Plan Review Details - Permit 06010175
Plan Review Stops For Permit 06010175
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-10-10 Cont ID  
Sent By amorse Date 2006-10-10 Time 07:43 Rev Time 0.00
Received By amorse Date 2006-10-10 Time 07:43 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-06-13 Cont ID  
Sent By amorse Date 2006-06-13 Time 10:04 Rev Time 0.50
Received By amorse Date 2006-06-13 Time 10:03 Sent To PC
Notes
2006-06-13 00:00:00 
  
 DENIED
  
 1) PER 1609.1.4 FBC GAZED OPENINGS
 LOCATED WITHIN 30 FT. OF GRADE SHALL
 MEET THE REQUIREMENTS OF THE LARGE
 MISSILE IMPACT TEST. THOSE BETWEEN 30
 AND 60 FT. SHALL MEET THE REQUIREMENTS
 OF THE SMALL MISSILE TEST. THE FILM THAT
 WAS SUPPLIED WILL NOT MEET THE LARGE
 MISSILE PROVISIONS THAT ARE REQUIRED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-04 Cont ID  
Sent By amorse Date 2006-05-04 Time 13:27 Rev Time 1.00
Received By amorse Date 2006-05-04 Time 13:27 Sent To PC
Notes
2006-05-04 00:00:00 
  
 DENIED
  
 1) THE OCCUPANT LOAD OF THE AREA
 SERVICED BY THE EXISTING DOOR (1ST FLR)
 REQUIRES THAT THE DOOR SHALL SWING INTHE
 PATH OF EXIT TRAVEL PER 1008.1.2 FBC OR
 605.4.2 EXIST BLDG. FBC
  
 2) WINDOWS LOCATED WITHIN 30 FT OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE
 MISSLE TEST PER 1609.1.4 FBC
  
 ***NOTE: FILM ON GLASS WILL NOT MEET
 THESE REQUIREMENTS AS THE FRAME IS PART
 OF ENTIRE ASSEMBLY AND ALSO REQUIRES
 IMPACT PROTECTION***
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-03 Cont ID  
Sent By amorse Date 2006-02-03 Time 13:07 Rev Time 2.00
Received By amorse Date 2006-02-03 Time 13:07 Sent To PC
Notes
2006-02-03 00:00:00 
  
 DENIED
  
 1) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL PAGE
 THAT IS RELEVANT. THESE SHOULD INCLUDE
 THE FLORIDA STATE APPROVAL COVER PAGES,
 AND THE PRODUCT NOA THAT LISTS THE
 SYSTEM COMPONENTS/ FASTENER LIST PAGES,
 THE PAGES WITH THE CHOSEN ASSEMBLY/
 SYSTEM TO BE USED AND THE GENERAL
 LIMITATIONS PAGE. ALL CAN BE FOUND ON
 WWW.FLORIDABUILDING.ORG
  
 2) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 WPB
 AMENDMENTS TO FBC 2004
  
 3) PROVIDE A COMPLIANT EGRESS PLAN
  
 4) BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8" SCALE PER 106.1.3 WPB
 AMENDMENTS TO THE FBC 2004
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-06 Cont ID  
Sent By adarroug Date 2006-10-06 Time 08:24 Rev Time 0.00
Received By adarroug Date 2006-10-06 Time 08:24 Sent To B
Notes
2006-10-06 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-09 Cont ID  
Sent By adarroug Date 2006-06-09 Time 13:44 Rev Time 0.00
Received By adarroug Date 2006-06-09 Time 13:44 Sent To B
Notes
2006-06-09 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-02 Cont ID  
Sent By adarroug Date 2006-05-02 Time 12:41 Rev Time 0.00
Received By adarroug Date 2006-05-02 Time 12:40 Sent To B
Notes
2006-05-02 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-03 Cont ID  
Sent By amorse Date 2006-02-03 Time 13:07 Rev Time 0.00
Received By amorse Date 2006-01-06 Time 16:01 Sent To  
Notes
2006-01-06 00:00:00TO "MISC" BOX#1