Plan Review Details - Permit 06010176
Plan Review Stops For Permit 06010176
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-03-09 Cont ID  
Sent By amorse Date 2006-03-09 Time 15:30 Rev Time 0.50
Received By amorse Date 2006-03-09 Time 15:30 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-02-24 Cont ID  
Sent By amorse Date 2006-02-24 Time 10:23 Rev Time 0.50
Received By amorse Date 2006-02-24 Time 10:23 Sent To PC
Notes
2006-02-24 00:00:001ST REVISION TO BLDG REVIEW
  
 DENIED
  
 1) REMOVAL OF INTERMEDIATE STRUCTURAL
 HORIZONTAL STEEL TUBE INCREASES THE
 OPENING HEIGHT. THIS IN TURN EXCEEDS THE
 MAX. FRAME HEIGHT OF THE WINDOW WALL
 SYSTEM (SEE PAGE 1 OF 8 IN NOA)
  
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-02-10 Cont ID  
Sent By amorse Date 2006-02-10 Time 10:59 Rev Time 0.50
Received By amorse Date 2006-02-10 Time 10:59 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-01 Cont ID  
Sent By amorse Date 2006-02-01 Time 11:16 Rev Time 1.00
Received By amorse Date 2006-02-01 Time 11:16 Sent To PC
Notes
2006-02-01 00:00:00 
  
 DENIED
  
  
 1) CONTRACTOR SHALL SUBMIT 2 COPIES OF
 THE FLORIDA STATE COVER SHEET WITH STATE
 APPROVAL AND FL# AS PART OF THE PRODUCT
 APPROVALS
  
 A) W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 2) CONTRACTOR SHALL SPECIFY THE SYSTEM
 TO BE USED IN THE NOA. SPECIFY BUY
 MARKING THE GLASS TYPE,ANCHOR OPTION,ETC
 THAT WILL BE USED AND WILL COMPLY WITH
 THE ENGINEERED WIND LOADS ON DRAWINGS
  
 3) IF A DESIGN PROFESSIONAL REGISTERED
 TO PRACTICE UNDER CHAPTER 481 OR 471 OF
 THE FLORIDA STATUTES THEN HE OR SHE
 SHALL AFFIX THEIR OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS AND
 SPECIFICATIONS PER 106 FBC 2004
  
 4) AN ENGINEER PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS SHALL
 INDICATE THEIR NAME AND LICENCE #, AS
 WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (1)-(5)
  
 5) ADD NOTE ON GLASS CONTRACTORS
 DRAWINGS, ALUMINUM CONTACTING METALSTHAT
 ARE NOT COMPATIBLE SHALL BE PROTECTED
 PER 2003.8.4 FBC 2004
  
  
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 13:57 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 13:57 Sent To B
Notes
2006-03-09 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-23 Cont ID  
Sent By adarroug Date 2006-02-23 Time 17:15 Rev Time 0.00
Received By adarroug Date 2006-02-23 Time 17:15 Sent To B
Notes
2006-02-23 00:00:00TO "AMORSE" DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-09 Cont ID  
Sent By adarroug Date 2006-02-09 Time 12:17 Rev Time 0.00
Received By adarroug Date 2006-02-09 Time 12:17 Sent To B
Notes
2006-02-09 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-01 Cont ID  
Sent By amorse Date 2006-02-01 Time 14:37 Rev Time 0.00
Received By amorse Date 2006-01-06 Time 16:29 Sent To  
Notes
2006-01-06 00:00:00TO "MISC" BOX#1