Plan Review Details - Permit 06010186
Plan Review Stops For Permit 06010186
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-05-19 Cont ID  
Sent By mjacobs Date 2006-05-19 Time 12:19 Rev Time 0.00
Received By mjacobs Date 2006-05-19 Time 12:14 Sent To PC
Notes
2006-05-19 00:00:00 
 PROVISO:
  
 THIS PERMIT IS FOR THE WORK ON THE
 COMMON WALLS/FLOORS AND CEILING ONLY.
 ALL OTHER WORK IN THE UNIT WILL REQUIRE
 A SEPERATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-04-28 Cont ID  
Sent By mjacobs Date 2006-04-28 Time 16:53 Rev Time 0.00
Received By mjacobs Date 2006-04-28 Time 14:58 Sent To  
Notes
2006-04-28 00:00:00 
 1) ONCE AGAIN, A DETAIL DRAWING OF THE
 ONE HOUR FIRE RATED WALL. (UL ASSEMBLY)
 THE INFORMATION SUBMITTED IS STILL NOT
 COMPLETE. WHAT TYPE OF MATERIAL WILL THE
 DRYWALL BE FASTENED TO? IS IT WOOD/METAL
 OR CONCRETE? THE BB SECTION ON PAGE 4
 SHOWS A DOUBLE WALL AND THE DETAIL ON
 SHEE 5 SHOWS A SINGLE WAL.
 SEE NOTES FROM ELECTRICAL REVIEWER.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-04 Cont ID  
Sent By mjacobs Date 2006-04-04 Time 08:35 Rev Time 0.00
Received By mjacobs Date 2006-04-04 Time 05:56 Sent To  
Notes
2006-04-04 00:00:00 
 1) SUBMIT A DETAIL UL ASSEMBLY DRAWING
 FOR THE ONE HOUR RATED WALL. THE
 INFORMATION SUBMITTED IS INADEQUATE.
  
 2) ON SHEET #5 WHAT TYPE OF FIRE
 BLOCKING MATERIALS WILL BE USED AT THE
 FLOORS AND CEILINGS. STATE THIS
 INFORMATION ON THE DRAWINGS. IN
 REFERENCE TO THE STATEMENT "FIRE RATED
 INSULATION AS PER CODES" EXPLAIN WHERE
 AND HOW THE INSULATION WILL BE
 INSTALLED. SAYING AS PER CODE IS NOT
 SUFFICENT INFORMATION. SEE NOTES FROM
 ELECTRIACAL REVIEWER.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-20 Cont ID  
Sent By mjacobs Date 2006-01-20 Time 09:39 Rev Time 2.50
Received By mjacobs Date 2006-01-20 Time 07:08 Sent To  
Notes
2006-01-20 00:00:001) DUE TO THE FACT THAT EACH UNIT HAS
 ITS' OWN PCN NUMBER AND WILL NEED REPAIR
 WORK , A SEPERATE PERMIT APPLICATION HAS
 TO BE FILED FOR EACH UNIT. THIS IS BASE
 ON THE DESCRIPTION OF THE WORK
 SUBMITTED. IF THIS APPLICATION IS FOR
 THE WORK IN THE COMMON AREA ONLY, THE
 DESCRIPTION ON THE APPLICATION AND THE
 SCOPE OF WORK WILL HAVE TO BE ALTERED.
  
 2) SUBMIT A DETAIL DRAWING SHOWING THE
 AREA WHERE THE WORK WILL BE DONE. ALL
 DRAWINGS AND DATA PRREPARED BY AN
 ARCHITECT OR ENGINEER SHALL BE AFFIXED
 WITH THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE AS STATE LAW REQUIRES.
 WPB AMENDMENTS 106.1.2 SEE SECTION 106
 FOR ADDITIONAL INFORMATION.
  
 3) NOTE: IF SMOKE TRAVEL THROUGH THE A/C
 SYSTEM A MECHINICAL INSPECTOR WILL HAVE
 TO DO A PRE-INSPECT TO MAKE SURE THE A/C
 SYSTEM IS OK.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-06-08 Cont ID  
Sent By dpalmer Date 2006-06-08 Time 12:13 Rev Time 0.00
Received By dpalmer Date 2006-06-08 Time 11:49 Sent To PC
Notes
2006-06-08 00:00:00REDLINED PLANS.
  
 NO ELECTRICAL WIRING BEING DONE. IF ANY
 WIRING OR BOXES ARE DAMAGED, PLANS ARE
 TO BE REVISED ACCORDINGLY.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-05-19 Cont ID  
Sent By btrobaug Date 2006-05-19 Time 06:47 Rev Time 0.75
Received By btrobaug Date 2006-05-19 Time 06:11 Sent To  
Notes
2006-05-19 00:00:00 
 DENIED
  
 PLEASE INDICATE THE EXISTING LOCATION OF
 ELECTRICAL FIXTURES IN THE PROPOSED WORK
 AREA SO THAT CODE REQUIREMENTS OF THE
 NEC 2002 CAN BE REVIEWED FOR PER FBC
 EXISTING BUILDING CODE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/805-6731
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-04-28 Cont ID  
Sent By dpalmer Date 2006-04-28 Time 10:55 Rev Time 0.00
Received By dpalmer Date 2006-04-28 Time 10:55 Sent To  
Notes
2006-04-28 00:00:00******* UNSAT 3RD REVIEW *******
  
 1) NOTE: PLEASE SEE THE SAME NOTES APPLY
 AS PREVIOUS REVIEW DATED 4/3/06.
  
 2) NOTE: PLEASE SEE PRINT OUT'S ATTACHED
 FROM THE STATE'S WEBSITE FROM THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION.
  
 PLEASE SUBMIT THE INFORMATION AS
 REQUESTED.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-03 Cont ID  
Sent By dpalmer Date 2006-04-03 Time 11:55 Rev Time 0.00
Received By dpalmer Date 2006-04-03 Time 11:55 Sent To  
Notes
2006-04-03 00:00:00**UNSAT **
  
 1) NOTE : PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCK(S).
 FAC 61G1-16.004, FS 481.219
 PLEASE SEE MISSING THE PRINTED NAME AND
 LICENSE # OF ARCHITECT.
 PLEASE SEE MISSING CERIFICATE OF
 AUTHORIZATION / FIRM LICENSE #.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2) NOTE: PLEASE SEE PLANS DO NOT
 INDICATE OR SHOW ANY DETAIL FOR
 ELECTRICAL WORK WHICH IS BEING APPLIED
 FOR.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-10 Cont ID  
Sent By dpalmer Date 2006-01-10 Time 08:10 Rev Time 0.00
Received By dpalmer Date 2006-01-10 Time 08:10 Sent To  
Notes
2006-01-10 00:00:00****** UNSAT ********
  
  
 1)NOTE: PLEASE PROVIDE PLANS DONE BY AN
 ARCHITECT AS REQUIRED UNDER FS 481.229
 PLEASE PROVIDE AN ELECTRICLA LAYOUT FOR
 ALL NEW. PLEASE SEE FBC FOR EXISTING
 BLDGS/UNITS ETC AND POSSIBLE BRINGING OF
 ALL ELECTRICAL ETC UP TO CURRENT CODE.
 PLEASE KNOW, ELECTRICLA IS NOW UNDER THE
 2002 NEC.
 PROVIDE MIN REQUIRED.
  
 2)NOTE: PLEASE KNOW, AS PER PALM BEACH
 COUNTY PROPERTY APPRAISER'S SITE, EACH
 UNIT IS AN INDIVIDUALLY OWNED UNIT AND
 MUST HAVE 6 INDIVIDUAL APPLICATIONS.
 PLEASE SEE BLDG REVIEW COMMENTS.
  
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-01-09 Cont ID  
Sent By nmccray Date 2006-01-09 Time 11:54 Rev Time 0.00
Received By nmccray Date 2006-01-09 Time 11:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-18 Cont ID  
Sent By adarroug Date 2006-05-18 Time 11:44 Rev Time 0.00
Received By adarroug Date 2006-05-18 Time 11:44 Sent To  
Notes
2006-05-18 00:00:00TO "BOB"#11

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-24 Cont ID  
Sent By adarroug Date 2006-04-24 Time 11:55 Rev Time 0.00
Received By adarroug Date 2006-04-24 Time 11:55 Sent To  
Notes
2006-04-27 00:00:00TO BOB3
2006-04-24 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-03 Cont ID  
Sent By adarroug Date 2006-04-03 Time 10:34 Rev Time 0.00
Received By adarroug Date 2006-04-03 Time 10:34 Sent To  
Notes
2006-04-03 00:00:00TO "BOB"#14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-01-20 Time   Rev Time 0.00
Received By adarroug Date 2006-01-06 Time 16:47 Sent To  
Notes
2006-01-06 00:00:00TO "BOB"#3

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-05-18 Cont ID  
Sent By tgordon Date 2006-05-18 Time 15:44 Rev Time 0.15
Received By tgordon Date 2006-05-18 Time 15:44 Sent To  
Notes
2006-05-18 00:00:00*** FIRE DAMAGE ***
 NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-05 Cont ID  
Sent By tgordon Date 2006-05-05 Time 10:24 Rev Time 0.15
Received By tgordon Date 2006-05-05 Time 10:24 Sent To  
Notes
2006-05-05 00:00:00*** DENIED ***
 1) PLEASE OBTAIN A MECHANICAL PERMIT AND
 HAVE PRE-INSPECTION OF AIR CONDITIONING
 EQUIPMENT BEFORE THE BUILDING PERMIT IS
 ISSUED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-06-01 Cont ID  
Sent By jleech Date 2006-06-01 Time 13:41 Rev Time 0.00
Received By jleech Date 2006-06-01 Time 13:41 Sent To  
Notes
2006-06-01 00:00:00PROVISO;
 PLUMBING PERMIT REQUIRED.
 SECOND ROUGH INSPECTION REQUIRED
 FOR TUB SET.

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-05-05 Cont ID  
Sent By jleech Date 2006-05-05 Time 07:32 Rev Time 0.00
Received By jleech Date 2006-05-05 Time 07:32 Sent To  
Notes
2006-05-05 00:00:00DENIED;
 1. SEE ELECTRICAL NOTES 1 AND 2.
 2. DISCRIPTION OF WORK STATES MOVING THE
 TOILET AND TUB TO NEW LOCATIONS, PLEASE
 SHOW A DRAWING OF OLD LAYOUT, TYPE OF
 PIPING MATERIAL TO BE USED. ARE THE
 DESIGNATED WASTE STACKS THE SAME FOR NEW
 LAYOUT? PLEASE SHOW RISER DIAGRAMS.
 THIS IS THE THIRD REQUEST FOR SCOPE OF
 WORK DETAILS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-04-04 Cont ID  
Sent By jleech Date 2006-04-04 Time 12:13 Rev Time 0.00
Received By jleech Date 2006-04-04 Time 12:12 Sent To  
Notes
2006-04-04 00:00:00DENIED;
  
 1.SEE ELECTRICAL PLAN REVIEWER'S COMMENT
 ONE. TITLE BLOCK, PRINTED NAME AND TITLE
 BLOCK.
 2.PLEASE SHOW THE SCOPE OF WORK TO BE
 DONE BY THE PLUMBING CONTRACTOR. WAS THE
 DRAINAGE PIPE DAMAGED? WATER PIPE TYPE.
 ARE ALL PLUMBING FIXTURES TO BE
 INSTALLED IN SAME LOCATION? MORE
 INFORMATION IS REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-10 Cont ID  
Sent By pschmitz Date 2006-01-07 Time 07:38 Rev Time 0.00
Received By pschmitz Date 2006-01-07 Time 07:38 Sent To  
Notes
2006-01-07 00:00:00DENIED
 SEE ELECTRICAL PLAN REVIEW NOTES.