Plan Review Stops For Permit 06010290 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2006-10-06 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-10-06 |
Time |
13:27 |
Rev Time |
0.00 |
Received By |
amorse |
Date |
2006-10-06 |
Time |
13:27 |
Sent To |
PC |
|
Notes |
2006-10-06 00:00:00 | | | | | REVISION | | | | EXTENSION OF HC RAMP |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2006-09-01 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-09-01 |
Time |
07:37 |
Rev Time |
0.00 |
Received By |
amorse |
Date |
2006-09-01 |
Time |
07:37 |
Sent To |
|
|
Notes |
2006-09-01 00:00:00 | | | | | PASSED | | | | CONTRACTOR SUBMITTED REQUIRED | | INFORMATION FOR REVISION | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2006-08-21 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-08-21 |
Time |
08:06 |
Rev Time |
0.00 |
Received By |
amorse |
Date |
2006-08-21 |
Time |
08:06 |
Sent To |
PC |
|
Notes |
2006-08-21 00:00:00 | | | | | DENIED | | | | 1) PROVIDE ATTACHMENT METHOD FOR METAL | | DECKING TO THE 1/4 X 4X4 ANGLE AND W8X15 | | BEAMS | | | | 2) PROVIDE INFORMATION ON MATERIAL TO BE | | APPLIED TO THE METAL DECK (CONCRETE, | | LIGHT WEIGHT CONCRETE, ETC.) | | | | 3) ROOFING PERMIT MAY ALSO REQUIRE A | | REVISION AS THE ATTACHMENT METHOD AND | | SUBSTRATE WILL BE DIFFERENT THAN WHAT | | WAS APPLIED FOR. | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2006-06-19 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-06-19 |
Time |
12:26 |
Rev Time |
0.00 |
Received By |
amorse |
Date |
2006-06-19 |
Time |
12:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-05-05 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-05-05 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
amorse |
Date |
2006-05-05 |
Time |
08:33 |
Sent To |
|
|
Notes |
2006-05-05 00:00:00 | | | | | DENIED | | | | NOTES 1 AND 4 WHERE ADDRESSED BUT MORE | | INFORMATION IS NEED, NOTE 3 WAS NOT | | ADDRESSED. | | | | 1) HANDRAIL EXTENTION IS SHOWN ON A2-1.0 | | BUT SIZE IS NOT SHOWN. PLEASE SHOW THAT | | MIN REQUIREMENT IS MET PER 11-4.8.5(2) | | FBC | | A2-1.0 SHOWS FOOTING UNDER CMU.THERE ARE | | NO DETAILS FOR FOOTING ONTHIS DETAIL OR | | 03/A0-0 | | LANDINGS ON RAMPS ARE REQUIRED TO BE NO | | LESS THAN 72" PER 11-4.8.4(2) FBC | | | | 3) PLEASE SEE A1-1.0 AT DOOR 114 AND | | RAMP MANUVERING REQUIRES A MINIMUM 24" | | OF LEVEL AREA ON THE LATCH SIDE ALSO | | APPROCH FROM THE PUSH SIDE REQUIRES A | | MINIMUM 12" AT THE LATCH SIDE OF DOOR | | (SEE FIG. 25 (A)AND(B) IN CHAPTER 11) | | FBC | | | | 4) IN BUILDINGS WITH MULTIPLE ACCESSIBLE | | ENTRANCES, ACCESSIBLE PARKING SPACES | | SHALL BE DISPERSED AND LOCATED CLOSEST | | TO THE ACCESSABLE ENTRANCES PER 11-4.6.2 | | FBC | | | | NEW NOTES: | | | | 1) DOOR 114 IS AN INTERIOR DOOR THAT | | WILL BE USED AS AN EXTERIOR DOORAS | | SUCH PLEASE PROVIDE PRODUCT APPROVALS | | PER 9B-72 F.A.C. ALSO STATE WIND DESIGN | | CRITERIA AND COMPONENT AND CLADING PSF"S | | FOR DOOR ON DRAWING PER 1603.1.4 FBC | | | | 2) APPLICABLE CODES SECTION OF PAGE T1 | | AND LS0-0 DO NOT MATCH SHOULD READ FBC | | 2004 PLEASE CLARIFY | | | | 3) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT IS REQUIRED PRIOR TO | | A PERMIT BEING ISSUED. ALTHOUGH IT IS | | GOOD FOR 1 YEAR FROM DATE OF ISSUE WORK | | MUST COMMENCE WITHIN 90 DAYS. PLEASE | | RE-RECORD | | | | 4) PLEASE NOTE THAT NO FURTHER PLAN | | REVIEWS WILL BE DONE UNTIL FALSE ALARM | | FEES ARE PAID AND FINANCE DEPT HOLD IS | | REMOVED CONTACT EFRAIM GARCED @ 805-1320 | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-04-03 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-04-03 |
Time |
11:43 |
Rev Time |
0.00 |
Received By |
amorse |
Date |
2006-04-03 |
Time |
11:43 |
Sent To |
PC |
|
Notes |
2006-04-03 00:00:00 | | | | | DENIED | | | | 1) PROVIDE DETAILS ON RAMP CONSTRUCTION | | FOOTING DETAILS, DECK CONSTRUCTION, TIE | | DOWNS, HANDRAIL ETC. | | | | 2) RAMPS SHALL HAVE HANDRAIL ON BOTH | | SIDE PER 11-4.8.5 FBC | | | | 3) COMPLY WITH MANUVERING DISTANCE | | REQUIREMENTS AT RAMP LANDING PER | | 11-4.13.6 FBC | | | | 4) SHOW LOCATION OF ACCESSABLE PARKING | | SPACE AND ROUTE TO NEW ACCESSABLE RAMP | | AND ENTRANCE | | | | 5) DOOR HARDWARE SHALL COMPLY WITH | | 11-4.13.9 | | | | 6) DOOR SCHEDULE SHOWS #104 AND #114 AS | | PAIRS PLEASE CLARIFY | | | | 7) PROVIDE DETAILS OF RECEPTION COUNTER | | FOR COMPLIANCE WITH ACCESSABILITY PER | | 11-7.2 | | | | 8) PROVIDE ACCESSABILITY REQUIREMENTS | | FOR KITCHEN SINK PER 11-4.24 | | | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2007-06-26 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2007-06-26 |
Time |
17:29 |
Rev Time |
1.00 |
Received By |
jleahy |
Date |
2007-06-26 |
Time |
17:29 |
Sent To |
|
|
Notes |
2007-06-26 17:30:29 | AS BUILTFOR JOBJL |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
P |
Date |
2007-05-29 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2007-05-29 |
Time |
20:29 |
Rev Time |
1.30 |
Received By |
jleahy |
Date |
2007-05-29 |
Time |
20:28 |
Sent To |
|
|
Notes |
2007-05-29 20:30:13 | NOTE TO INSPECTOR | | | | PLAN STATES NO NEW CIRCUITS, IF NEW ONES ARE ADDED THEN | | NEW PANEL | | SCHEDULES WILL BE REQUIRED. | | | | JAKE |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
F |
Date |
2006-11-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-11-20 |
Time |
18:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-11-20 |
Time |
18:28 |
Sent To |
PC |
|
Notes |
2006-11-20 18:46:12 | *** UNSAT *** | | | | | | 1) NOTE: PLEASE KNOW THAT THE ENGINEER SHOWN ON PLANS | | SUBMITTED FOR REVISIONS TO ELECTRICAL LIGHTING PLANS IS | | NOT THE ENGINEER OR FIRM OF RECORD. | | PLEASE KNOW THIS IS NOT PERMITTED UNDER FLORIDA | | STATUTES 471.025. | | MUST BE THE ENGINEER/ FIRM OF RECORD OR PLANS CAN BE | | TAKEN OVER BY ANOTHER ENGINEERING HOWEVER PLEASE CALL | | TO GO OVER ANY SUCH REQUIREMENTS FOR THIS. | | | | ** PLEASE KNOW AS FYI, THE TITLE BLOCK FOR ENGINEERING | | FIRM AS SHOWNIS MISSING LICENSE NUMBER FOR FIRM AS | | REQUIRED UNDER FLORIDA ADMINISTRATIVE CODE | | 61G15-23.002, AND FLORIDA STATUTES 471.023. THIS IS FOR | | INFORMATIONAL PURPOSE ONLY. | | | | | | IF THERE ARE ANY QUESTIONS ON THE ABOVE COMMENTS, OR IF | | THE COMMENTS ARE NOT CLEAR IN ANY FASHION, PLEASE DO | | NOT HESITATE IN CONTACTING THIS REVIEW WITH QUESTIONS | | OR COMMENTS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPARTMENT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2006-09-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-09-20 |
Time |
12:49 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-09-20 |
Time |
12:49 |
Sent To |
PC |
|
Notes |
2006-09-20 00:00:00 | REVISION FOR CHANGING CONDUIT TO ALSO | | ALLOW MC CABLE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2006-09-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-09-17 |
Time |
10:57 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-09-17 |
Time |
10:57 |
Sent To |
PC |
|
Notes |
2006-09-17 00:00:00 | ELEC REV/AS-BUILTS OK. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2006-05-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-05-03 |
Time |
20:08 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-05-03 |
Time |
19:23 |
Sent To |
|
|
Notes |
2006-05-03 00:00:00 | OLD VOIDED ELECTRICAL SHEETS REMOVED, | | ELECTRICAL PLANS STAMPED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-02-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-02-10 |
Time |
21:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-02-10 |
Time |
20:59 |
Sent To |
|
|
Notes |
2006-02-10 00:00:00 | IN ELEC FOR REVIEW | | ******** UNSAT ********** | | | | 1)NOTE: PLEASE INDICATE ALL CIRCUITING | | ON PLANS AND CORRELATE A PANEL SCHEDULE | | OR PANEL SCHEDULE(S) TO BE SUBMITTED. | | NEW OR EXISTING PANELS BEING ADDED FOR | | WORK/ CIRCUITS? | | 215.5 | | | | 2)NOTE: PLEASE SEE MANY NEW 30A RECEPTS | | ARE INDICATED. PLEASE ALSO SEE PLANS | | INDICATE 60A RECEPTS ALSO WITH OUT ANY | | INFORMATIONFOR LOADS DEVICES ETC. | | PLEASE SUBMIT LOAD CALCUALTIONS FOR ALL | | EXISITNG AND NEW TO BE ADDED. PLEASE | | ALSO SPECIFY USE OF THE NEW DEVICES AND | | LOADS. | | 215.5,220 | | | | 3)NOTE: PLEASE SEE SHEET T-1 WHICH | | INDICATES A 2004 NFPA-101. PLEASE KNOW, | | AS OF JAN 1ST, 2005 WE ARE CURRENTLY | | UNDER THE 2003 NFPA-101. | | | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2006-06-21 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-06-21 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-06-21 |
Time |
09:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2006-05-05 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-05-05 |
Time |
15:02 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-05-05 |
Time |
15:02 |
Sent To |
|
|
Notes |
2006-05-05 00:00:00 | ******DENIED****** | | | | 1) RESPONSE TO COMMENT 1- PLEASE NOTE | | THAT NFPA 101, 2003 EDITION SHALL BE | | REFERENCED. 2004 EDITION SHALL BE | | APPLIED TO THE FLORIDA FIRE PREVENTION | | CODE. | | | | 2) PLEASE PROVIDE INFORMATION REGARDING | | STORAGE AND APPLICATION OF MATERIALS | | USED IN JEWELRY PROCESS. PLEASE INDICATE | | QUANTITY AND TYPE OF MATERIAL. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-02-15 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-02-15 |
Time |
14:24 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-02-15 |
Time |
14:24 |
Sent To |
|
|
Notes |
2006-02-15 00:00:00 | ******DENIED****** | | | | 1) NFPA 101, AND NFPA-1 2003 EDITION | | SHALL BE REFERENCED. PLEASE MAKE | | CORRECTION ON SHT T-1. | | | | 2) RAMPS AND STAIRS SHALL HAVE HANDRAILS | | ON BOTH SIDES. | | | | 3) MONTGOMERY HALL OCCUPANT LOAD IS | | INCORRECT. CALCULATION WAS BASED ON 5 | | SQ'/PERSON, HOWEVER 15 SQ'/PERSON SHOULD | | BE USED. | | | | 4) PLEASE INDICATE THE INTERIOR FINISH | | CLASSIFICATION OF WALLS AND CEILINGS, | | CLASS A,B,OR C. | | | | 5) SEPARATE SHOP DRAWING AND PERMITS | | REQUIRED FOR FIRE SPRINKLER AND FIRE | | ALARM REMODEL. | | | | 6) EXIT DOORS SERVING OCCUPANT LOADS | | GREATER THAN 100 SHALL HAVE PANIC | | HARDWARE. PLEASE SHOW ON DOOR SCHEDULE. | | | | | | 7) A CURRENT OCCUPANT LOAD SIGN MAY BE | | OBTAINED FROM THE BUREAU OF FIRE | | PREVENTION IF DIFFERENT FROM LAST | | CACULATION. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLANS REVIEW (%^1) 805-6722 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2006-06-15 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-06-15 |
Time |
14:13 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-06-15 |
Time |
14:36 |
Sent To |
|
|
Notes |
2006-06-15 00:00:00 | PAUL SCHMITZ | | [email protected] | | FBC 2004 PLUMBING CODE PLAN REVIEW | | FBC2004 FUEL GAS CODEPLAN REVIEW | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | PROVISO: | | | | SEE LETTER DATED 6-2-06 FROM HERRICK | | BROS. CONST. JEFF WADE. | | ARMORY ARTS CNTR STAFF IS STILL IN | | DEVELPOPING STAGES FOR STUDIOS 110, 111. | | REVISIONS TO FOLLOW WHEN DESIGN IS | | COMPLETED. | | | | QUESTIONS 561-805-6692 | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
N |
Date |
2006-05-02 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-05-02 |
Time |
15:09 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-05-02 |
Time |
15:19 |
Sent To |
|
|
Notes |
2006-05-02 00:00:00 | PLAN REVIEW DATED 5-2-06 FOR GAS | | | | RESPONSE DATED 3-28-06 BY NELSON LONG | | GAS IS NOT IN THE SCOPE OF RENOVATION |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2006-03-11 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-03-11 |
Time |
11:11 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-03-11 |
Time |
11:11 |
Sent To |
|
|
Notes |
2006-03-11 00:00:00 | PAUL SCHMITZ | | FBC 2004 FUEL GAS CODE, PLAN REVIEW | | DENIED | | | | 1)SHT A1-1.0 SEC 415 GROUP H-5 | | OCCUPANCY. ROOM #110,111 JEWELRY MFG. | | STUDIO. PROVIDE IN DETAIL ALL | | INFORMATION REQUIRED FOR GROUP H-5 USE. | | | | 2) SEC 106.3.5.2 GAS: ISOMETRIC | | REQUIRED. | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
2006-01-09 00:00:00 | OK PER F MITNER 1-8-06 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
10 |
Status |
N |
Date |
2007-06-26 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-26 |
Time |
15:07 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-26 |
Time |
15:07 |
Sent To |
E |
|
Notes |
2007-06-26 15:07:47 | TO 'JLEAHY" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2007-05-29 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-29 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-29 |
Time |
16:13 |
Sent To |
E |
|
Notes |
2007-05-29 16:15:09 | TO "E" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2006-11-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-11-20 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-11-20 |
Time |
11:04 |
Sent To |
E |
|
Notes |
2006-11-20 11:05:15 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-10-03 |
Time |
17:13 |
Sent To |
|
|
Notes |
2006-10-03 00:00:00 | TO "COMM" BD#27 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2006-09-26 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-09-26 |
Time |
16:27 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-09-26 |
Time |
16:27 |
Sent To |
P |
|
Notes |
2006-09-26 00:00:00 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2006-09-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-09-13 |
Time |
13:16 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-09-13 |
Time |
13:16 |
Sent To |
E |
|
Notes |
2006-09-13 00:00:00 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2006-08-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-08-17 |
Time |
17:57 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-08-17 |
Time |
17:57 |
Sent To |
Z |
|
Notes |
2006-08-17 00:00:00 | TO "AMORSE" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-06-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-06-07 |
Time |
16:15 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-06-07 |
Time |
16:15 |
Sent To |
|
|
Notes |
2006-06-07 00:00:00 | TO "BOB"#14--EXPEDITED PLANS-- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-05-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-05-01 |
Time |
16:46 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-05-01 |
Time |
16:46 |
Sent To |
|
|
Notes |
2006-05-03 00:00:00 | TO "BOB"#15 | 2006-05-01 00:00:00 | WAITING FOR "BOB" | | EXPEDITED PLANS--PER RBROWN |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2006-04-03 |
Time |
|
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-01-10 |
Time |
16:21 |
Sent To |
|
|
Notes |
2006-03-24 00:00:00 | MOVED TO BOB #3 | | | 2006-02-01 00:00:00 | TO "COMM" BD#13 | 2006-01-10 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2006-02-23 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2006-02-23 |
Time |
17:21 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2006-02-23 |
Time |
17:21 |
Sent To |
|
|
Notes |
2006-02-23 00:00:00 | NO MECHANICAL PLANS.2/23/06 HM. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2006-10-18 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2006-10-18 |
Time |
07:55 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2006-10-18 |
Time |
07:55 |
Sent To |
|
|
Notes |
2006-10-18 07:55:50 | AS BUILTS |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2006-06-16 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-06-15 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-06-15 |
Time |
14:37 |
Sent To |
|
|
Notes |
2006-06-16 00:00:00 | PAUL SCHMITZ | | [email protected] | | FBC 2004 PLUMBING CODE PLAN REVIEW | | FBC2004 FUEL GAS CODEPLAN REVIEW | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | PROVISO: | | | | SEE LETTER DATED 6-2-06 FROM HERRICK | | BROS. CONST. JEFF WADE. | | ARMORY ARTS CNTR STAFF IS STILL IN | | DEVELPOPING STAGES FOR STUDIOS 110, 111. | | REVISIONS TO FOLLOW WHEN DESIGN IS | | COMPLETED. | | | | SEE RESPONSE DATED 6-16-06 FROM LYNN | | MASSON. | | EXEMPTION GRANTED DUE TO SMALL AMOUNT OF | | WASTE WATER DISCHARGE, FOR CHEMICALS IN | | PRINT MAKING STUDIO 108, DARK ROOM 109. | | | | QUESTIONS 561-805-6692 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2006-05-03 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-05-03 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-05-02 |
Time |
15:21 |
Sent To |
|
|
Notes |
2006-05-02 00:00:00 | | | PAUL SCHMITZ | | [email protected] | | FBC 2004 PLUMBING CODE PLAN REVIEW | | FBC2004 FUEL GAS CODEPLAN REVIEW | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | UNSAT | | PREVIOUS COMMENTS DATED 3-11-06 NOTE #3 | | SHT A1-1.0 RM 109 IS LABELED AS A DARK | | ROOM WITH A SOLUTION BENCH. | | | | 3) SHT A1-1.0 ROOM ,109 DARK ROOM. | | SEC 803.2 NEUTRALIZING DEVICE REQUIRED | | FOR CORROSIVE WASTE. | | CONTACT W P BEACHWATERPLANT LAB | | SUPERVISORINDUSTRIAL COORDINATOR, | | LYNN MASSON | | OFFICE 561-822-2271 | | E-MAIL [email protected] | | | | NOTE #4 NOT ADDRESSED. | | 4)SHT A1-1.0 SEC 415 GROUP H-5 | | OCCUPANCY. ROOM #110,111 JEWELRY MFG. | | STUDIO. PROVIDE IN DETAIL ALL | | INFORMATION REQUIRED FOR GROUP H-5 USE. | | | | 5-2-06 REVISIONS COMMENT UNSAT WAITING | | FOR A CALL FROM ARCHITE5CT | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2006-03-11 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-03-11 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-03-11 |
Time |
09:57 |
Sent To |
|
|
Notes |
2006-03-11 00:00:00 | | | PAUL SCHMITZ | | [email protected] | | FBC 2004 PLUMBING CODE PLAN REVIEW | | FBC2004 FUEL GAS CODEPLAN REVIEW | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | DENIED | | | | 1) 106.1.1 INFORMATION ON CONSTRUCTION | | DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE | | DIMENSIONED AND DRAWN UPON SUITABLE | | MATERIAL. ELECTRONIC MEDIA DOUCMENTS ARE | | PERMITTED TO BE SUBMITTED WHEN APPROVED | | BY THE BUILDING OFFICAL. CONSTRUCTION | | DOUCMENTS SHALL BE OF SUFFICENT CLARITY | | TO INDICATE THE LOCATION, NATURE AND | | EXTENT OF THE WORK PROPOSED AND SHOW IN | | DETAIL THAT ITWILL CONFORM TOTHE | | PROVISIONS OF THIS CODE AND RELEVANT | | LAWS, ORDINANCES, RULES AND REGULATIONS | | AS DETERMINED BY THE BUILDING OFFICAL ( | | SEE ALSO SECTION 106.3.5) | | 2) SHT LS0-0 REQUIRED MINIMUM FACILITIES | | SHOW THE LOCATION OF THE REQUIRED D/F | | AND S/S, REFERENCED ON CODE SUMMARY. | | 3) SHT A1-1.0 ROOM #108,109 DARK ROOM. | | SEC 803.2 NEUTRALIZING DEVICE REQUIRED | | FOR CORROSIVE WASTE. | | CONTACT W P BEACHWATERPLANT LAB | | SUPERVISORINDUSTRIAL COORDINATOR, | | LYNN MASSON | | OFFICE 561-822-2271 | | E-MAIL [email protected] | | 4)SHT A1-1.0 SEC 415 GROUP H-5 | | OCCUPANCY. ROOM #110,111 JEWELRY MFG. | | STUDIO. PROVIDE IN DETAIL ALL | | INFORMATION REQUIRED FOR GROUP H-5 USE. | | 5) SHT A1-1.0 CONFERENCE RM SINK. | | 11-4.24 SINKS. | | 11-4.24.1 GENERAL. | | SINKS REQUIRED TO BE ACCESSIBLE BY | | SECTION 11-4.1 SHALL COMPLY WITH SECTION | | 11-4.24. | | 11-4.24.2 HEIGHT. | | SINKS SHALL BE MOUNTED WITH THE COUNTER | | OR RIM NO HIGHER THAN 34 INCHES (865 MM) | | ABOVE THE FINISH FLOOR. | | 11-4.24.3 KNEE CLEARANCE. | | KNEE CLEARANCE THAT IS AT LEAST 27 | | INCHES (685 MM) HIGH, 30 INCHES (760 MM) | | WIDE, AND 19 INCHES (485 MM) DEEP SHALL | | BE PROVIDED UNDERNEATH SINKS. | | 11-4.24.4 DEPTH. | | EACH SINK SHALL BE A MAXIMUM OF 6? | | INCHES (165 MM) DEEP. | | 11-4.24.5 CLEAR FLOOR SPACE. | | A CLEAR FLOOR SPACE AT LEAST 30 INCHES | | BY 48 INCHES (760 MM BY 1219 MM) | | COMPLYING WITH SECTION 11-4.2.4 SHALL BE | | PROVIDED IN FRONT OF A SINK TO ALLOW | | FORWARD APPROACH. THE CLEAR FLOOR SPACE | | SHALL BE ON AN ACCESSIBLE ROUTE AND | | SHALL EXTEND A MAXIMUM OF 19 INCHES (485 | | MM) UNDERNEATH THE SINK (SEE FIGURE | | 11-32). | | 11-4.24.6 EXPOSED PIPES AND SURFACES. | | HOT WATER AND DRAIN PIPES EXPOSED UNDER | | SINKS SHALL BE INSULATED OR OTHERWISE | | CONFIGURED SO AS TO PROTECT AGAINST | | CONTACT. THERE SHALL BE NO SHARP OR | | ABRASIVE SURFACES UNDER SINKS. | | 11-4.24.7 FAUCETS. | | FAUCETS SHALL COMPLY WITH SECTION | | 11-4.27.4. LEVER-OPERATED, PUSH-TYPE, | | TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED | | MECHANISMS ARE ACCEPTABLE DESIGNS. | | 6)SEC 106.3.5.1.3 (3,4.)COMMERICAL | | BUILDINGS: PLUMBING, SANITARY; WATER. | | ISOMETRIC REQUIRED. | | 7) SEC 106.3.5.2 GAS: ISOMETRIC | | REQUIRED. | | 8)PLEASE SEE ANY POSSIBLE COMMENTS FROM | | OTHER TRADES WHICH MAY AFFECT PLUMBING | | PLANS. | | END OF COMMENTS, QUESTIONS 561-805-6692 | | | | |
|
|