THE DUCTS LOCATED OUTSIDE
 THE HOISTWAY OR MACHINE ROOM ARE
 ENCLOSED BY CONSTRUCTION HAVING NOT LESS
 THAN THE FIRE PROTECTION RATING REQUIRED
 FOR THE HOISTWAY. HOLES IN THE MACHINE
 ROOM FLOORS FOR THE PASSAGE OF ROPES,
 CABLES OR OTHER MOVING ELEVATOR
 EQUIPMENT SHALL BE LIMITED SO AS NOT TO
 PROVIDE GREATER THAN 2 INCHES (51 MM) OF
 CLEARANCE ON ALL SIDES.
  
 3004.3 AREA OF VENTS.
 EXCEPT AS PROVIDED FOR IN SECTION
 3004.3.1 , THE AREA OF THE VENTS SHALL
 NOT BE LESS THAN 3? PERCENT OF THE AREA
 OF THE HOISTWAY NOR LESS THAN 3 SQUARE
 FEET (0.28 M 2 ) FOR EACH ELEVATOR CAR,
 AND NOT LESS THAN 3? PERCENT NOR LESS
 THAN 0.5 SQUARE FOOT (0.047 M 2 ) FOR
 EACH DUMBWAITER CAR IN THE HOISTWAY,
 WHICHEVER IS GREATER. OF THE TOTAL
 REQUIRED VENT AREA, NOT LESS THAN
 ONE-THIRD SHALL BE OF THE PERMANENTLY
 OPEN TYPE UNLESS ALL VENTS ACTIVATE UPON
 DETECTION OF SMOKE FROM ANY OF THE
 ELEVATOR LOBBY SMOKE DETECTORS.
  
 45) A3.1.1 & A3.1.3 NORTH AND EAST
 ELEVATIONS, THE DISTANCE TO THE PROPERTY
 LINE IS NOT PROVIDED, THE ALLOWABLE AREA
 OF OPENINGS PER FLOOR CAN'T BE COMPUTED.
 704.8 ALLOWABLE AREA OF OPENINGS.
 THE MAXIMUM AREA OF UNPROTECTED OR
 PROTECTED OPENINGS PERMITTED IN AN
 EXTERIOR WALL IN ANY STORY SHALL NOT
 EXCEED THE VALUES SET FORTH IN TABLE
 704.8 . WHERE BOTH UNPROTECTED AND
 PROTECTED OPENINGS ARE LOCATED IN THE
 EXTERIOR WALL IN ANY STORY, THE TOTAL
 AREA OF THE OPENINGS SHALL COMPLY WITH
 THE FOLLOWING FORMULA:
  
 A/A+AU/AU<1.0
  
 46) A6.1.1- A6.14.2 1207.2 AIR-BORNE
 SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS
 OR OPENINGS IN CONSTRUCTION ASSEMBLIES
 FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE
 SEALED, LINED, INSULATED OR OTHERWISE
 TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT
 APPLY TO DWELLING UNIT ENTRANCE DOORS;
 HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 47) A6.1.1- A6.14.1 1207.3
 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN
 THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT
 LESS THAN 50 (45 IF FIELD TESTED) WHEN
 TESTED IN ACCORDANCE WITH ASTM E 492.
  
 48) A6.1.1 DOOR T01E TO BE A MINIMUM OF
 32" CLEAR, FAIR HOUSING ANSI A117.1-
 404.2.3.SMALL CLOSETS SUCH AS LINEN
 CLOSETS NOT COVERED, SHELVES WITHIN
 REACH, THIS CLOSEET IS 3'-0" DEEP.
  
 49) A6.2.1 DOOR T02C1 SEE DOOR CHART FOR
 WIDTH.
  
 50) A6.3.2 NOTE: REFER TO INTERIOR
 DESIGNERS DRAWINGS FOR ALL BATH
 ACCESSORY SPECIFICATIONS AND MOUNTING
 HEIGHT. THERE IS NO INDEX NOR NOTE
 INDICATING WHERE THIS INFORMATION CAN BE
 LOCATED. 11-4.26.2 SIZE AND SPACING OF
 GRAB BARS AND HANDRAILS.
 THE DIAMETER OR WIDTH OF THE GRIPPING
 SURFACES OF A HANDRAIL OR GRAB BAR SHALL
 BE 1? INCHES TO 1? INCHES (32 MM TO 38
 MM), OR THE SHAPE SHALL PROVIDE AN
 EQUIVALENT GRIPPING SURFACE. IF
 HANDRAILS OR GRAB BARS ARE MOUNTED
 ADJACENT TO A WALL, THE SPACE BETWEEN
 THE WALL AND THE GRAB BAR SHALL BE 1?
 INCHES (38 MM) [SEE FIGURE 11-39 (A),
 FIGURE 11-39 (B), FIGURE 11-39 (C), AND
 FIGURE 11-39 (E)]. HANDRAILS MAY BE
 LOCATED IN A RECESS IF THE RECESS IS A
 MAXIMUM OF 3 INCHES (76 MM) DEEP AND
 EXTENDS AT LEAST 18 INCHES (455 MM)
 ABOVE THE TOP OF THE RAIL [SEE FIGURE
 11-39 (D)].
 11-4.26.3
 11-4.26.3 STRUCTURAL STRENGTH.
 THE STRUCTURAL STRENGTH OF GRAB BARS,
 TUB AND SHOWER SEATS, FASTENERS AND
 MOUNTING DEVICES SHALL MEET THE
 FOLLOWING SPECIFICATION:
 (1)BENDING STRESS IN A GRAB BAR OR
 SEAT INDUCED BY THE MAXIMUM BENDING
 MOMENT FROM THE APPLICATION OF 250 LBF
 (1112 N) SHALL BE LESS THAN THE
 ALLOWABLE STRESS FOR THE MATERIAL OF THE
 GRAB BAR OR SEAT.
 (2)SHEAR STRESS INDUCED IN A GRAB
 BAR OR SEAT BY THE APPLICATION OF 250
 LBF (1112 N) SHALL BE LESS THAN THE
 ALLOWABLE SHEAR STRESS FOR THE MATERIAL
 OF THE GRAB BAR OR SEAT. IF THE
 CONNECTION BETWEEN THE GRAB BAR OR SEAT
 AND ITS MOUNTING BRACKET OR OTHER
 SUPPORT IS CONSIDERED TO BE FULLY
 RESTRAINED, THEN DIRECT AND TORSIONAL
 SHEAR STRESSES SHALL BE TOTALED FOR THE
 COMBINED SHEAR STRESS, WHICH SHALL NOT
 EXCEED THE ALLOWABLE SHEAR STRESS.
 (3)SHEAR FORCE INDUCED IN A
 FASTENER OR MOUNTING DEVICE FROM THE
 APPLICATION OF 250 LBF (1112 N) SHALL BE
 LESS THAN THE ALLOWABLE LATERAL LOAD OF
 EITHER THE FASTENER OR MOUNTING DEVICE
 OR THE SUPPORTING STRUCTURE, WHICHEVER
 IS THE SMALLER ALLOWABLE LOAD.
 (4)TENSILE FORCE INDUCED IN A
 FASTENER BY A DIRECT TENSION FORCE OF
 250 LBF (1112 N) PLUS THE MAXIMUM MOMENT
 FROM THE APPLICATION OF 250 LBF (1112N)
 SHALL BE LESS THAN THE ALLOWABLE
 WITHDRAWAL LOAD BETWEEN THE FASTENER AND
 THE SUPPORTING STRUCTURE.
 (5)GRAB BARS SHALL NOT ROTATE
 WITHIN THEIR FITTINGS.
 ALL HANDRAILS, GRAB BARS, AND TUB AND
 SHOWER SEATS REQUIRED TO BE ACCESSIBLE
 BY SECTION 11-4.1 , 11-4.8 , 11-4.9 ,
 11-4.16 , 11-4.17 , 11-4.20 OR 11-4.21
 SHALL COMPLY WITH SECTION 11-4.26 .
  
 51) A6.6.2 MASTER BEDROOM: 11-9.2.2
 MINIMUM REQUIREMENTS.
 AN ACCESSIBLE UNIT, SLEEPING ROOM OR
 SUITE SHALL BE ON AN ACCESSIBLE ROUTE
 COMPLYING WITH SECTION 11-4.3 AND HAVE
 THE FOLLOWING ACCESSIBLE ELEMENTS AND
 SPACES.
 (1)ACCESSIBLE SLEEPING ROOMS SHALL
 HAVE A 36 INCH (915 MM) CLEAR WIDTH
 MANEUVERING SPACE LOCATED ALONG BOTH
 SIDES OF A BED, EXCEPT THAT WHERE TWO
 BEDS ARE PROVIDED, THIS REQUIREMENT CAN
 BE MET BY PROVIDING A 36 INCHES (915 MM)
 WIDE MANEUVERING SPACE LOCATED BETWEEN
 THE TWO BEDS. CHECK ALL UNITS!
  
 51) A6.10.1A6.1.1 DOOR P01E TO BE A
 MINIMUM OF 32" CLEAR, FAIR HOUSING ANSI
 A117.1- 404.2.3.SMALL CLOSETS SUCH AS
 LINEN CLOSETS NOT COVERED, SHELVES
 WITHIN REACH, THIS CLOSEET IS 3'-0"
 DEEP.
  
 52)A6.13.1 MASTER BEDROOM MASTER
 BEDROOM: 11-9.2.2 MINIMUM REQUIREMENTS.
 AN ACCESSIBLE UNIT, SLEEPING ROOM OR
 SUITE SHALL BE ON AN ACCESSIBLE ROUTE
 COMPLYING WITH SECTION 11-4.3 AND HAVE
 THE FOLLOWING ACCESSIBLE ELEMENTS AND
 SPACES.
 (1)ACCESSIBLE SLEEPING ROOMS SHALL
 HAVE A 36 INCH (915 MM) CLEAR WIDTH
 MANEUVERING SPACE LOCATED ALONG BOTH
 SIDES OF A BED, EXCEPT THAT WHERE TWO
 BEDS ARE PROVIDED, THIS REQUIREMENT CAN
 BE MET BY PROVIDING A 36 INCHES (915 MM)
 WIDE MANEUVERING SPACE LOCATED BETWEEN
 THE TWO BEDS. CHECK ALL UNITS!
  
 53) A8.1.1 FINISH SCHEDULE NOT COMPLETE
 PAGE IS BLANK.
  
 54) A9.1 DETAILS 3& 4 ARE MISSING THE
 SOUND TRANSMITION RATING.1207.2
 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS
 OR OPENINGS IN CONSTRUCTION ASSEMBLIES
 FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE
 SEALED, LINED, INSULATED OR OTHERWISE
 TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT
 APPLY TO DWELLING UNIT ENTRANCE DOORS;
 HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 55) SHEET A9.1 REFERS BACK TO 0/A8.00
 FOR LIMITING HEIGHT AND GAUGE TABLE.
 THERE IS NO SUCH SHEET.
  
 56) SHEET A9.2 PROVIDE UL LISTING OR
 GYPSUM ASSOCIATION NUMBER FOR EACH
 ASSEMBLY.FIRE PARTITION. A VERTICAL
 ASSEMBLY OF MATERIALS DESIGNED TO
 RESTRICT THE SPREAD OF FIRE IN WHICH
 OPENINGS ARE PROTECTED.
 SHAFT ENCLOSURE. THE WALLS OR
 CONSTRUCTION FORMING THE BOUNDARIES OF A
 SHAFT.
  
 57) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 58)FL BLD CODE 1609.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) CURTAIN WALL
 B) STOREFRONT WINDOW AND DOOR
 C) LOUVERED DOORS -REQUIRES STORM
 SHUTTERS SEE REPORT (NOA)
 D) EXTERIOR DOOR AT AUTO ELEVATOR
 E) SOFFITS(EFIS)
 F) ROOF HATCH
 G) PRE-ENGINEERED A/C STANDS
 H) MULLIONS
  
 58) CONTRACTOR TO HIGHLIGHT WHICH
 ROOFING APPLICATION FLAT DECK SBS SYSTEM
 DECK TYPE APPLICATION TYPE 31 OR DECK
 TYPE 3.
  
 59) PLANS DO NOT ADEQUATELY PROVIDE
 WHAT TYPE OF WINDOWS ARE TO BE USED ,
 EXAMPLE UNITS 1707- 2107 WINDOW (00)
 DEPENDING ON TYPE OF WINDOW EAST
 ELEVATION REPORT FOR WIND TUNNEL TEST
 INDICATES A NEGATIVE PEAK PRESSURE OF
 105.
 PROVIDE MORE DETAIL OF WINDOW TYPES AND
 LOCATION. (WINDOW SCHEDULE)
  
 60) SHEET A5.8 PLANS INDICATE DROPPED
 CEILINGS BUT NO DETAILS INDICATING THE
 TYPE OF CEILING THICKNESS, TYPE OF
 FRAMING, THICKNESS SIZE, MATERIAL
 THICKNESS NOR FLANGE SIZE. PLANS ALSO DO
 NOT PROVIDE THE ALLOWABLE CEILING
 DEFLECTIONS. PLANS DO NOT INDICATE IF
 STIFF BACKS ARE USED.THIS SAME
 INFORMATION WILL BE REQUIRED FOR DROPPED
 SOFFITS INTERIOR AND EXTERIOR.
  
 61) (A5.6) EXTERIOR DETAILS THERE IS NO
 DETAILS INDICATING HOW TO FASATEN TO
 DECK ABOVE, FREQUENCY OF FASTENERS NOR
 SPACING. NO MENTION OF SUBSHEATHING OR
 FINISH.
  
 62) S-1 NOTE: 8'-0" THICK MAT FOUNDATION
 SEE DWG S-16 FOR DETAILS, NO DETAILS
  
 63) A6.1.1 HEARING IMPAIRED UNITS,
 SHOW COMPLIANCE WITH 11-9.3/ 11-4.28.4.
 PROVIDE MANUFACTURER SPEC SHEET.
  
 64) A6.11 TYPICAL BALCONY RAILING NOTE
 NOT COMPLETE.XXX
  
 ADDITIONAL COMMENTS MAY APPEAR ON THE
 NEXT REVIEW DUE TO THE RESPONCE TO THESE
 COMMENTS OR LACK THERE OFF.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)805-6731
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-04-10 Cont ID  
Sent By dpalmer Date 2006-04-10 Time 16:41 Rev Time 0.00
Received By dpalmer Date 2006-03-29 Time 20:29 Sent To  
Notes
2006-04-10 00:00:00IN REVIEW
 ******** UNSAT **********
  
 THE HARRICKHOTEL / CONDO
  
  
 1) NOTE: PLEASE BE SURE TO REFERENCE ALL
 THE CURRENT CODE IN EFFECT AS FOLLOWS.
 NFPA-20 (2002), NFPA-110 (2002). OTHERS
 ARE SHOWN CURRENT TO DATE.
  
 2) NOTE: PLEASE SEE "KEY NOTES" ON E1.1,
 #4 SEEMS TO BE #1, AND #1 SEEMS TO BE
 IDENTIFIED IN TWO LOCATIONS? PLEASE
 CORRELATE.
  
 3) NOTE: PLEASE CLARIFY AREAS INCLUDING
 FIRST FLOOR WHICH MENTIONS A FUTURE
 TENANT BUILD OUT YET, THIS ARE SEEMS TO
 BE THE LOBBY AREA OF THE HOTEL/ CONDO.
 HOW IS THIS TENANT BLD OUT?
  
 4) NOTE: PLEASE PROVIDE ALL ROOM AND
 AREA DESIGNATIONS ON PLANS.
 PLEASE ALSO PROVIDE ALL AREA AND ROOM
 DESIGNATIONS FOR UNITS AS SOME CODE
 COMPLIANCE ITEMS CAN NOT BE VERIFIED AT
 THIS TIME.
 215.5
  
 5) NOTE: PLEASE CORRELATE ALL DOORS FOR
 ELECTRICAL ROOMS FOR OUT SWING. PLEASE
 SEE ELECTRICAL PLANS INDICATE THE
 CORRECT OUT-SWING FOR MAIN ELECTRICAL
 ROOM; HOWEVER ARCHITECTURAL PLANS SHOW
 DOORS SWINGING INWARDS.
 PLEASE ALSO PLACE NOTE ON PLANS FOR
 REQUIRED PANIC HARDWARE.
 110.26
 PLEASE ALSO SEE ANY INTERFERENCE WITH
 MINIMUM WIDTHS AND EGRESS PATHS WHICH
 MAY BE AFFECTED.
 PLEASE PROVIDE NOTE FOR PANIC HARDWARE
 WHICH WILL BE REQUIRED.
 6) NOTE: PLEASE SEE MAIN ELECTRICAL ROOM
 SHALL CONTAIN TWICE THE CLEARANCES
 REQUIRED PER 110.26 FOR ATS EQUIPMENT
 PER NFPA-110 7.2.2.1.
 THIS WILL AFFECT LAYOUT AS SHOWN.
  
 7) NOTE: PLEASE SEE 6.24* FOR MANUAL
 MEANS OF DISCONNECT REQUIRED FOR ATS
 DEVICES.
 CAN NOT VERIFY AT THIS TIME.
  
 8) NOTE: PLEASE SEE 7.2.1.1 FOR MIN 2HR
 RATINGS FOR EPSS EQUIPMENT. NFPA-110
  
 9) NOTE: PLEASE SEE COLOR CODING OF
 277/480V SYSTEMS SHALL BE "BROWN,
 PURPLE, AND YELLOW". ORANGE IS ONLY FOR
 HIGH-LEG SYSTEMS AND IS NOT PERMITTED
 FOR 277/480V.
 215, 90.4.
  
 10) NOTE: PLEASE KNOW, "LIGHTNING
 PROTECTION"SYSTEM AS SHOWN IF
 INSTALLED BY A SUB CONTRACTOR WILL
 REQUIRED THIS TO BE PULLED UNDER A
 SEPARATE PERMIT.
  
 11) NOTE: PLEASE SEE NFPA-1107.3.3*
 THE INTENSITY OF ILLUMINATION IN THE
 ROOM HOUSING THE EPS EQUIPMENT FOR LEVEL
 1 SHALL BE 32.3 LUX (30 FT-CANDLES).
 PLEASE SHOW DETAIL.
  
 12) NOTE: PLEASE PROVIDE AIC RATINGS FOR
 ALL EPS EQUIPMENT. (ATS). PLEASE SEE
 6.5.2 NFPA-110.
 UNABLE TO VERIFY AT THIS TIME.
  
 13) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR ALL EQUIPMENT:
 ATS'S, GENERATOR, FIRE PUMP FIRE PUMP
 CONTROLLER, SUB-BASE FUEL TANK ETC.
 PLEASE SEE OTHER COMMENTS AND KNOW THAT
 MANY ITEMS FOR CODE COMPLIANCE CAN NOT
 BE REVIEW AT THIS TIME DUE TO THESE
 ITEMS NOT BEING SUBMITTED FOR REVIEW.
  
  
  
 14) NOTE: PLEASE SEE NFPA-20 7.2FOR
 LOCATION OF FP CONTROLLER, HEIGHT, NEMA
 TYPE 2 ENCLOSURES AND ROOM CONTAINING A
 FLOOR DRAIN.
  
 15) NOTE:PLEASE NOTE ON PLANS THE
 ACCEPTANCE OF THE EPS AS REQUIRED IN
 NFPA-110 7.13.
  
  
 16) NOTE: PLEASE PROVIDE NOTE ON PLANS
 WHICH PROHIBITS THE INSTALLATION OF ANY
 ELECTRICAL CONDUITS ETC IN STAIRS UNLESS
 SPECIFICALLY DESIGNATED TO THE STAIRS.
 PLEASE ALSO PROVIDE NOTE FOR ELEVATOR
 EQUIPMENT ROOMS.
 215.5
  
  
 17) NOTE: PLEASE SUBMIT WIND LOAD
 CALCULATIONS FOR ALL SITE LIGHTING POLES
 INCLUSIVE OF ATTACHED LIGHT FIXTURES.
 PLEASE KNOW, THIS SHOULD INCLUDE ANY
 POLE FIXTURES ON POOL DECK/ROOF
 LEVEL(S).
 THESE CALCULATIONS WHICH ARE REQUIRED AT
 THIS TIME SHALL MEET THE 2004 FBC WITH
 RESPECT TO WIND PRESSURES AND DESIGNS
 140 MPH.
  
 18) NOTE: PLEASE SEE GFI PROTECTION
 REQUIRED IN POOL AREAS FOR CIRCUITS
 EE22-26., PL-22 /27
  
 19) NOTE: PLEASE SEE FIXTURES ON FIXTURE
 SCHEDULE WHICH INDICATE 120V TYPE
 FIXTURES IN POOL AREAS, YET THESE ARE
 CIRCUITED TO THE 277/480V PANELS??
 PLEASE SEE THE CODE DOES NOT SEE TO
 PROVIDE COMMENTARY FOR ALLOWING 277/480V
 LIGHTING IN CLOSE PROXIMITY TO POOL
 AREAS.
 PLEASE VERIFY FIXTURES TYPES AND
 VOLTAGES AND ADJUST PLANS AND SCHEDULES
 AS NEEDED.
 680, 215.5.
  
 20) NOTE: PLEASE SEE NOTE TO BE PROVIDED
 ON ALL E-2.09AB FOR MINIMUM CLEARANCES
 FOR POOL AREA FIXTURES. PLEASE 680.22
 FOR HIGH VOLTAGE FIXTURES (5FT MIN W/
 GFI PROTECTION AND 10FT MIN FOR LOW
 VOLTAGE TYPE FIXTURES. 411.4
  
  
 21) NOTE: PLEASE SEE FIXTURE AS T-1
 SHOWN IN FIRE PUMP ROOM COULD NOT BE
 LOCATED ON SCHEDULE. PLEASE KNOW AND
 BATTERY BACK UP FIXTURE OF SOME SORT
 WILL BE REQUIRED. THIS FIXTURE AS SHOWN
 SEEMS TO BE SHADED WHICH LENDS
 IDENTIFICATION TO MANY OTHER FIXTURES ON
 PLANS WHICH ARE SHADED AND ARE FIXTURES
 WITH BATTERY BACK UP.
 NFPA-20, LS 101 NFPA-70
  
 22) NOTE:PLEASE SEE NFPA-20.6.2.2
 WHICH REQUIRES A MIN OF 8HRS RUNNING @
 100% LOAD FOR FIRE PUMP. PLEASE ALSO
 BEAR IN MIND THE MINIMUM 100% LOADS FOR
 ALL OTHER LEGALLY REQUIRED STAND-BY
 ITEMS
  
 23) NOTE: PLEASE VERIFY POWER LAYOUT FOR
 FLOORS 1-4. 16-21 SHOWN ON E-2.16, AND
 5-15, ?
 215.5
  
 24) NOTE: PLEASE SEE 2.23 WHICH SEEM TO
 SHOW TWO DIFFERENT B-1 FIXTURES. PLEASE
 CORRELATE AND SEE ONE SHADED AND THE
 OTHER IS NOT.
 REDLINED AT LOCATION(S).
  
 25) NOTE: PLEASE PROVIDE A BATTERY BACK
 FIXTURE OF SOME SORT IN ELEVATOR
 EQUIPMENT ROOMS.
 LS 101 7.8,7.9,700.16
  
 26) NOTE: PLEASE SEE E2.3, WHICH SHOWS
 WHAT APPEARS TO BE FCU LOCATED IN FRONT
 OFPANEL EH-3?
 PLEASE VERIFY IF UNIT IS CEILING
 MOUNTED?
 PLEASE SEE MANY OTHER UNITS IN
 ELECTRICAL ROOMS AND SPACES WHICH MAY
 NOT BE PERMITTED.
 110.26
  
  
 27) NOTE: PLEASE SEE 620.22, 620.23, AND
 620.24 FOR ALL MINIMUM REQUIRED
 DEDICATED BRANCH CIRCUITS. PLEASE SEE
 SOME APPEAR TO SHARE WITH OTHER AREAS
 BESIDES ONLY THE ELEVATOR EQUIPMENT
 ROOMS.
 ALL ROOMS SHALL CONTAIN THEIR OWN
 DEDICATED CIRCUITS AND MAY NOT FEED
 OTHER ROOMS OR OTHER COMMON AREAS.
  
 28) NOTE: PLEASE SEE FIRE PUMP ROOM
 WHICH SHOWS A SYMBOL WHICH COULD NOT BE
 IDENTIFIED. THIS IS ALSO LOCATED IN ROOM
 ADJACENT TO FIRE PUMP ROOM.
 215.5
  
 29) NOTE: PLEASE PROVIDE EMERGENCY
 LIGHTING FOR EGRESS TO THE PUBLIC RIGHT
 OF WAY. PLEASE SEE THE BREEZEWAY AREAS/
 DRIVE AREA WHICH MAY BE USED AS AN
 EGRESS PATH WAY.
 LS 101-7.8,7.9
  
 30) NOTE: PLEASE SEE FBC 2004 CHAPTER 13
 FOR MEANS OF CONTROL REQUIRED FOR
 EXTERIOR LIGHTING. PLEASE PROVIDE ANY
 AREA CALCULATIONS AS SET FORTH.
 13-415.1.ABC.2 (IF APPLICABLE)
  
 31) NOTE: PLEASE SEE 13-415.1.ABC.1.1 &
 .2 FOR CONTROL OF INTERIOR LIGHTS.
 PLEASE KNOW, ALL ROOMS NOT IN USE FOR
 24HR OPERATION SHALL CONTAIN MEANS OF
 BEING AUTOMATICALLY TURNED OFF.PLEASE
 KNOW, THIS INCLUDES ANY STORAGE,
 MECHANICAL, CLOSETS ETC.
 PLEASE SEE OTHER NEW REQUIREMENTS OF
 CHAPTER 13.
  
  
 32) NOTE:PLEASE PROVIDE COMPLETE
 PHOTO-METRICS FOR ALL CORRIDORS, EGRESS
 PATHS, STAIR TOWERS.
 PLEASE SEE 2003 NFPA-101 7.8 AND 7.9.
 THIS REQUIRES A MIN OF 10 FT CANDLES
 FOR STAIRS UNDER NORMAL POWER AND A
 MINIMUM OF 1 FT CANDLE UNDER EM POWER.
 PLEASE ALSO KNOW THAT BATTERY BACK UP
 FIXTURE IS ALREADY BEING SHOWN IN STAIR
 TOWERS.
 PLEASE KNOW THIS MAY BE A "TYPICAL"
 DETAIL FOR THESE AREAS.. PLEASE SEE
 OTHER AREAS BESIDES STAIRS SHALL BE
 PERMITTED TO PROVIDE 1FT CANDLE
 (AVERAGE) UNDER NORMAL AND EMERGENCY.
  
 33) NOTE:PLEASE SEE THAT ANY AFTER
 DUSK BEFORE DAWN SWIMMING WILL REQUIRE
 PHOTO-METRICS FOR POOL AREA(S). PLEASE
 KNOW, ALL PHOTO-METRICS WILL BE REQUIRED
 TO BE SUBMITTED TO PALM BEACH COUNTY
 HEALTH DEPARTMENT FOR REVIEW AND
 STAMPING. ONLY THE STAMPED PLANS/SHEETS
 FROM PBCHD SHOULD BE SUBMITTED.
  
 34) NOTE: PLEASE VERIFY SPECS FOR FIRE
 PUMP CONTROLLER. AS SHOWN THIS IS NOT AN
 ELECTRIC DRIVE UNITS, HOWEVER PLEASE SEE
 NFPA-20 AS THE MEANS OF DISCONNECTING IS
 REQUIRED ON THE OUTSIDE OF THE FIRE PUMP
 CONTROLLER. PLEASE SEE SPECS WERE NOT
 SUBMITTED AND UNABLE TO VERIFY THIS AT
 THIS TIME.
  
 35)NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1 AND .2 WITH RESPECT TO
 DESIGN IF LIGHTING CONTROL WHICH NOT 24
 HRS OF OPERATION, MEANS OF EGRESS OR FOR
 SECURITY PURPOSES.
  
 36) NOTE: PLEASE PROVIDE VOLTAGE DROP
 ANALYSIS FOR ALL FEEDERS AND BRANCH
 CIRCUITS. THIS MAY BE A WORST CASE
 SCENARIO FOR EACH.
 THIS MAY ALSO BE NOTED. PLEASE SEE FBC
 CHAPTER 13, 13-413.1.ABC.1.1, &.2.
 PLEASE SEE RISER MENTIONS VD FOR
 FEEDERS, YET THIS IS BUS-DUCT.
  
 37) NOTE: PLEASE SEE FAIR HOUSING ACT
 REGULATIONS, 24 CFR 100.205 WITH RESPECT
 TO HEIGHTS AND LOCATIONS FOR ALL
 ACCESSIBLE DEVICES.
 PLEASE PLACE NOTE ON PLANS FOR FHAR.
  
 38) NOTE: PLEASE SEE LOCATION OF
 GENERATOR LOCATED ON ROOF TOP IS STILL
 IN REVIEW AND WILL BE GONE OVER WITH
 FIRE MARSHAL'S OFFICE FOR ANY
 DETERMINING FACTOR'S WHICH MAY AFFECT
 THE ELECTRICAL PLANS.
 PLEASE KNOW, AT THIS TIME, THE EDS2 WILL
 BE REQUIRED TO CONTAIN A MAIN, WITH A
 MANUAL MEANS OF DISCONNECT LOCATED ON
 THE OUTSIDE OF THE EQUIPMENT. THE
 BREAKER LOCATED AT THE ROOFTOP GEN
 SHOULD BE THE UNIT TO CONTAIN THE SHUNT
 TRIP BREAKER. PLEASE ALSO KNOW, A MEANS
 OF SHUTTING DOWN THE NATURAL GAS AND
 OTHER FUEL SUPPLY WILL BE REQUIRED.
  
 39) NOTE: PLEASE SEE CODES WITH RESPECT
 TO LOCATIONS OF SMOKE DETECTORS.
 PLEASE SEE FIRE REVIEW COMMENTS AS THESE
 UNITS ARE ALSO TO BE CONDO UNITS
 CONTAINING COOKING FACILITIES, THE SD'S
 MAY NOT BE CONNECTED INTO THE MAIN
 BUILDING FA SYSTEM. PLEASE KNOW, IF THIS
 IS INDEED THE CASE THE SD'S WILL BE 120V
 BATTERY BACK UP AND CIRCUITED TO UNITS.
 THIS WILL AFFECT CIRCUITING AND INVOKE
 ARC FAULT PROTECTION.
 PLEASE SEE 2002 NFPA-72 11.5.1.1,
 11.5.8.3.5. SD'S ARE TO BE LOCATED A MIN
 OF 3FT FROM KITCHEN AND BATH DOORS AND A
 MIN OF 20FT FROM COOKING APPLIANCES.
 (WITH EXCEPTIONS TO THE DISTANCE FROM
 COOKING APPLIANCES.
 PLEASE PLACE NOTES ON PLANS.
  
  
 40) NOTE: PLEASE SEE 210.12 IN THE 2002
 NEC WHICH REQUIRES ARC FAULT PROTECTION
 FOR ALL "OUTLETS" ( SD'S, LTS, FANS,
 RECEPTS ETC.)IN BEDROOMS.
 PLEASE SEE NOTES ON PLANS FOR ALL UNITS
 INDICATE PROTECTION FOR RECEPTS ONLY.
 PLEASE SEE 2002 NEC.
  
  
 41) NOTE: PLEASE SEE 210.52 FOR
 RECEPTACLE SPACING INSIDE DWELLING UNITS
 FOR 2 FT, 6FT AND 12 FT RULE.
 PLEASE SEE UNIT LAYOUT AS MANY OF THESE
 HAVE BEEN REDLINED.
  
 42) NOTE: PLEASE SEE PLANS SEEM TO
 INDICATE A BUS-DUCT FROM NORMAL MDS2 TO
 EDS, YET RISER SHOWS CONDUITS AND
 FEEDERS. PLEASE CORRELATE AND ALSO SEE
 FORTH COMING COMMENTS WITH RESPECT TO
 CONDUCTORS AND SIZES.
  
 43) NOTE: PLEASE SEE DETAIL FOR FC ROOM,
 WHICH A 2' TABLE FOR PLAN/LAYOUT REVIEW,
 HOWEVER OVERVIEW OF ROOM DOES NOT SHOW
 THIS?
  
  
 44) NOTE: PLEASE PLACE NOTE ON PLANS FOR
 ALL SIGNAGE AND MAPPING TO BE LOCATED IN
 MAIN ELECTRICAL ROOM, FIRE COMMAND ROOM
 ETC.
 230.2E,700.8 ETC.
 PLEASE KNOW, ALL PERMANENT SIGNAGE SHALL
 CONTAIN A MINIMUM OF 1 INCH LETTERING ON
 A CONTRASTING BACKGROUND. PLEASE KNOW,
 MAPPING SHOWING THE PATHS FOR ACCESS TO
 SYSTEMS WILL BE REQUIRED AT FC ROOM
 LOCATION.
  
 45) NOTE: PLEASE PROVIDE ROOM/AREA
 DESIGNATIONS FOR INSIDE UNITS.
 215.5
  
 46) NOTE: PLEASE SEE CIRCUITING FOR
 DINING ROOMS AND AREAS OF THE LIKE SHALL
 BE ON ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS.
 210.52B1.
 UNABLE TO VERIFY.
  
 47) NOTE: PLEASE SEE MINIMUM FACILITIES
 FOR CONDO UNITS FOR WASHER/LAUNDRY,
 DRYERS.
 PLEASE VERIFY , IF UNITS ARE GOING TO BE
 OWNED CONDOS?
 220.16,220.18,210.11C1,210.52B
  
 48) NOTE: PLEASE VERIFY PANELS IN UNITS
 AS THESE ARE SHOWN AS 225A, WITH
 30CIRCUITS? PLEASE KNOW THIS IS NOT A
 COMMON SIZE.
 215.5 SEE NEXT COMMENT.
  
 49) NOTE: PLEASE CORRELATE ALL UNIT
 PANELS, OCP AND SIZES.
 PLEASE SEE RISER INDICATES PANELS AS
 100A?S, HOWEVER MANY UNITS ARE 125A
 FEEDS/ OCP ON THESE 100A PANELS. PLEASE
 ALSO SEE PANELS ARE SHOWN AS 225A?
  
 50) NOTE: PLEASE SEE PANEL WHICH ARE
 SHOWN WITH 150A OCP ON 100A PANELS. SEE
 GI, I,
 215.5
  
 51) NOTE: PLEASE SEE RISER DOES NOT
 INDICATE PANEL "G1" , ONLY SHOWS "G"?
 PLEASE CORRELATE.
 PLEASE ALSO SEE THESE ARE ALL SHOWN AS
 100A.
 215.5
  
  
 52) NOTE: PLEASE SEE MANY UNITS WHICH
 SHOW THE CONTROL FOR SWITCHING THE
 RECEPTS. THIS IS OK, HOWEVER PLEASE SEE
 PLANS INDICATE SWITCHING OF THE ENTIRE
 DEVICE. PLEASE KNOW, THIS IS OK, HOWEVER
 AN ADDITIONAL RECEPT WILL BE REQUIRED TO
 MEET OUTLET SPACING PER 210.52, 210.70
 THIS APPEARS TO BE A MISPRINT? PLEASE
 CORRELATE AND ADJUST.
 215.5
  
 53) NOTE: PLEASE SEE WHAT APPEARS TO BE
 TWO DIFFERENT SCALES USED FOR UNIT
 PLANS. PLEASE SEE SOME SHOWN AS 3/8 INCH
 AND OTHERS AS 1/4 INCH.
 PLEASE SEE T-06, P-05.
 PLEASE SEE THESE SEEM TO BE THE SAME
 SIZE.
 215.5
  
 54) NOTE: PLEASE VERIFY ALL AIC RATINGS
 ON PANELS AND BRANCH BREAKERS. PLEASE
 KNOW, IF PANELS MENTION 42K FOR RATINGS,
 THEN IT WILL BE ASSUMED THIS IS FOR BUS
 AND BRKR.
 110.9,215.5
 PLEASE CLARIFY.
  
 55) NOTE: PLEASE VERIFY ALL RANGES/COOK
 TOPS IN UNITS. PLEASE SEE SOME UNITS ARE
 SHOWN AS 4-BURNER AND SOME AS WHAT
 APPEARS TO BE 2-BURNERS? IN EITHER CASE
 PLEASE VERIFY THE 2-20A BREAKER FEEDING
 THESE UNITS AND THE KW RATINGS AS SOME
 UNITS ARE LARGER, YET BOTH SHOW THE SAME
 LOAD AND OCP?
 215.5
  
 56) NOTE: PLEASE SEE NOTES FOR KITCHEN
 GFI RECEPTS REFERENCE THE WRONG CODE.
 SHOULD BE 210.8A6.
  
 57) NOTE: PLEASE SEE NOTEON DRAWING
 NOTES WHICH MENTIONS DINING ROOMS TO BE
 GFI PER 210.52B1? PLEASE KNOW, 210.52B1
 DOES NOT MENTIONS GFI PROTECTION
 REQUIRED FOR DINING ROOM RECEPTS. PLEASE
 SEE DINING ROOM RECEPTS SHALL BE ON ONE
 OR MORE OF THE 20A SMALL APPLIANCE
 CIRCUITS.
  
 58) NOTE: PLEASE VERIFY ALL MAINS ,
 MDS1, MDS2, AND EDS2 AS CONTAINING A
 MANUAL MEANS OF DISCONNECT LOCATE DON
 THE OUTSIDE OF THE EQUIPMENT PER
 230.76,230.79.
 THESE ARE ALL NOTED AS BEING SHUNT TRIP,
 HOWEVER THESE ARE ALSO REQUIRED TO HAVE
 DISC?S PER ABOVE.
  
 59) NOTE: PLEASE VERIFY GROUND FAULT
 PROTECTION SHOWN FOR MDS1?
 PLEASE SEE 240.13, 230.95 ETC WHERE THE
 GFP IS REQUIRED AND NOTE REQUIRED. GFP
 IS NOT REQUIRED ON THIS MAIN, HOWEVER
 MAY BE INSTALLED.
  
 60) NOTE:PLEASE SEE 230.13, 230.95,
 700.7D, 700.26, NFPA-110 6.2.15*, WITH
 RESPECT TO GROUND FAULT PROTECTION ON
 EMERGENCY SIDE OF ED SYSTEM. PLEASE SEE
 SENSING OF GROUND FAULT AND ISOLATION OF
 NEUTRAL IS DESIRED, HOWEVER GFP ON THE
 EM SIDE O THE DISTRIBUTION SYSTEM IS NOT
 DESIRED. PLEASE SEE CODE COMMENTARY FOR
 FURTHER EXPLANATION.
  
 61) NOTE: PLEASE SEE RISER NOTES AS GFP
 IS BEING NOTED FOR ALL SYSTEMS AND ATS'S
 ON THE EM DISTRIBUTION SIDE. PLEASE SEE
 THE NOTE IS REFERENCING THE NEC ARTICLE
 517??
 PLEASE SEE 517 IS FOR HEALTH CARE
 FACILITIES AND DOES NOT APPLY FOR THIS
 BUILDING OR SCOPE.
 PLEASE VERIFY THE ABOVE AND ADJUST RISER
 AS NEEDED.
  
 62) NOTE: PLEASE PROVIDE GROUNDING
 ELECTRODE SYSTEM DETAIL FOR THE
 SEPARATELY DERIVED GENERATOR AS SHOWN.
 250.30, 250.50
  
 63) NOTE: PLEASEPROVIDE ATTACHMENT
 LOCATION FOR ALL TRANSFORMERS PER 250.30
 IT IS NOTED THAT A GROUND RISER WAS
 SHOWN.
  
 64) NOTE: PLEASE SEE 250.104 WHICH
 REQUIRE ALL OTHER METAL PIPING SYSTEMS
 TO BE BONDED.
 ( FIRE SPRINKLER ETC)
  
 65) NOTE: PLEASE SEE7.9.3.1
 GALVANIZED FUEL LINES SHALL NOT BE USED.
 NFPA-110 7.9
  
 66) NOTE: PLEASE SEE 450.3, MAX OCP FOR
 THE LINE SIDE OF TRANSFORMERS SHALL BE
 125%. IT IS PERMITTED TO GO THE NEXT
 SIZE UP WHEN THE AMPERAGE DOES NOT
 CORRELATE TO THE OCP DEVICE. PLEASE SEE
 EEL22 WHICH EXCEEDS THIS 125%
  
 67) NOTE: PLEASE SEE EE22 IS SHOWN AS
 400A ON RISER, YET SHOWN AS 225A ON
 PANEL SCHEDULE.
 215.5 PLEASE CORRELATE.
  
 68) NOTE: PLEASE SEE EE2 WHICH IS SHOWN
 AS 200A ON RISER AND SHOWN AS 225A ON
 PANEL SCHEDULE. PLEASE CORRELATE. 215.5
  
 69) NOTE: PLEASE SEE RISER SHOWS EH3 AS
 400A ON RISER AND 600A ON SCHEDULE.
 PLEASE CORRELATE.215.5
  
 70) NOTE: PLEASE SEE EL3, 200A ON RISER
 AND 225A ON SCHEDULE.
 215.5
  
 71) NOTE: PLEASE BE SURE TO GO THROUGH
 ALL FEEDS TO TRANSFORMERS. PLEASE SEE
 EH3, SHOWS A NEUTRAL CONDUCTOR WITH
 FEEDERS TO TRANSFORMER? PLEASE KNOW,
 THESE ARE SEPARATELY DERIVED SYSTEMS
 WHICH CREATE A NEW SYSTEM NEUTRAL.
 PLEASE SEE 250.6, 250.24B, 250.30 ETC.
 215.5
  
 72) NOTE: PLEASE SEE ATS-1 ON RISER IS
 NOTED AS 260A'S?
 PLEASE CORRELATE AS THIS IS FED FROM A
 200A DEVICE AND 260A'S IS NOT A COMMON
 SIZE.
 215.5
  
 73) NOTE: PLEASE SEE 240.3 AS DEVICES
 RATED OVER 800A'S SHALL CONTAIN
 CONDUCTORS RATED AT OR ABOVE THE OCP
 PROVIDED.
 PLEASE SEE FEEDER NOTED TO ATS-2 FROM
 EDS2.
 PLEASE ALSO SEE FEEDER FROM MDS2 WHICH
 SHOWS THE SAME FEEDER #7.
 PLEASE SEE MDS2 AS THIS FEEDER ON
 SCHEDULE DOES NOT CORRELATE WITH THIS.
 215.5
  
 74) NOTE: PLEASE SEE RISER SHOWS PANEL
 PC-2 AS 225A WITH 400A OCP FEEDING THIS
 PANEL.
 240, 215.5 ETC
  
 75) NOTE: PLEASE SEE PANEL PM-2 SHOWS
 400A OCP FEEDING A PANEL RATED AT
 225A'S.
 240.4,408,215.5.
  
 76) NOTE: PLEASE SEE PANEL SCHEDULE FOR
 PM-2, PLEASE SEE AMPS IS SHOWN AS BLANK.
 215.5
 PLEASE ALSO SEE THIS SAME PANEL MENTIONS
 FED FROM MSD2, WHEN IT SHOULD BE MDS2.
 (MISPRINT?)
  
 77) NOTE: PLEASE SEE PANEL PC-2 SHOWS
 AMP'S AS BLANK.
 215.5
 PLEASE ALSO SEE THIS SAME PANEL DETAILS
 BEING FED FROM MSD2, WHEN IT SHOULD READ
 MDS2. (MISPRINT?)
  
 78) NOTE: PLEASE ADJUST FEEDERS TO BOTH
 PC-2 AND PM-2 DEPENDING ON SIZE AND
 RATING OF PANELS. PLEASE SEE PREVIOUS
 COMMENTS WITH RESPECT TO OCP FEEDING
 THESE PANELS.
 215.5, 310.16, 240.4
  
 79) NOTE:PLEASE SEE KL2 WHICH MENTIONS
 FED FROM PM22? THIS DOES NOT CORRELATE
 WITH RISER?
  
 80) NOTE: PLEASE SEE 2002 NEC 210.8B3
 FOR ALL RECEPTS LOCATED IN KITCHENS
 15/20A 125VTO BE GFIPROTECTED.
 PLEASE KNOW, THIS IS REQUIRED WHETHER OR
 NOT THESE ARE COUNTER SPACE RECEPTACLES.
  
 81) NOTE: PLEASE SEE PL-2 WHICH SHOWS
 BEING FED FROM MSD2, INSTEAD OF MDS2.
 PLEASE ALSO SEE THE AMPERAGE IS SHOWN
 BLANK?
 PLEASE CORRELATE AND COMPLETE. 215.5
  
 82) NOTE: PLEASE SEE MISPRINT? FOR KP-2,
 MDS2, MSD2.
 215.5
  
 83) NOTE: PLEASE SEE RISER SHOWS HP-1,
 AND PANEL HP-2 AS 100A'S AND PANEL
 SCHEDULE SHOWS THIS AS 225A'S.?
 PLEASE CORRELATE. 215.5
  
 84) NOTE: PLEASE ALSO SEE NUMEROUS
 PANELS WHICH ARE SHOWN AS 100A'S, YET
 THESE ARE SHOWN AS 42 CIRCUIT PANELS.
 THE # OF CIRCUITS AVAILABLE FOR THESE
 100A?S PANEL SHOULD BE VERIFIED.
 215.5
  
 85) NOTE: PLEASE INDICATE ALL CONDUCTORS
 ON THE SECONDARY SIDE OF TRANSFORMERS.
 PLEASE PROVIDE A TRANSFORMER SCHEDULE
 SHOWING.
 215.5, 310.16, 240.4 ETC.
 THESE CAN NOT BE VERIFIED AT THIS TIME.
  
 86) NOTE: PLEASE CLARIFY THE TWO
 DIFFERENT PANEL/UNIT CALCULATIONS ON
 UNIT LAYOUT SHEETS?
 PLEASE ONLY SHOW ONE AND CORRELATE WITH
 NOTES BELOW.
 215.5
  
 87) NOTE: PLEASE SEE UNIT C WHICH SHOWS
 87A'S AND SHOWN AS 86 ON LOAD SUMMARY?
 215.5
  
 88) NOTE: PLEASE SEE ALL DP PANELS'
 SCHEDULES WHICH FEED HOUSE PANELS.
 PLEASE SEE HOUSE LOADS ARE SHOWN TAKING
 THE DE-RATINGFOR THE UNITS UNDER
 220.32. PLEASE KNOW THE HOUSE PANEL
 LOADS CAN NOT BE DERATED WITH THESE
 DWELLING UNITS.
 215.5
  
 89) NOTE: PLEASE SHOW ALL CONTINUOUS
 LOADS AND LARGEST MOTOR LOADS AT 125%.
 215.3, 230.42 ETC.
 PLEASE ADJUST ALL LOADS.
  
 90) NOTE:PLEASE SEE PANEL G1 MISSING
 FROM RISER. PLEASE ALSO SEE PREVIOUS
 COMMENTS ABOVE WITH RESPECT TO
 CORRELATION OF OCP AND PANEL SIZES.
 215.5
  
 91) NOTE: PLEASE SEE FIRE ALARM RISER
 WHICH INDICATES 120V POWER SUPPLY TO NAC
 PANELS, YET THESE ARE CIRCUITED ON THE
 277/480V PANELS?
  
 92) NOTE: PLEASE SEE NAC PANELS SHOWN ON
 RISER; HOWEVER THESE COULD NOT BE
 LOCATED ON PANEL SCHEDULE(S)?
 215.5
  
 93) NOTE: PLEASE SEE KEYNOTE WHICH
 MENTIONS KITCHEN/ REST, BUT ONE COULD
 NOT BE LOCATED?
  
  
 94) NOTE: PLEASE PROVIDE INFORMATION FOR
 LOADS, PANELS AND ELECTRICAL PROVISIONS
 BEING ALLOTTED FOR "FUTURE" TENANT
 SPACES.
 PLEASE SUBMIT LOAD FOR SQ FT ETC.
 215.5
  
 95) NOTE:PLEASE SEE RETAIL COMMON
 "SHELL AREAS"CONTAIN MINIMUM LIGHTING
 AS REQUIRED AND PERFIRE MARSHAL'S
 OFFICE,LS 101 7.8, 7.9 HOWEVER PLEASE
 SEE THESE AREAS ARE ALL BEING SHOWN
 CIRCUITED TO PANELSWHICH UNDER THE
 BASE BUILDING. PLEASE PROVIDE NOTES ON
 PLANS, AS ALL OF THIS INTERIOR
 CIRCUITING WILL BE REQUIRED TO BE
 REMOVED AND RE-CIRCUITED TO THE PANELS
 AND SERVICE THESE TENANT SPACES ONCE
 PERMITTED.
 CROSSING OVER OF SERVICES, COMMON AREA
 BRANCH CIRCUITS IS NOT PERMITTED.
 230.70, 225.25 ETC
  
 96) NOTE: PLEASE SEE 700.12E WHICH
 REQUIRES ALL EM/EXT LTS TO BE CIRCUITED
 TO THE LOCAL BRANCH CIRCUIT FEEDING ANY
 ONE AREA.
 PLEASE SEE THIS IS NOTED ON PLANS,
 HOWEVER THERE ARE A COUPLE OF AREAS
 WHICH DO NOT LEND TO THIS CIRCUITING.
 215.5
  
 97) NOTE: PLEASE KNOW, MANY OF THE ABOVE
 ITEMS ARE REDLINED ON ONE SET OF THE
 MEP'S FOR MANY OF THE SD'S, RECEPTS,
 LTS ETC AND LOCATIONS OF COMMENTS.
 PLEASE KNOW, THIS IS IN NO WAY ALL
 LOCATIONS WHICH MAY BE NEEDED. PLEASE GO
 OVER PLANS FOR ALL ITEMS.
  
 98) NOTE: PLEASE KNOW A DETAILED
 RESPONSE LETTER ON HOW ALL COMMENTS WERE
 ADDRESSED AND CLARIFICATIONS NEEDED.
 THIS WILL HELP IN EXPEDITING THE REVIEW
 PROCESS.
  
 99) NOTE: PLEASE SEE ALL COMMENTS FROM
 OTHER REVIEWS WHICH MAY AFFECT
 ELECTRICAL PLANS AND DESIGN.
  
 100) NOTE:ONCE ALL REVIEWS ARE
 COMPLETE AND BEFORE RESUBMITTING PLANS:
 "ALL OLD/VOIDED SHEETS SHALL BE REMOVED
 AND ONLY THE NEW REVISED SHEETS SHOULD
 BE INSERTED INTO THREE COMPLETE SETS FOR
 REVIEW AND STAMPING".
 ONE SET OF ALL OLD/VOIDED SHEETS WHICH
 ARE REMOVED SHOULD BE SUBMITTED FOR
 REFERENCE ALONG WITH THE NEW SETS. ALL
 VOIDED SHEETS MUST BE REMOVED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
2006-04-07 00:00:00PLANS WILL GO INTO FAILED STATUS.
  
 ** REVIEW TO CONTINUE ON 4/10.
  
 COMMENTS TO FOLLOW.
2006-04-05 00:00:00REVIEW COMMENCED
2006-03-29 00:00:00ONE ROLL OF PLANS IN ELECTRIC FOR
 REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2006-06-22 Cont ID  
Sent By   Date 2006-06-22 Time   Rev Time 1.00
Received By   Date 2006-06-22 Time   Sent To  
Notes
2006-06-22 00:00:00PLEASE SUBMIT DRAINAGE CALCULATIONS FOR
 WATER QUALITY TREATMENT AND FLOOD
 ROUTING.
  
 STEVE SARLEY
 (5610 494-1095

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-04-28 Cont ID  
Sent By mwennerg Date 2006-04-28 Time 11:01 Rev Time 0.00
Received By mwennerg Date 2006-04-28 Time 11:01 Sent To  
Notes
2006-04-28 00:00:00******DENIED******
  
 1) FIRE DEPARTMENT CONNECTIONS SHALL BE
 LOCATED NO FURTHER THAN 150' FROM A FIRE
 HYDRANT.
  
 2) BUILDING SHALL MEET ALL REQUIREMENTS
 FOR HIGHRISE STRUCTURES IN ACCORDANCE
 WITH APPLICABLE BUILDING CODES, AND NFPA
 101, CHAPTER 11.
  
 3) IN ADDITION TO ELECTRONIC
 SUPERVISION, DOUBLE CHECK DETECTOR
 ASSEMBLY SHALL BE SECURED WITH CHAIN AND
 LOCK.
  
 4) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 5) INCORRECT CODE EDITIONS ARE
 REFERENCED ON SHT M0.1. AS PART OF LIFE
 SAFETY, MEANS OF EGRESS TO COMPLY WITH
 NFPA 101, 2003 EDITION. NFPA 13, AND
 NFPA 72, 2002 EDITIONS SHALL BE
 REFERENCED.
  
 6) PLEASE VERIFY THE WIDTH OF DOOR 100B
 THAT ENTERS THE LOBBY.
  
 7) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN BUILDING REACHES (3) STORIES OR 30'
 IN HEIGHT.
  
 8) STANDPIPE CONNECTIONS TO BE 2 1/2"- 1
 1/2" REDUCER WITH CHAINS.
  
 9) WARNING SIGNS ARE REQUIRED IN
 ELEVATOR LOBBIES.
  
 10) PLEASE INDICATE ALL ELEVATORS THAT
 ARE STRETCHER ACCESSIBLE.
  
 11) SIGNS SHALL BE PROVIDED IN ALL
 STAIRWELLS INDICATING TOP, BOTTOM, FLOOR
 IDENTITY AND ROOF ACCESS.
  
 12) NO CUTTING OR WELDING OPERATIONS ARE
 PERMITTED WITHOUT APPROVAL OF THE BUREAU
 OF FIRE PREVENTION AND COMPLIANCE WITH
 NFPA 51B.
  
 13) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS AND GUARDS.
  
 14) IS THERE A DOOR LOCATED AT THE
 BOTTOM OF STAIR #1 AT EXIT CORRIDOR 112?
  
 THERE IS NOT ONE SHOWN.
  
 15) PLEASE PROVIDE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS IN TERMS OF CLASS A,B OR C.
  
 16) THE PARKING GARAGE SHALL COMPLY WITH
 APPLICABLE BUILDING CODES AND NFPA 88A.
  
 17) STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 18) PLEASE INDICATE THE QUANTITY AND
 TYPE OF CONTENTS THAT WILL BE STORED IN
 POOL EQUIPMENT ROOM.
  
 19) COOLING TOWERS SHALL COMPLY WITH
 NFPA 214.
  
 20) NO STORAGE ALLOWED IN ELECTRICAL OR
 MECHANICAL EQUIPMENT ROOMS THAT ARE
 SUBJECT TO SERVICING AND INSPECTIONS.
  
 21) PLEASE INDICATE ON PLANS REGARDING
 POOL DECK AREA TO BE SLIP RESISTANT. IN
 ADDITION, PROVIDE OCCUPANT LOAD FOR SAME
 AREA.
  
 22) ADDRESS IS REQUIRED ON BUILDING.
 PLEASE ILLUSTRATE OF PROVIDE NOTE TO
 THIS EFFECT ON ELEVATION SHEETS.
  
 23) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241. JOB
 SITE SHALL BE CLEANED OF DEBRIS DAILY.
  
 24) SOFFITS SHALL NOT INTERFERE WITH
 FIRE PROTECTION EQUIPMENT OR DEVICES.
  
 25) FIRE EXTINGUISHER CABINETS SHALL BE
 INSTALLED AT DISTANCES NOT TO EXCEED 75'
 TRAVEL DISTANCE.
  
 26) NO MENTION ON DOOR SCHEDULES
 REGARDING UL CERTIFIED CLOSERS ON RATED
 DOORS.
  
 27) ELEVATORS TO COMPLY WITH ASME A17.1.
  
 28) PLEASE PROVIDE ADDITIONAL
 INFORMATION AND CUT SHEETS FOR CO
 SENSORS IN PARKING GARAGE AREAS.
  
 29) DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 30) PLEASE ADD THE STACK EFFECT WORDING
 TO THE MECHANICAL PLANS.
  
 31) PLEASE CORRECT CODE EDITIONS ON ALL
 SHEETS.
  
 32) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 33) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE PUMP, FUEL AND
 ASSOCIATED EQUIPMENT.
  
 34) PLEASE PROVIDE INFORMATION THAT
 WOULD SUPPORT THE APPROVAL OF A 750 GPM
 FIRE PUMP SERVICING A 21 STORY BUILDING.
  
  
 35) BUILDING SHALL BE FULLY FIRE
 SPRINKLER PROTECTED. ANY AREAS NOT PART
 OF THIS SCOPE OF WORK MAY REQUIRE
 REMODEL ONCE OCCUPIED BY FUTURE TENANT.
  
 36) PLEASE INCLUDE LIFE SAFETY SHEETS TO
 ILLUSTRATE ALL ASPECTS OF MEANS OF
 EGRESS INCLUDING MAXIMUM TRAVEL
 DISTANCES.
  
 37) PLEASE INCLUDE THE FIRE SPRINKLER
 LAYOUT FOR TRASH AND LAUNDRY CHUTES.
  
 38) FIRE ALARM SYSTEM SHALL BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE.
 CERTIFICATE OR APPROVED COPY OF SUCH
 SHALL BE AVAILABLE PRIOR TO OR AT THE
 TIME OF FIRE ALARM FINAL.
  
 39) FIRE DEPARTMENT CONNECTIONS ARE
 BEING SHOWN ON THE BUILDING AND FIRE
 BACK FLOW PREVENTER ON FP 4.1. ARE THERE
 A TOTAL OF (3) CONNECTIONS?
  
 40) FIRE ALARM SYSTEM TO MEET THE NFPA
 72 REQUIREMENTS FOR SURVIVABILITY.
  
 41) PLANS DON'T APPEAR TO SHOW COMPLETE
 FIRE ALARM EQUIPMENT LAYOUT ON
 ELECTRICAL SHEETS.
  
 42) SMOKE DETECTORS IN LIVING UNITS ARE
 REQUIRED TO BE SINGLE STATION TYPE. ALL
 OTHER DEVICES SHALL BE TIED INTO THE
 FIRE ALARM SYSTEM.
  
 43) PLEASE PROVIDE FURTHER
 INFORMATION/CUT SHEETS FOR SMOKE GUARD
 SHUTTERS THAT ARE TIED INTO FIRE ALARM
 SYSTEM.
  
 44) THE GENERATOR SHALL COMPLY WITH NFPA
 110, STANDARD FOR EMERGENCY AND STANDBY
 POWER SYSTEMS.
  
 45) SMOKE DETECTORS SHALL BE LOCATED A
 MINIMUM OF (3)' FROM HVAC DIFFUSERS.
  
 46) FIRE ALARM SYSSTEM SHALL BE CLASS A
 OR FULLY ADDRESSABLE.
  
 47) ALL SHAFTS THAT ARE LARGE ENOUGH FOR
 PERSONS TO FALL INTO MUST BE MARKED
 SHAFTWAY IN "6" IN CHARACTERS.
  
 48) ALL FIRE DOORS/WINDOWS TO COMPLY
 WITH NFPA 80. PLEASE ADD NOTE TO PLANS.
  
 49) EXITS SIGNS SHALL BE LOCATED AT
 DISTANCES NOT TO EXCEED 100'.
  
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-23 Cont ID  
Sent By rbrown Date 2006-06-23 Time 20:40 Rev Time 0.00
Received By rbrown Date 2006-01-10 Time 10:10 Sent To  
Notes
2006-06-23 00:00:00PROJECT HAS BEEN 'SHELVED' AS OF 6/23/06
  
2006-02-03 00:00:00TO "COMM" BD#37/PLANS ON RACK
2006-01-11 00:00:00**CHECK WITH R BROWN OR L MARTINEZ**
 *BEFORE DOING FIRST REVIEW. 1/11/06. RB*
  
  
2006-01-10 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-24 Cont ID  
Sent By pkrauss Date 2006-03-24 Time 12:15 Rev Time 0.00
Received By pkrauss Date 2006-03-24 Time 11:46 Sent To  
Notes
2006-03-24 00:00:00DENIED:
 1.PLAN SHEET M0.1 MECHANICAL CODES,
 PLEASE NOTE, THE FOLLOWING CODES SHOULD
 READ AS FOLLOWS: NFPA 90A-2002, NFPA
 90B-2002.
  
 2.PLAN SHEET M2.1 EXHAUST FROM THE
 FIRE PUMP ROOM & THE TRASH ROOM
 TERMINATE OVER THE DOOR AREA.PER 2004
 FMC 401.5 EXHAUST OPENINGS SHALL BE
 LOCATED A MINIMUM OF 10 FT FROM LOT
 LINES.WHERE OPENINGS FRONT ON A STREET
 OR PUBLIC WAY, THE DISTANCE SHALL BE
 MEASURED TO THE CENTERLINE OF THE STREET
 OR PUBLIC WAY.PER 2004 FMC 401.5.2
 OUTDOOR EXHAUST AIR SHALL NOT BE
 DIRECTED ONTO WALKWAYS OR CREATE A
 NUISANCE.
  
 3.PLAN SHEET M2.1 FRESH AIR INTAKE
 SHALL COMPLY WITH 2004 FMC 401.5 &
 410.5.1.
  
 4.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2004 FMC
 TABLE 403.3.PROVIDE CALCUALTIONS FOR
 ALL COMMON, RESIDENTIAL, AND GARAGE
 AREAS.
  
 5.PLAN SHEET M2.2 EXHAUST TERMINATING
 FROM THE TRASH & RESTROOMS.PLEASE
 NOTE, THE TERMINATION IS BELOW A BALCONY
 WITH SLIDING GLASS DOORS.
  
 6.PLEASE CLARIFY RATING OF THE
 SEPARATION WALL BETWEEN THE TRASHOLD (RM
 218) & THE DIRECTOR OF SALES (RM 221).
 SHOW COMPLIANCE WITH NFPA 82-1999
 CHAPTER 3 SUB-SECTION 3-2.3. FIRE
 DAMPERS ARE NOT REQUIRED IN AREAS WHERE
 THE DUCT COMPLIES WITH 2004 FMC 607.5.3
 EXCEPTION #2 ITEMS 2.1 THROUGH 2.6.
 PLEASE ANNOTATE ON PLAN THE LOCATIONS
 THAT THIS WILL APPLY.
  
 7.PLAN SHEET M2.2 CLARIFY THE LINEN
 STORAGE AREA, INDICATE IF A LAUNDRY
 CHUTE WILL BE INSTALLED.
  
 8.PLEASE NOTE, LINEN & TRASH CHUTES
 SHALL COMPLY WITH NFPA 82-1999 CHAPTER 3
 SUB-SECTION 3-2.5.1, WHICH REQUIRES
 AUTOMATIC SPRINKLERS.
  
 9.PLAN SHEET M2.3, PLEASE INDICATE
 WHERE THE MAKE-UP AIR WILL COME FROM FOR
 THE GARAGE VENTILATION.
  
 10. PLANS FOR PARKING AREA (M2.3 & M2.4)
 DO NOT INDICATE WHERE THE CO SENOSRS
 WILL BE SET.PER 2004 FMC 404.1, THE
 ACTIVATION OF THE GARAGE EXHAUST BY
 CARBON MONOXIDE SENSORS SHALL BE AT A
 CONSENTRATION LEVEL NOT GREATER THAN
 25PPM. PLEASE INDICATE HOW THE SENSORS
 WILL BE TESTED.
  
 11. PLAN SHEET M2.5, M2.6, M2.16, &
 M2.17 INDICATE FIRE DAMPERS ON THE
 SUPPLY AND SMOKE EXHAUST DUCTS FOR THE
 COMMON AREAS. ACCORDING TO THE LEGEND ON
 PLAN SHEET M0.1 FIRE DAMPERS ARE THE
 ONLY DAMPERS INDICATED ON THE PLANS.
 PLAN SHEET M5.3, INDICATES THE FIRE
 DAMPERS DEPICTED ON THE PLANS SHOULD
 ACTUALLY BE COMBINATION FIRE/SMOKE
 DAMPERS.PLEASE VERIFY AND CORRELATE
 WITH SMOKE CONTROL SYSTEM.PLEASE
 INDICATE THE CORRECT SYMBOL AS INDICATED
 UNDER THE "MECHANICAL SYMBOLS" DEPICTED
 ON PLAN SHEET M0.1.
  
 12. PLAN SHEET M2.5, PLEASE CLARIFY THE
 SUPPLY AIR FROM AHU-1 WHICH SERVES THE
 CORRIDOR.IS THE INTENT OF THIS FOR
 COMPLIANCE WITH THE OUTSIDE AIR
 REQUIREMENTS OF 2004 FMC TABLE 403.3?
  
 13. PLAN SHEET M2.5 UNIT 503, PLEASE
 INDICATE LOCATION OF THE RETURN AIR BACK
 TO FCU-V5.
  
 14. PLAN SHEET M2.5, M2.6, M2.16, &
 M2.17 PLEASE INDICATE DUCT, GRILLE SIZE
 & CFM FOR THE SUPPLY DUCT TO THE
 BATHROOM AREAS.
  
 15. PLEASE NOTE DEPENDING ON THE
 RESPONSE TO ITEM 14 R/A TRANSFER GRILLS
 MAY NOT BE SIZED LARGE ENOUGH.
  
 16. PLAN SHEET M2.21 KEY NOTE 1
 REFERENCES DETAIL 07 ON PLAN SHEET M8.1.
 PLAN SHEET M8.1 WAS NOT SUBMITTED FOR
 REVIEW.
  
 17. PLAN SHEET M2.1 KEY NOTE 3 "RISER
 SIZE EQUAL TO VERTICAL RUN".PLEASE
 CLARIFY, "RISER SIZE EQUAL TO VERTICAL
 RUN", A RISER IS A VERTICAL RUN.SHOULD
 THIS READ, "RISER SIZE EQUAL TO
 HORIZONTAL RUN"?
  
 18. PLEASE SIZE ALL DUCTWORK AND PIPING.
  
 19. PLEASE PROVIDE ADDTIONAL INFORMATION
 ABOUT THE MECHANICAL ROOMS LOCATED ON
 THE ROOF (GENERATOR, AHU, PUMP COOLING
 TOWERS).ARE THESE AREAS ENCLOSED?
 PLEASE PROVIDE INFORMATION ON THE
 VENTILATION OF THESE AREAS SHOULD THEY
 BE ENCLOSED.
  
 20. PROVIDE ENERGY AND MANUAL J
 CALCULATIONS IN ACCORDIANCE WTIH 2004
 FBC CHAPTER 13.
  
 21. PLEASE PROVIDE SUBMITTALS FOR ALL
 EQUIPMENT & APPLIANCES.
  
 22. PLEASE PROVIDE FILL INFORMATION FOR
 THE EMERGENCY GENERATOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 1 Status   Date 2006-04-24 Cont ID  
Sent By kstevens Date 2006-04-24 Time 11:00 Rev Time 0.00
Received By kstevens Date 2006-04-19 Time 17:13 Sent To  
Notes
2006-04-24 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 MUNICIPAL CODE CITY WPB
  
 1. PLEASE SUBMIT A CODE SUMMARY
 INDICATING WHICH CODES THE BUILDING HAS
 BEEN DESIGNED BY.
 2. PLEASE DECLARE OCCUPANCY FOR THE
 BUILDING. SECTION 106.1.1.
 3. PLEASE SUBMIT A SUMMARY CHART
 SUPPLYING INFORMATION ON THE AMOUNT OF
 UNITS, UNIT TYPES WITH AMOUNT OF EACH,
 AND SHOW COMPLIANCE WITH SECTIONS
 11-9.1.2, 11-9.1.3, 11-9.1.4 & 11-9.2.3.
 INDICATE THE ROOM NUMBER FOR EACH
 REQUIREMENT, IE: ACCESSIBLE ROOM, ROOMS
 WITH ROLL IN SHOWERS, ACCOMODATIONS FOR
 PERSONS WITH HEARING IMPAIRMENTS ETC.
 THIS WILL BE REQUIRED FOR THE PERCENTAGE
 FOR ALL UNITS. (HOTEL)
 4. PLEASE INDICATE HOW ALL THE UNITS
 FROM THE PREVIOUS COMMENT WILL BE MADE
 AVAILABLE, AND IF THESE UNITS WILL BE
 SOLD AS CONDO'S WILL THEY BE MADE
 AVAILABLE AT ALL TIMES. SECTION 106.1.1.
 5. PLEASE INDICATE UNIT LOCATIONS AND
 ROOM NUMBERS CONSIDERED "CONDO
 OCCUPANCY". FAIR HOUSING WILL BE
 REQUIRED FOR THOSE UNITS. IF ALL UNITS,
 ALL UNITS SHALL BE REQUIRED TO MEET
 FHA-91 DESIGN MANUAL REQUIREMENTS ONE
 THRU SEVEN.
 6. SHTS A2.91 7 A2.10.1 INDICATE THE
 LOCATION OF ALL PRIMARY AND SECONDARY
 DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS.
 7. SHT A2.11.1 SHOW THE LOCATION OF
 SECONDARY ROOF DRAINS FOR THE AREA SOUTH
 OF THE ELEVATOR EQUIPMENT ROOM, RO2.
 SECTION 1107.
 8. SHTS A6.1.1 THRU A6.14.2 ALL WATER
 CLOSETS SHALL BE 1'6" OFF THE WALL TO
 THE CENTER LINE OF THE FIXTURE. THIS IS
 AN ABSOLUTE MENSUREMENT PER PAGE 6.5 FHA
 DESIGN MANUAL, AND FIGURE 28 SECTION
 11.3.1 FBC-2004. MEASUREMENTS SHOWN ARE
 1'63/8" OR 1'6" MIN. PLEASE CORRECT THE
 W/C MEASUREMENTS.
 9. SHTS A6.1.1 THRU A6.14.2 INDICATE THE
 CORRECT HEIGHT OF THE LAV AS 34" AS
 REQUIRED ON PAGE 7.52 FHA DESIGN MANUAL.
 10. SHTS A6.1.1 THRU A6.14.2 ALL
 ACCESSIBLE UNITS SHOW THE FOLLOWING:
 FOR W/C'S:
 A. 11-4.16.5 FLUSH CONTROLS
 B. 11-4.16.6 DISPENSERS
 FOR LAVS:
 A. 1-4.19.4 EXPOSED PIPES & SURFACES
 FOR TUBS:
 A. 11-4.20.5 CONTROLS
 B. 11-4.20.6 SHOWER UNIT
 FOR SHOWERS:
 A. 11-4.21.3 SEAT
 B. 11-4.21.4 GRAB BARS
 C. 11-4.21.5 CONTROLS
 D. 11-4.21.6 SHOWER UNIT
 E. 11-4.21.7 CURBS
 11. SUBMIT A LEGEND SHOWING THE AMOUNT
 OF UNITS, AND INDICATE UNIT TYPES.
 INDICATE THE AMOUNT OF ACCESSIBLE UNITS,
 AMOUNT OF UNITS WITH ROLL-IN SHOWER,
 AMOUNT OF UNITS WITH ACCOMMODATIONS FOR
 PERSONS WITH HEARING IMPAIRMENTS, AND
 UNITS FOR HOTEL, MOTEL AND CONDOMINIUM
 SPECIAL ACCESSIBILITY FEATURE. SECTIONS
 11-9.1.2, 11-9.1.3, 11-9.1.4 AND
 11-9.2.3. INDICATE THE UNIT NUMBERS FOR
 EACH REQUIREMENT.
 12. SHTS A6.1.1 THRU A6.14.2 ALL
 ACCESSIBLE UNITS, PER SECTION 11-9.2(7)
 KITCHENETTS INDICATE PARALLEL APPROACH.
 THIS IS NOT APPROVED PER SECTION
 11-4.24.5. FORWARD APPROACH IS REQUIRED,
 AND CABINET DOORS ARE NOT APPROVED IN
 THE CLEAR FLOOR SPACE. PLEASE SUBMIT AN
 ELEVATION SHOWING COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 13. SHTS A6.1.1 THRU A6.14.2 ALL FHA
 UNITS WITH A 2ND BATHROOM, SHOW THE
 OPENING DIMENSION FOR THE WATER CLOSET.
 MINIMUM 33" REQUIRED. W/C SHALL BE 18"
 OFF THE WALL TO CENTER OF FIXTURE, (IF
 WALL ADJACENT TO FIXTURE), OR MINIMUM OF
 18" OFF ONE FIXTURE AND MINIMUM OF 15"
 OFF THE OTHER FIXTURE. SEE PAGES 6.7,
 7.43, 7.44, 7.45, & 7.46.
 14. SHT A8.1.1 FINISH SCHEDULE FOR THE
 COMMON AREA IS NOT COMPLETE. SECTION
 106.1.1.
 15. SHT A8.2.1 REINFORCING AT THE TUB,
 SHOW REINFORCING AT THE HEAD OF THE TUB
 PER PAGE 6.9 FHA DESIGN MANUAL.
 16. SHT P0.1 CODE IS FBC-2004. CHANGE
 CODE REFERENCES.
 17. SHT P2.0 GAS PIPING FROM THE METER
 TO THE GAS RISERS. ONLY ONE RISER SHOWN.
 PLEASE CLARIFY. SECTION 106.1.1.
 18. SHTS P2.0 & P2.1 GREASE LINE INTO
 THE BUILDING SHOWS NO RISER FROM BELOW
 GRADE. SHT A2.1.1 DOES NOT SHOW A
 KITCHEN ON THE FIRST FLOOR. PLEASE
 CLARIFY. SECTION 106.1.1.
 19. SHT P2.1 GAS LINES SHOWN UNDER THE
 SLAB OF THE BUILDING. PLEASE INDICATE
 HOW THE PIPING WILL BE PRESSURE TESTED
 AND INSPECTED, THEN AFTER THE PIPING
 TEST AND INSPECTION, SHALL HAVE CONDUIT
 INSTALLED OVER THE PIPE AS REQUIRED IN
 SECTIONS 404.11 AND 406.4. SHOW THE
 CONDUIT DETAIL SHOWING COMPLIANCE WITH
 SECTION 404.11.
 20. SHT P2.1 5" COMBINATION WASTE/VENT
 STACK, (#33) SHOWS 4" ON THE HORIZONTAL
 OFFSET. PLEASE CLARIFY. SECTION 704.2
 THE SIZE OF THE DRAINAGE PIPING SHALL
 NOT BE REDUCED IN THE DIRECTION OF FLOW.
 21. SHT P2.2 GAS RISER DIAGRAM INDICATES
 THE GAS FOR THE KITCHEN FLOOR RISES UP
 ABOVE THE SECOND FLOOR. ONLY ON RISER
 SHOWN. PLEASE CORRELATE RISER AND FLOOR
 PLAN. SECTION 106.1.1.
 22. SHT P2.2 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTION 1106 & 1107 AND ALL SUBSECTIONS.
 SHOW SQUARE FOOTAGE AREA AND SHOW 1/2
 AREA OF ALL VERTICAL WALLS ADDED TO
 CALCULATIONS. IF SECONDARY ROOF DRAINS
 WILL BE SCUPPERS, THEY WILL BE SIZED PER
 SECTIONS 1101.7, 1107.3 AND TABLE
 1106.7. THE SIZING OF SCUPPERS CAN NOT
 BE DETERMINED WITH REFERENCE TO THE
 DEFLECTION OF THE ROOF. PLEASE NOTE IN
 CALCULATIONS.
 23. SHT P2.3 DOMESTIC WATER PUMP ROOM
 INDICATES A FLOOR DRAIN. NO PIPING IS
 SHOWN TO FLOOR DRAIN. SHOW PIPING ON THE
 FLOOR PLAN, WITH ALL PIPE SIZE, VENTING,
 TRAPS. SECTION 106.1.1.
 24. SHT P2.5 INDICATE THE LOCATION OF
 THE SECONDARY DRAINS FOR THE AREAS
 OUTSIDE UNITS T05 THRU T08. SUBMIT
 CALCULATION FOR PRIMARY AND SECONDARY
 DRAINS PER SECTIONS 1106 & 1107 AND ALL
 SUBSECTION. SHOW AREA TO BE DRAINED FOR
 EACH AREA DRAIN, AND SHOW 1/2 AREA OF
 ALL VERTICAL WALL INCLUDING PARAPETS TO
 EACH AREA. IF SECONDARY DRAINS ARE
 SCUPPERS, INDICATE THAT THE SIZE OF THE
 SCUPPERS HAVE BEEN CALCULATED PER
 SECTIONS 1101.7, 1107.3 AND TABLE
 1106.7. THE SIZING OF THE SCUPPERS CAN
 NOT BE DETERMINED WITHOUT REFERENCE TO
 THE DEFLECTION OF THE ROOF.
 25. SHT P2.6 RWL'S ARE NOT IDENTIFIED IN
 COLS. OUTSIDE UNIT T03. SECTION 106.1.1.
 26. SHT P2.16 AREA DRAINS OUTSIDE UNITS
 P02 AND P04 INDICATE PIPING DROPING TO
 THE 15TH FLOOR, BUT NO RWL SHOWN ON THE
 15TH FLOOR. PLEASE CLARIFY. SECTION
 106.1.1.
 27. SHT P2.16 INDICATE THE LOCATION OF
 THE SECONDARY DRAINS FOR THE AREAS
 OUTSIDE UNITS P02 THRU P04. SUBMIT
 CALCULATION FOR PRIMARY AND SECONDARY
 DRAINS PER SECTIONS 1106 & 1107 AND ALL
 SUBSECTION. SHOW AREA TO BE DRAINED FOR
 EACH AREA DRAIN, AND SHOW 1/2 AREA OF
 ALL VERTICAL WALL INCLUDING PARAPETS TO
 EACH AREA. IF SECONDARY DRAINS ARE
 SCUPPERS, INDICATE THAT THE SIZE OF THE
 SCUPPERS HAVE BEEN CALCULATED PER
 SECTIONS 1101.7, 1107.3 AND TABLE
 1106.7. THE SIZING OF THE SCUPPERS CAN
 NOT BE DETERMINED WITHOUT REFERENCE TO
 THE DEFLECTION OF THE ROOF.
 28. SHT P2.22 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. IF SECONDARY ROOF DRAIN ARE
 SCUPPERS, THEY WILL BE SIZED PER
 SECTIONS 1101.7, 1107.3, AND TABLE
 1106.7.
 29. SHT P2.22 FLOOR DRAIN AT COOLING
 TOWERS IS NOT AN APPROVED INDIRECT WASTE
 RECEPTOR. SECTIONS 802.3 & 802.3.2.
 FLOOR SINK OR HUB DRAIN REQUIRED.
 RECEPTOR SHALL BE LOCATED UNDER COOLING
 TOWER TO PREVENT STORM WATER FROM
 ENTERING.
 30. SHT P2.23 SHOW THE LOCATION OF ALL
 THE PRIMARY AND SECONDARY ROOF DRAINS.
 SUBMIT CALCULATION FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE AREA OF
 EACH DRAIN AND INDICATE 1/2 AREA OF ALL
 VERTICLE WALLS INCLUDING PARAPETS IN
 CALCULATION. IF SECONDARY DRAINS ARE
 SCUPPERS, THEY SHALL BE SIZED PER
 SECTIONS 1101.7, 1107.3 AND TABLE
 1106.7.
 31. SHT P2.24 SUBMIT CALCULATION FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTION 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW AREA OF EACH DRAIN AND
 SHOW 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS FOR EACH AREA IN
 CALCULATIONS.
 32. SHT P3.1 DETAIL #03 RISER #33 SHALL
 NOT DRAIN THROUGH THE WET VENT FOR THE
 BATHROOM FIXTURES.ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 33. SHT P4.1 SUBMIT A WATER RISER
 DIAGRAM TO REFLECT THE PIPING FOR THE
 1ST AND 2ND FLOORS. SECTION 106.3.5.1.3.
 SHOW ALL PIPE SIZES, VALVES, ETC.
 34. SHT P4.3 GAS RISER DIAGRAM. THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 SEPARATE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DEAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS. SOME SECTIONS DO NOT INDICAT
 THE LENGTHS. (SEE HIGHLIGHTED SECTIONS
 ON ONE SET OF PLANS)
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING IF USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTIONS 502 THRU 505.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 35. SHT P4.3 DETIAL 01 INDICATES A
 TYPICAL BASE OF STACK SOVENT. THIS IS
 NOT TYPICAL OF ANY BASE OF STACK FOR THE
 SOVENT SYSTEM. PLEASE CLARIFY. SECTION
 106.1.1.
 36. SHT P4.4 DETAIL 04 DOES NOT REFLECT
 THE FLOOR PLAN FOR THE WATER PIPING TO
 THE SHOWER AND TUB. NO DROPS FOR TUB AND
 SHOWER ARE SHOWN. PLEASE CORRELATE RISER
 AND FLOOR PLAN. SECTION 106.1.1.
 37. SHT P4.4 DETAIL 05 SANITARY RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE THE RISER AND THE FLOOR
 PLAN. SECTION 106.1.1.
 38. SHT P4.4 DETAIL 06 DOES NOT REFLECT
 THE FLOOR PLAN FOR THE WATER PIPING TO
 THE SHOWER AND TUB. NO DROPS FOR TUB AND
 SHOWER ARE SHOWN. PLEASE CORRELATE RISER
 AND FLOOR PLAN. SECTION 106.1.1.
 39. SHT P4.4 DETAIL 07 DOES NOT REFLECT
 THE FLOOR PLAN. RISER SHOWS A TUB, BUT
 THE FLOOR PLAN SHOWS A SHOWER. PLEASE
 CORRELATE RISER AND FLOOR PLAN. SECTION
 106.1.1.
 40. SHT P4.4 DETAIL 08 DOES NOT RELFECT
 THE FLOOR PLAN. RISER SHOWS A TUB, BUT
 THE FLOOR PLAN SHOWS A SHOWER. PLEASE
 CORRELATE RISER AND FLOOR PLAN. SECTION
 106.1.1.
 41. SHT P4.5 DETAIL 06 DOES NOT REFLECT
 THE FLOOR PLAN. RISER SHOWS HOT & COLD
 STUBB OUTS ON THE DROP TO THE LAV AND
 SHOWER. PLEASE CORRELATE RISER AND THE
 FLOOR PLAN. SECTION 106.1.1.
 42. SHT P4.7 SANITARY RISER DIAGRAM FOR
 THE SECOND FLOOR BATHROOM DOES NOT
 REFLECT THE FLOOR PLAN. FIRST W/C SHOWN
 PRIOR TO 4" SAN. DOWN ON THE FLOOR PLAN,
 BUT ON THE OTHER SIDE OF THE 4" SAN.
 DOWN ON THE RISER DIAGRAM. HDCP W/C FOR
 THE WOMEN'S TOILET ROOM IS NOT SHOWN ON
 THE RISER. PLEASE CORRELATE THE RISER
 AND THE FLOOR PLAN. SECTION 106.1.1.
 43. SHT P4.7 DETAIL 02 SANT. RISER
 DIAGRAM FOR 2ND FLOOR PLAN. AIR
 ADMITTENCE VALVES ARE NOT APPROVED AS
 SHOWN. SEE SECTIONS 917.3.1 AND 917.3.2
 917.3.1 LOCATION OF BRANCH.
 THE HORIZONTAL BRANCH DRAIN SHALL
 CONNECT TO THE DRAINAGE STACK OR
 BUILDING DRAIN A MAXIMUM OF FOUR BRANCH
 INTERVALS FROM THE TOP OF THE STACK.
 917.3.2 RELIEF VENT.
 THE HORIZONTAL BRANCH SHALL BE PROVIDED
 WITH A RELIEF VENT THAT SHALL CONNECT TO
 A VENT STACK, OR STACK VENT, OR EXTEND
 OUTDOORS TO THE OPEN AIR. THE RELIEF
 VENT SHALL CONNECT TO THE HORIZONTAL
 BRANCH DRAIN BETWEEN THE STACK OR
 BUILDING DRAIN AND THE MOST DOWNSTREAM
 FIXTURE DRAIN CONNECTED TO THE
 HORIZONTAL BRANCH DRAIN. THE RELIEF VENT
 SHALL BE SIZED IN ACCORDANCE WITH
 SECTION 916.2 AND INSTALLED IN
 ACCORDANCE WITH SECTION 905 . THE RELIEF
 VENT SHALL BE PERMITTED TO SERVE AS THE
 VENT FOR OTHER FIXTURE.
 44. SHT P4.7 DETAIL 01 SANT. RISER
 DIAGRAM COLLECTION DOES NOT REFLECT THE
 FLOOR PLAN. RISER SHOWS 10"(1600FU), BUT
 THE FLOOR PLAN SHOWS 8"(1000FU). THE
 BASE OF STACKS P/1, P/3, P/5, 9/7 DOES
 NOT REFLECT THE FLOOR PLAN FOR THE PRL
 PIPING. THE RISER DOES NOT SHOW THE
 CONNECTION FOR THE 5" COMBINATION
 WASTE/VENT STACK (NOTE 33). PLEASE
 CORRELATE INFORMATION ON THE RISERS AND
 THE FLOOR PLAN. SECTION 106.1.1.
 45. SHT P4.7 DETAIL 01 SANT. RISER
 DIAGRAM COLLECTION AIR ADMITTENCE VALVES
 ARE NOT APPROVED.SECTIONS 917.3.2 AND
 917.3.2.
 46. SHT P4.7 DETAIL 01 SANT. RISER
 DIAGRAM COLLECTION, PLEASE INDICATE
 WHERE THE CONTINUATION OF THE 2" UP TO
 SINK ON THE SECOND FLOOR IS LOCATED.
 SHOW PIPE SIZE, VENTING ETC. SECTION
 106.1.1.
 47. SHT P4.7 DETAILS 01 & 02 SHOW ALL
 PIPE SIZES OF ALL SECTIONS OF PIPE AND
 SHOW THE DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM. TABLES 710.1(1) & 710.1(2).
 48. SHT P5.1 DETAIL 08 PLEASE INDICATE
 CONDENSATE DRAIN FOR CONDENSATE.
 CONDENSATE SHALL NOT CONNECT TO SANITARY
 PER MUNICIPAL CODE SECTION 90-125(5).
 CONDENSATE SHALL BE PIPED OUT OF THE
 BUILDING SEPARATELY AND CONNECT TO THE
 STORM, CATCH BASIN, OR A DRYWELL. IF ITS
 A ROOF UNIT, IT CAN DRAIN TO A ROOF
 DRAIN. PLEASE CLARIFY.SECTION 106.1.1.
 49. SHT P5.2 DETAIL 01 DOES NOT REFLECT
 ANY BASE OF STACKS SHOWN ON THE FLOOR
 PLAN. PLEASE CORRLEATE WITH FLOOR PLAN.
 SECTION 106.1.1.
 50. SHT P5.2 DETAIL 06 FILTER FOR THE
 ICE MACHINE SHALL COMPLY WITH NSF 42.
 PLEASE SUBMIT MANUF. SPECIFICATION
 SHEETS. SECTION 611.1
 51. SUBMIT A WATER RISER DIAGRAM TO
 REFLECT THE PIPING FOR THE 1ST AND 2ND
 FLOORS. SECTION 106.3.5.1.3.
 52. SUBMIT A WATER RISER DIAGRAM T0
 REFLECT THE PIPING ON THE 14 TH & 15TH
 FLOORS. SECTION 106.3.5.1.3.
 53. SUBMIT A GREASE WASTE ISOMETRIC
 RISER DIAGRAM. SECTION 106.3.5.1.3.
 54. SUBMIT A BUILDING STORM ISOMETRIC
 RISER DIAGRAM SHOWING ALL PIPE SIZES,
 RWL CONNECTIONS AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM, AS WELL AS
 VERTICAL STORM RISERS. SECTION
 106.1.5.1.3.
 55. GREASE INTERCEPTORS SHALL BE SIZED
 BY LYNN MASSON ENVIRONMENTAL COMPLIANCE
 MANAGER. CONTACT HER AT (561) 822-2271,
 OR BY FAX (561) 772-2279, OR BY E-MAIL
 [email protected]. SUBMIT THE
 DETERMINATION SHEET FOR REVIEW WHEN
 RESUBMITTING PLANS REVIEW IN
 CONSTRUCTION SERVICES. WASTER ORD. 3434.
 57. SUBMIT THE DESIGN MANUAL FOR THE
 SOVENT SYSTEM. THIS IS REQUIRED TO MAKE
 SURE ALL CRITERIA FOR THE SYSTEM IS
 BEING MET. SECTION 106.1.1.
 58. PLANS DO NOT SEEM TO BE COMPLETE
 THIS REVIEW AND MORE COMMENTS WILL BE
 FOUTHCOMING WHEN PLANS ARE RESUBMITTED
 AS MORE INFORMATION IS AVAILABLE AND
 ACCORDING TO THE RESPONSE FROM THIS
 REVIEW.
 59. SHTS A6.1.1 THRU A6.14.2 ALL
 ACCESSIBLE BATHROOMS. SOME UNITS
 INDICATE THAT THE SHOWER IS NOT AN ADA
 ACCESSIBLE PLUMBING FIXTURE. ALL SHOWERS
 PROVIDED IN ACCESSIBLE UNITS SHALL BE
 ACCESSIBLE PER SECTION 11-4.21. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.21 AND ALL SUBSECTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE SUBMIT THE HIGHLIGHTED SET OF
 PLUMBING PLANS FROM FIRST REVIEW FOR
 COMPARISON TO HELP EXPEDITE THE SECOND
 REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***